Plan Review Details - Permit 01010048
Plan Review Stops For Permit 01010048
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-07-18 Cont ID  
Sent By jwitmer Date 2001-07-18 Time 12:46 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-18 00:00:00PLANS ARE TO BE FOR THE REMODEL OF THE
 INTERIOR OF STORE & MANSARD ATTACHED TO
 THE BUILDING. CONTRACTTOR STRUCK OR
 (DELETED) THE FREE STANDING CANOPY. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-07-10 Cont ID  
Sent By jwitmer Date 2001-07-10 Time 18:53 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-10 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01010048
 1300 N. TAMARIND AV
 CONT. FLORIDA GENERAL CONT.
 P: 346-4988
 ENG: J. E. CLAYTON
 P: (561) 996-7048
 DRAFTSMAN: HUGH MILLINGTON
 P: 687-2965
 1)- CANOPY DETAIL "A" SHOWS WHITE OUT &
 NOTES ADDED WITHOUT THE ENGINEERS
 INITIALS OR DATE. I CALLED THEENGINEER
 TO VERIFY THIS WAS HIS WORK OR THAT HE
 HAD REVIEWED THIS WORK, HE STATED HE HAD
 NOT SEEN THE DRAWINGS OR DRAFTSMAN IN
 OVER A WEEK. THE DRAFTSMAN WAS IN THE
 DAY BEFORE ON THIS PROJECT AND FOR
 ANOTHER PROJECT. CALLED THE CONTRACTOR
 COME AND PICK UP THE DRAWINGS.
 JIM WITMER
 PLAN REVIEW
 (561) 659-8096

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-07-03 Cont ID  
Sent By jwitmer Date 2001-07-03 Time 11:26 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01010048
 1300 N TAMARIND AV
 CONT: FLORIDA GENERAL CONT.
 PHONE : 722-5454
  
 THE RENDERING OF THE CANOPY DOES NOT
 HAVE SUFFICIENT STUCTURAL INFORMATION TO
 BE ABLE TO DO A COMPENTENT STRUCTURAL
 PLAN REVIEW AT THIS TIME.
  
 1)- A STUCTURAL DESIGN CERTIFICATION
 CODE ANALYSIS NEEDS TO BE COMPLETED FOR
 THE CANOPY. ATTACHED COPY.
  
 2)- MISSING IS THE ENGINEERS' ANALYSIS
 FOR MOMENT OF OVERTURNING FOR THE CANOPY
  
 3)- MISSNG IS THE FOOTING AND MONOLITHIC
 PAD INFORMATION, GRADE OF STEEL, SPACING
 SIZE OF STEEL,PLACEMENTAND INFORMATION
 ON THE CONCRETE MIX.
  
 4)- ENGINEER TO GIVE THE P.S.F. THAT
 WILL BE REQUIRED FOR THE (3) FOOTINGS OF
 THE CANOPY.
  
 5)- SOILS REPORT FOR THE CANOPY.
  
 6)- TUBULAR COLUMNS: MISSING IS THE SIZE
 OF THE STEEL,GRADE, THICKNESS OF THE
 WALL,LBS/FT CONNECTIONS AT THE FOOTER
 AND TO THE CANOPY FRAME, WELDS/ TYPE.
  
 7)- CANOPY FRAMING: NO INFORMATION IS
 GIVEN: SBC 404.2.2. REQUIRES THE CANOPY
 AND SUPPORTS TO BE 1HR. OR TYPE III
 CONSTRUCTION.
  
 8)- NO INFORMATION IS GIVEN AS TO THE
 FINISH MATERIALS,SIDES, ROOF DECKING,
 GUTTERS & LITTERS OR SIGNAGE.
  
 9)- SBC 404.2.2(2) THE CANOPY MUST MEET
 THESE REQUIREMENTS.
  
 10)- SBC 404.2.4. PUMPS INSTALLED ABOVE
 GRADE SHALL BE MOUNTED ON A CONCRETE
 FOUNDATION & PROTECTED AGAINST VEHICLE
 DAMAGE.
 EXISTING BUILDING:
 11)- CANOPY "A" THE DRAWINGS INDICATE
 THE CANOPY TO BE MADE OUT OF 2X4 TRUSSES
 THEY ALSO INDICATE THAT THERE WILL BE A
 DOUBLE 2X4 BOLTED TO THE WALL. THE
 PROBLEM IS WITH THE 9" TAP-CONS WE CAN
 NOT FIND IN ANY CATALOGS 9" TAP-CONS,
 PLEASE SUBMIT THE MANUFACTURES SPECS.
  
