Plan Review Details - Permit 01010142
Plan Review Stops For Permit 01010142
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-24 Cont ID  
Sent By hpiskura Date 2001-01-24 Time 14:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-18 Cont ID  
Sent By hpiskura Date 2001-01-18 Time 14:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-18 00:00:00SPECIFIC CONNECTION DETAILS ARE
 NECESSARY FOR THE METAL STUDS TO THE
 EXISTING STRUCTURE SUCH AS THAT SHOWN
 IN SECTION 1 SHEET A-5 AND ANYWHERE
 ELSE THEY WILL BE SUSPENDED OR LOADED
 IN TENSION.
  
 WHAT LOADS WILL BE IMPOSED BY THE
 "VOLKSWAGEN THAT WILL BE RECESSED INTO
 THE WALL" SHOWN ON SHEET A-4?

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 17:12 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 17:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-19 Cont ID  
Sent By dpalmer Date 2001-01-19 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2001-01-19 Time 14:56 Sent To  
Notes
2001-01-19 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2)NOTE: PLEASE SUBMIT CLARIFICATION FOR
 EQUIPMENT GROUNDING BETWEEN MAIN
 DISCONNECT AND PANEL "B" AND PANEL"B"
 TO PANEL"A".
  
 3)NOTE: PLEASE SUBMIT CLARIFICATION ON
 TRACK LIGHTING LOADS. PLEASE SHOW PER
 220-12B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-01-24 Cont ID  
Sent By hpiskura Date 2001-01-24 Time 14:47 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-24 Cont ID  
Sent By mcarsill Date 2001-01-24 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2001-01-24 Time 12:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-08 Cont ID  
Sent By mcarsill Date 2001-01-08 Time 17:14 Rev Time 0.00
Received By mcarsill Date 2001-01-08 Time 16:39 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. SOFFITS PLANNED ARE NOT TO
 INTERFERE WITH FIRE SPRINKLER HEAD
 DISCHARGE PATTERNS.
 2) PLEASE PROVIDE MORE DETAILS ON
 RECESSED VOLKSWAGON PLANNED FOR THE
 INTERIOR.
 3) ENTRY DOORS TO SWING IN THE DIRECTION
 OF EXIT TRAVEL. THE SALES FLOOR AREA OF
 2,636 SQUARE FEET DIVIDED BY 30 SQUARE
 FEET PER PERSON PROVIDES FOR AN OCCUPANT
 LOAD OF 87 PERSONS. DOORS MUST SWING
 IN THE DIRECTION OF EXIT TRAVEL.
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS.
 5) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST,
 DOOR LEADING TO STOCKROOM IS NOT SUBJECT
 TO LOCKING, AN AISLE OF AT LEAST 44
 INCHES WIDE IS PROVIDED AND MAINTAINED,
 AND ONLY 50 PERCENT OF EXIT ACCESS IS
 PROVIDED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-22 Cont ID  
Sent By ndenmark Date 2001-01-22 Time 11:46 Rev Time 0.33
Received By ndenmark Date 2001-01-22 Time 11:46 Sent To  
Notes
2001-01-22 00:00:00PROVISO:
 NOTIFICATION OF FAN SHUT DOWN BY HORN
 AND STROBE REQUIRED PER 1996 90A 4-4.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-26 Cont ID  
Sent By jleech Date 2001-01-26 Time 07:49 Rev Time 0.50
Received By jleech Date 2001-01-26 Time 07:49 Sent To  
Notes
2001-01-26 00:00:00PROVISO;
  
 FIXED LADDER FOR MUST BE A SHIPS LADDER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By jleech Date 2001-01-17 Time 16:37 Rev Time 0.50
Received By jleech Date 2001-01-17 Time 16:37 Sent To  
Notes
2001-01-17 00:00:00WATER HEATER TO BE READILY ACCESSIBLE.
 94 SPC SEE DEFINITIONS PAGE 27. IF
 INSTALLED ABOVE CIELING A SHIPS LADDER
 MUST BE PERMITTLY INSTALLED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-01-24 Cont ID  
Sent By hpiskura Date 2001-01-24 Time 14:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***