Plan Review Details - Permit 01010069
Plan Review Stops For Permit 01010069
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-04-26 Cont ID  
Sent By jwitmer Date 2001-04-26 Time 08:07 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-02-01 Cont ID  
Sent By jwitmer Date 2001-02-01 Time 17:30 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-01 00:00:00PROVISO: OWNER, ARCH, CONT TO SIGN
 ENERGY CALS BEFORE ISSUANCE, MEETS THE
 20% DISPROPORTIONATE COST TO NOT HAVE TO
 MOVE WALL IN MENS HC RESTROOM AT LATCH
 SIDE OF DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By jwitmer Date 2001-01-17 Time 13:58 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-17 00:00:00BILDING PLAN REVIEW:
 1). SBC 104.2.2- DOOR SCHEDULE IS MISS-
 ING INFORMATION FOR DOOR #3.
 2). NOTE DOOR #3, IF USED IN A EXIT
 ACCESS THE NET CLEAR OPENING CAN NOT BE
 LESS THAN 32".
 3). FL. ACCESSIBILITY CODE 4.13.5-
 CLEAR WIDTH OF DOORS, THE DOORS LEADING
 INTO THE HANDICAPPED RESTROOMS WILL
 REQUIRE A CLEAR 32" OPENING, MEASURING
 FROM THE FACE OF THE DOOR TO THE DOOR
 STOP ON THE OTHER JAMB.
 4). FL. ACCESIBILITY CODE 4.13.6-
 MANEUVERING CLEARENCES AT DOORS- SEE
 RESTROOM DOORS INTERIOR LATCH SIDE
 REQUIRES 18" MINIMUM.
 5). SEE FL. ACCESSIBILITY FOR DISPRO-
 PORTIONATE COST 20%. SEE ATTACHMENT.
 6). SBC 704.3 OFFICE #119 WILL REQUIRE
 A 1 HR WALL FOR TENANT FIRE SEPERATION.
 WILL NEED A DETAIL FOR THE WALL FROM
 FLOOR TO CEILING, UL LISTING OR GYPSUM
 NUMBER.
 7). ENERGY CALS SIGNED BY THE PERSON PRE
 PARING THE COMPLIANCE CALULATION.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561) 659- 8096 EX 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-04-09 Cont ID  
Sent By dpalmer Date 2001-04-09 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2001-04-09 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-01 Cont ID  
Sent By dpalmer Date 2001-02-01 Time 19:35 Rev Time 0.00
Received By dpalmer Date 2001-02-01 Time 19:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-08 Cont ID  
Sent By dpalmer Date 2001-01-08 Time 18:22 Rev Time 0.00
Received By dpalmer Date 2001-01-08 Time 18:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-02-05 Cont ID  
Sent By lsmith Date 2001-02-05 Time 11:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-02-27 Cont ID  
Sent By mcarsill Date 2001-02-27 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2001-02-27 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-02-14 Cont ID  
Sent By mcarsill Date 2001-02-14 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2001-02-14 Time 14:08 Sent To  
Notes
2001-02-14 00:00:001) PREVIOUS PLAN REVIEW COMMENTS BY
 THIS OFFICE NOT RESPONDED TO.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-25 Cont ID  
Sent By mcarsill Date 2001-01-25 Time 11:53 Rev Time 0.00
Received By mcarsill Date 2001-01-25 Time 11:53 Sent To  
Notes
2001-01-25 00:00:001) PLEASE EXPLAIN DEAD-END OCCURRENCE
 ADJACENT TO STAFF WORK AREA.
 2) NO INTERIOR FINISH SHOWN ON PLANS.
 INTERIOR FINISH ON WALLS AND CEILING
 TO MEET MINIMUM REQUIREMENTS IN EXITS
 AND OFFICES.
 3) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS TO THIS OFFICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-02-05 Cont ID  
Sent By lsmith Date 2001-02-05 Time 11:09 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2001-02-05 00:00:00MECH CONTRACTOR TO SUBMIT SEPARATE PLANS
 AND PERMIT APP

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-03-01 Cont ID  
Sent By jleech Date 2001-03-01 Time 07:49 Rev Time 0.33
Received By jleech Date 2001-03-01 Time 07:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-02-21 Cont ID  
Sent By jleech Date 2001-02-21 Time 15:18 Rev Time 0.75
Received By jleech Date 2001-02-21 Time 15:17 Sent To  
Notes
2001-02-21 00:00:00DENIED;
  
 1.SANITARY AND WATER RISERS ARE NEEDED
 SINCE THERE ARE MANY CHANGES TO THE
 PLUMBING SYSTEM.
 A.IS THERE HOT WATER?
 B.WHAT SIZE IS WATER AND SEWER
 PIPES
 C.TYPE OF AIR CHAMBERS TO BE USED
 MUST CALCULATED AND SIZED AND
 MUST BE ACCESSIBLE.
  
 PLEASE SUBMIT INFORMATION REQUESTED.
 PLUMBING REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-18 Cont ID  
Sent By jleech Date 2001-01-18 Time 15:50 Rev Time 1.00
Received By jleech Date 2001-01-18 Time 15:50 Sent To  
Notes
2001-01-18 00:00:00DENIED;
  
 1.DRINKING FOUNTAIN TO COMPLY WITH 97
 FACBC 4.1.3(10) AND 4.15 FOR PEOPLE
 WHO HAVE TROUBLE BENDING AND STOOPING.
  
 2.KITCHEN SINK MUST COMPLY WITH FACBC
 4.24.1 THRU 4.24.7. SHOW DETAIL FOR
 CONSTRUCTION PURPOSES.
  
 3.FACBC 4.23.5 IF URINALS ARE PROVIDED
 THEN AT LEAST ONE SHALL COMPLY WITH
 4.18. DOOR SWINGS INTO CLEAR FLOOR
 SPACE. SHOW DETAIL SHOW CLEAR FLOOR
 SPACE AND HIGHTH WITH ELONGATED RIM
 14" OFF WALL.
  
 4.SHOW SQ. FT. OF BUILDING INTERIOR FOR
 MINIMUM PLUMBING FIXTURES PER 94 SPC
 TABLE 407.
  
 5.SHOW SANITARY AND WATER RISER DIAGRAM.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377