 12)- RESTROOM: SBC 1203.4.2/SMC 503.3.2
 REQUIRES COMMERCIAL RESTROOMS TO HAVE A
 MINIMUM 2 CU.FT./ MIN EXCHANGE OF AIR
 WHERE THERE IS NO WINDOW.
  
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-04-23 Cont ID  
Sent By hpiskura Date 2001-04-23 Time 08:22 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-04-23 00:00:00THE PLANS DO NOT COMPLY WITH THE
 RESPONSIBILITY RULES OF PROFESSIONAL
 ENGINEERS CONCERNING THE DESIGN OF
 STRUCTURES AS FOUND IN CHAPTER 61G15-31
 OF THE FLORIDA ADMINISTRATIVE CODE.
 THE CANOPY, FOUNDATIONS AND GAS PUMPS
 HAVEFAR TOO FEW DETAILS
 DIMENSIONS OR SIZES.THERE IS NO
 DELEGATION OF DESIGN TO A SPECIALTY
 ENGINEER.THERE ARE NO CONNECTION
 DETAILS.
  
 THE FRAMING DETAIL FOR THE EXTERIOR
 MANSARD TYPE ROOF IS NOT CLEAR.
  
 PROVIDE
 MORE DETAIL AND THE DESIGN STANDARDS
 USED FOR THE DESIGN OF THE GASOLINE
 PUMPS AND THEIR PIPING.
  
 ASPHALT SHINGLES CANNOT BE USED ON A
 1:12 PITCH ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-02-05 Cont ID  
Sent By jwitmer Date 2001-02-05 Time 14:07 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-05 00:00:00TANK & TUMMY
 1300 N TAMARIND AV
 FL GENERAL CONTRACTORS INC
 PERMIT # 01010048
  
 1)- THE PLANS STUCTURAL NOTES "STANDARD
 BUILDING CODE 1934"
 2)- PAGE 1 OF THIS PLAN DEPICTS AN
 ADDITION FOR A RESIDENCE FROM VARIOUS
 NOTES AND THE PANEL SCHEDULE. CORRECT.
 3)- CANOPY DETAIL; THIS DETAILDEPICTS EI
 THER 1X3 OR 1X4 STRIP SHEATHING,PBC
 AMENDMENTS TO THE SBC1503.1.2.2 REQUIRES
 ALL ROOF COVERINGS SHALL BE APPLIED TO
 SOLID DECKING OR SHEATHING.
 4)- 1503.3.2 AMENDMENTS TO THE SBC ;
 ROOF COVERINGS AND SYSTEMS SHALL BE
 DESIGNED TO WITHSTAND THE APPROPRIATE
 WINDLOADS PRESCRIBED IN SBC 1606. PRO-
 DUCT APPROVAL REPORTS ARE REQUIRED
 SHOWING TESTING FOR 110 MPH WIND LOADS.
 DADE COUNTY OR SBCCI REPORTS ARE ACCEPT-
 ED.
 5)- DISCREPANCY: CANOPY DETAIL GIVES (2)
 METHODS OF ATTACHMENT TO WALL. THE FIRST
 HAS THE FRAMEWORK ATTACHED BY 2 /9"
 TAPCONS, NO SPACING IS GIVEN, THE SHANK
 DIAMETER ISN'T GIVEN. THE SECOND METHOD
 DECRIBES (2) 2X6'S ATTACHED TO THE WALL
 BUT THE SPACING ISN'T GIVEN NOR THE
 HURRICANE STRAPPING FROM THE LEDGER TO
 THE TRUSS.
 6)- DISCREPANCY CANOPY DETAIL VS. FRONT
 ELKEVATION. THE FRONT ELEVATION SHOWS
 23' OF WINDOW & DOOR OPENINGS UNSUPPORT-
 ED PLUS THE ADDITIONAL WEIGHT OF THE
 NEW CANOPY.WHAT TYPE OF MATERIAL IS
 SUPPORTING THIS TYPE OF LOAD? WHERE IN
 RELATIONSHIP DDOES THE ROOF LINE TIE IN?
 7)- SBC 1507.4 SCUPPERS REQUIRED?
 8)- SBC 1606.4.1 / 1707.4.1 GLAZED OPEN-
 INGS REQUIRE PRODUCT TESTING FOR LARGE
 MISSLE IMPACT TESTING. DADE COUNTY OR
 SBCCI REPORT ACCEPTED.
 9)- FL ENERGY CODE CALCULATIONS REQUIRED
 10)- SBC 1203.4.2/ SMC 503.3.2 COMMER-
 CIAL RESTROOMS REQUIRE 2CU.FT/ MIN EX-
 CHANGE OF AIR WHERE THERE IS NO WINDOW.
 11)- FL ACCESSIBILITY CODE 4.1.6 ALTERA-
 TIONS, IF ALTERATIONS OF SINGLE ELEMENTS
 WHEN CONSIDERED TOGETHER, AMOUNT TO AN
 ALTERATION OF A ROOM OR SPACE IN A BUILD
 ING OF FACILITY, THE ENTIRE SPACE SHALL
 BE MADE ACCESSIBLE.
 12)- FL. ACC CODE 4.1.6VERTICAL ACCESS-
 IBILITY, AN ACCESSIBLE ENTRANCE, RAMPS
 NO STEPS.
 13)- FL ACC CODE 4.1.6.2.2 (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA.
 14)- FL ACC CODE (III) AT LEAST ONE
 ACCESSIBLE UNISEX RESTROOM, OUTSING DOOR
 15)- IS THERE A DOOR ON THE WALK IN COOL
 ER?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-07-18 Cont ID  
Sent By dpalmer Date 2001-07-18 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2001-07-18 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-06-18 Cont ID  
Sent By dpalmer Date 2001-06-18 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2001-06-18 Time 12:09 Sent To  
Notes
2001-06-18 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS STILL DO
 NOT CONTAIN TITLE BLOCK. THIS IS REQ`D
 UNDER F.S. F.A.C. 61G15-23.002.
  
