| Plan Review Stops For Permit 01010142 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-24 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-18 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-18 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-18 00:00:00 | SPECIFIC CONNECTION DETAILS ARE | | | NECESSARY FOR THE METAL STUDS TO THE | | | EXISTING STRUCTURE SUCH AS THAT SHOWN | | | IN SECTION 1 SHEET A-5 AND ANYWHERE | | | ELSE THEY WILL BE SUSPENDED OR LOADED | | | IN TENSION. | | | | | | WHAT LOADS WILL BE IMPOSED BY THE | | | "VOLKSWAGEN THAT WILL BE RECESSED INTO | | | THE WALL" SHOWN ON SHEET A-4? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-25 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-25 |
Time |
17:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-19 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-19 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2001-01-19 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | | | | 2)NOTE: PLEASE SUBMIT CLARIFICATION FOR | | | EQUIPMENT GROUNDING BETWEEN MAIN | | | DISCONNECT AND PANEL "B" AND PANEL"B" | | | TO PANEL"A". | | | | | | 3)NOTE: PLEASE SUBMIT CLARIFICATION ON | | | TRACK LIGHTING LOADS. PLEASE SHOW PER | | | 220-12B. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-24 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-24 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-24 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-01-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-08 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-08 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | PLANS. SOFFITS PLANNED ARE NOT TO | | | INTERFERE WITH FIRE SPRINKLER HEAD | | | DISCHARGE PATTERNS. | | | 2) PLEASE PROVIDE MORE DETAILS ON | | | RECESSED VOLKSWAGON PLANNED FOR THE | | | INTERIOR. | | | 3) ENTRY DOORS TO SWING IN THE DIRECTION | | | OF EXIT TRAVEL. THE SALES FLOOR AREA OF | | | 2,636 SQUARE FEET DIVIDED BY 30 SQUARE | | | FEET PER PERSON PROVIDES FOR AN OCCUPANT | | | LOAD OF 87 PERSONS. DOORS MUST SWING | | | IN THE DIRECTION OF EXIT TRAVEL. | | | 4) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATIONS. | | | 5) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST, | | | DOOR LEADING TO STOCKROOM IS NOT SUBJECT | | | TO LOCKING, AN AISLE OF AT LEAST 44 | | | INCHES WIDE IS PROVIDED AND MAINTAINED, | | | AND ONLY 50 PERCENT OF EXIT ACCESS IS | | | PROVIDED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-22 |
Time |
11:46 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-01-22 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2001-01-22 00:00:00 | PROVISO: | | | NOTIFICATION OF FAN SHUT DOWN BY HORN | | | AND STROBE REQUIRED PER 1996 90A 4-4.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-26 |
Time |
07:49 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-26 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2001-01-26 00:00:00 | PROVISO; | | | | | | FIXED LADDER FOR MUST BE A SHIPS LADDER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-17 |
Time |
16:37 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-17 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | WATER HEATER TO BE READILY ACCESSIBLE. | | | 94 SPC SEE DEFINITIONS PAGE 27. IF | | | INSTALLED ABOVE CIELING A SHIPS LADDER | | | MUST BE PERMITTLY INSTALLED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-24 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|