| Plan Review Stops For Permit 01010069 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-04-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-04-26 |
Time |
08:07 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-01 |
Time |
17:30 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-01 00:00:00 | PROVISO: OWNER, ARCH, CONT TO SIGN | | | ENERGY CALS BEFORE ISSUANCE, MEETS THE | | | 20% DISPROPORTIONATE COST TO NOT HAVE TO | | | MOVE WALL IN MENS HC RESTROOM AT LATCH | | | SIDE OF DOOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-17 |
Time |
13:58 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | BILDING PLAN REVIEW: | | | 1). SBC 104.2.2- DOOR SCHEDULE IS MISS- | | | ING INFORMATION FOR DOOR #3. | | | 2). NOTE DOOR #3, IF USED IN A EXIT | | | ACCESS THE NET CLEAR OPENING CAN NOT BE | | | LESS THAN 32". | | | 3). FL. ACCESSIBILITY CODE 4.13.5- | | | CLEAR WIDTH OF DOORS, THE DOORS LEADING | | | INTO THE HANDICAPPED RESTROOMS WILL | | | REQUIRE A CLEAR 32" OPENING, MEASURING | | | FROM THE FACE OF THE DOOR TO THE DOOR | | | STOP ON THE OTHER JAMB. | | | 4). FL. ACCESIBILITY CODE 4.13.6- | | | MANEUVERING CLEARENCES AT DOORS- SEE | | | RESTROOM DOORS INTERIOR LATCH SIDE | | | REQUIRES 18" MINIMUM. | | | 5). SEE FL. ACCESSIBILITY FOR DISPRO- | | | PORTIONATE COST 20%. SEE ATTACHMENT. | | | 6). SBC 704.3 OFFICE #119 WILL REQUIRE | | | A 1 HR WALL FOR TENANT FIRE SEPERATION. | | | WILL NEED A DETAIL FOR THE WALL FROM | | | FLOOR TO CEILING, UL LISTING OR GYPSUM | | | NUMBER. | | | 7). ENERGY CALS SIGNED BY THE PERSON PRE | | | PARING THE COMPLIANCE CALULATION. | | | | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | (561) 659- 8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-09 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-09 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-01 |
Time |
19:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-01 |
Time |
19:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-01-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-08 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-08 |
Time |
18:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-02-05 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-02-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-27 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-27 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-14 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-14 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2001-02-14 00:00:00 | 1) PREVIOUS PLAN REVIEW COMMENTS BY | | | THIS OFFICE NOT RESPONDED TO. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-25 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-25 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | 1) PLEASE EXPLAIN DEAD-END OCCURRENCE | | | ADJACENT TO STAFF WORK AREA. | | | 2) NO INTERIOR FINISH SHOWN ON PLANS. | | | INTERIOR FINISH ON WALLS AND CEILING | | | TO MEET MINIMUM REQUIREMENTS IN EXITS | | | AND OFFICES. | | | 3) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS TO THIS OFFICE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-02-05 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | MECH CONTRACTOR TO SUBMIT SEPARATE PLANS | | | AND PERMIT APP |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-01 |
Time |
07:49 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-03-01 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-02-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-21 |
Time |
15:18 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2001-02-21 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2001-02-21 00:00:00 | DENIED; | | | | | | 1.SANITARY AND WATER RISERS ARE NEEDED | | | SINCE THERE ARE MANY CHANGES TO THE | | | PLUMBING SYSTEM. | | | A.IS THERE HOT WATER? | | | B.WHAT SIZE IS WATER AND SEWER | | | PIPES | | | C.TYPE OF AIR CHAMBERS TO BE USED | | | MUST CALCULATED AND SIZED AND | | | MUST BE ACCESSIBLE. | | | | | | PLEASE SUBMIT INFORMATION REQUESTED. | | | PLUMBING REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-01-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-18 |
Time |
15:50 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-01-18 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2001-01-18 00:00:00 | DENIED; | | | | | | 1.DRINKING FOUNTAIN TO COMPLY WITH 97 | | | FACBC 4.1.3(10) AND 4.15 FOR PEOPLE | | | WHO HAVE TROUBLE BENDING AND STOOPING. | | | | | | 2.KITCHEN SINK MUST COMPLY WITH FACBC | | | 4.24.1 THRU 4.24.7. SHOW DETAIL FOR | | | CONSTRUCTION PURPOSES. | | | | | | 3.FACBC 4.23.5 IF URINALS ARE PROVIDED | | | THEN AT LEAST ONE SHALL COMPLY WITH | | | 4.18. DOOR SWINGS INTO CLEAR FLOOR | | | SPACE. SHOW DETAIL SHOW CLEAR FLOOR | | | SPACE AND HIGHTH WITH ELONGATED RIM | | | 14" OFF WALL. | | | | | | 4.SHOW SQ. FT. OF BUILDING INTERIOR FOR | | | MINIMUM PLUMBING FIXTURES PER 94 SPC | | | TABLE 407. | | | | | | 5.SHOW SANITARY AND WATER RISER DIAGRAM. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|