 2)NOTE: PLEASE NOTE THAT WHEN COMMENT ON
 FIRST REVIEW STATED THAT WORK IS TO BE
 DONE TO "MEC". TYPE-O. IT MEANT THAT IT
 WAS A MISPRINT. WORK IS TO BE DONE TO
 THE "NEC" NATIONAL ELECTRIC CODE"
  
 3)NOTE: PLEASE CLARIFY SERVICE ENTRANCE
 CONDUCTORS SHOWING 2-3/0`S?IS THIS A
 MISPRINT ALSO? NOTE: 2 HOTS AND ONE
 NEUTRAL IS NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-04-18 Cont ID  
Sent By dpalmer Date 2001-04-18 Time 17:50 Rev Time 0.00
Received By dpalmer Date 2001-04-18 Time 17:50 Sent To  
Notes
2001-04-18 00:00:00************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 WERE ADDRESSED.
  
  
 PLEASE SEE ORIG NOTES ATTACHED AND
 SUBMIT INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-31 Cont ID  
Sent By dpalmer Date 2001-01-31 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2001-01-31 Time 18:51 Sent To  
Notes
2001-01-31 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.A.C.
 SECTIONS 61G15-23.002 AND 471.025 ALL
 PLANS ARE TO CONTAIN TITLE BLOCK WITH
 ALL INFORMATION FOR ENGINEER OF RECORD.
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING,,,," ELECTRICAL REQUIREMENSTS
 OPTIONAL."?? PLEASE CLARIFY THIS.
 PLEASE NOTE
 RISER/PANEL SCHEDULE NOTES,,,ALL WORK
 TOCOMPLY WITH "MEC" TYPE-O
  
 3)NOTE: PLEASE SEE RISER, SHOWING 125A
 DISCONNECT AND 240A PANEL?
  
  
 4)NOTE: ALSO IN NOTES, PANEL RATED
 10,000 W. W- WATTS? PLEASE CLARIFY.
  
 5)NOTE: PLEASE SHOW ALL ELECTRICAL
 OUTLET REQ`MENTS ON PLANS AND SHOW ALL
 BRANCH CIRCUIT #`S ON PLANS AND
 CORRELATE WITHPANEL SCHEDULES.215-5
  
 6)NOTE: NEED TO SHOW MORE DETAIL ON
 CLASS LOCATIONS/WIRING METHODS OF GAS
 PUMPS ETC. SEE ARTS IN ART 500
  
 7) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
 8)NOTE: SUBMIT LOAD CALCULATIONS. 215-5
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 10)PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE. NEED TO SHOWA/C
 EQUIPMENT ON PLANS.
  
 11)PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
  
 12)NOTE: PLEASE SHOW CONDUCTORS BETWEEN
 MAIN AND PANEL. 215-5
  
 13)NOTE: PLEASE SEE PANEL SCHEDULES AND
 EXPLAIN " LIVING ROOM, DINING RM,
 BEDROOMS 1,2,3???????
  
 14)NOTE: PLEASE EXPLAIN #16 AWG ON PANEL
 SCH????
  
 15)NOTE: RAISED SEALED IS TO BE
 COMPLETELY VISIBLE.
  
 16)NOTE: ALL EQUIPMENT TO BE SHOWN ON
 PANEL SCHEDULES AND LOAD CALCULATIONS.
  
 17)NOTE: SHOW CONDUCTOR SIZES FOR RISER!
  
 PLEASE CORRECT PLANS COMPLETELY AND
 SUBMIT FOR REVIEW WITH ALL THE
 INFORMATION ABOVE ADDRESSED. IF THERE
 ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2001-08-23 Cont ID  
Sent By mamini Date 2001-08-23 Time 14:35 Rev Time 2.00
Received By mamini Date 2001-08-23 Time 14:33 Sent To  
Notes
2001-08-23 00:00:00NOT APPLICABLE:
 1. # 01010048 BUILDING PERMIT ONLY
 THERE WILL BE NO WORKS ON SITE AND/OR
 BEYOND THE PROPERTY LINES.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2001-07-20 Cont ID  
Sent By mamini Date 2001-07-20 Time 13:18 Rev Time 0.00
Received By mamini Date 2001-07-20 Time 13:18 Sent To  
Notes
2001-07-20 00:00:00FAILED:
 1. DUMPSTER ENCLOSURE MUST BE PER CITY
 STANDARD AND REQUIREMENT, SEE ATTACHED.
 2. MUST COMPLY WITH VISIBILITY TRIANGLE
 AT CORNER OF PALM BEACH LAKE &
 N. TAMARIND AVENUE, SEE ATTACHED.
 3. PLEASE SHOW THE EXISTING SIDEWALK
 ALONG THE PALM BEACH LAKE BLVD. &
 N. TAMARIND.PLAN AS SUBMITTED DOES NOT
 MATCH THE EXISTING CONDITIONS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-24 Cont ID  
Sent By mamini Date 2001-04-24 Time 14:43 Rev Time 1.00
Received By mamini Date 2001-04-24 Time 14:27 Sent To  
Notes
2001-04-24 00:00:00FAILED:
 1. INSUFFICIENT INFORMATION FOR CIVIL
 ENGINEERING REVIEW.PLEASE INDICATE IF
 THERE ARE CHANGES ON SITE PLAN (EXISTING
 / NEW).ALSO SHOW UNDERGROUND UTILITY
 WORKS, DRIVEWAY, SIDEWALK,NEW
 LANDSCAPING,DUMPSTER, ETC..
 IF ANY QUESTION PLEASE CONTACT 561-659-
 8096 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 09:38 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 09:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-06-21 Cont ID  
Sent By mcarsill Date 2001-06-21 Time 08:49 Rev Time 0.00
Received By mcarsill Date 2001-06-21 Time 08:49 Sent To  
Notes
2001-06-21 00:00:001) WHAT IS THE VENTLESS HOOD USED FOR.
 IF ANY COOKING IS DONE ON THE PREMISES
 THAT PRODUCES SMOKE OR GREASE LADEN
 VAPORS THEN IT MUST BE PROTECTED BY AN
 APPROVED HOOD,DUCT AND EXTINGUISHING
 SYSTEM. A VENTLESS HOOD IS NOT
 ACCEPTABLE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-02-05 Cont ID  
Sent By mcarsill Date 2001-02-05 Time 12:34 Rev Time 0.00
Received By mcarsill Date 2001-02-05 Time 12:33 Sent To  
Notes
2001-02-05 00:00:001) BUILDING ADDRESS STILL NOT SHOWN ON
 PLANS.
 2) ELECTRICAL OUTLETS NOT SHOWN ON PLANS
 3) PLEASE EXPLAIN OVEN AND FRIDGE WITH
 HOOD NOTED ON PLANS. A FRIER IS ALSO
 NOTED ON PLANS.
 4) NO FIRE EXTINGUISHER, EXIT SIGNS OR
 EMERGENCY LIGHTING SHOWN ON PLANS.
 5) WARNING SIGNS REQUIRED AT FUEL ISLAND
 6) ELECTRICAL PANEL SCHEDULE INDICATES
 BEDROOMS, DINING AND LIVING ROOMS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2001-01-25 Cont ID  
Sent By mcarsill Date 2001-01-09 Time 12:04 Rev Time 0.00
Received By mcarsill Date 2001-01-09 Time 12:04 Sent To  
Notes
2001-01-09 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) PLEASE PROVIDE SEPARATE PLANS AND
 PERMIT FOR THE FUEL EQUIPMENT PLANNED
 TO BE USED.
 3) EXISTING FUEL TANKS ARE TO BE
 PROPERLY SAFEQUARDED IN ACCORDANCE WITH
 NFPA 30. THE FUEL TANKS SHOULD BE
 RENDERED TEMPORARILY OUT OF SERVICE FOR
 NO LONGER THAN 90 DAYS. THE TANKS ARE TO
 REMOVED OR ABANDONED IN PLACE WITH
 APPROPRIATE SAFEGUARDS.
 4) THIS PERMIT IS FOR MANSARD ONLY.
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-07-24 Cont ID  
Sent By pkrauss Date 2001-07-24 Time 08:24 Rev Time 0.30
Received By pkrauss Date 2001-07-24 Time 08:24 Sent To  
Notes
2001-07-24 00:00:00*******************DENIED***************
  
 NO HVAC WORK BEING DONE WITH THIS
 PERMITAPPLICATION.PLEASE PROVIDE
 PLANS WITH MECHANICAL PERMIT
 APPLICATION.
  
 ADDITIONAL PLANS AND PERMIT REQUIRED
 FOR MECH HOOD, EHXAUST SYSTEM AND MAKE
 UP AIR.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-06-25 Cont ID  
Sent By pkrauss Date 2001-06-25 Time 16:29 Rev Time 0.50
Received By pkrauss Date 2001-06-25 Time 16:14 Sent To  
Notes
2001-06-25 00:00:00******************DENIED****************
  
  
 ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 NOTE:AS PER 1997 SMC 504.1, AN EXHAUST
 HOOD SHALL BE INSTALLED FOR ALL
 COMMERCIAL COOKING EQUIPMENT
 PRODUCING GREASE-LADEN AIR OR
 SMOKE.
  
 NO HVAC PLANS SUBMITTED FOR REVIEW WITH
 THIS PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-01-30 Cont ID  
Sent By ndenmark Date 2001-01-30 Time 14:49 Rev Time 0.50
Received By ndenmark Date 2001-01-30 Time 14:49 Sent To  
Notes
2001-01-30 00:00:00NO MECHANICAL WORK SHOWN PERMIT REQUIRED
 PRIOR TO ANY MECHANCIAL WORK BEING DONE

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-08-23 Cont ID  
Sent By jleech Date 2001-08-23 Time 18:19 Rev Time 1.00
Received By jleech Date 2001-08-23 Time 18:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-07-24 Cont ID  
Sent By jleech Date 2001-07-24 Time 13:30 Rev Time 0.00
Received By jleech Date 2001-08-14 Time 07:36 Sent To  
Notes
2001-07-24 00:00:00DENIED;
 1.BATHROOM DOES NOT COMPLY WITH FACBC
 4.16 AND 4.19 MINIMUM WIDTH IS TO
 SMALL AND DOOR SHALL BE DIAGONAL FROM
 TOILET.
 2.SANITARY RISER DIAGRAM NOT TO CODE.
 FLOOR DRAIN UNVENTED. FLOOR DRAIN
 SHALL HAVE A TRAP PRIMER. SPC SEC.
 409.4.1.1.
 3.RISER DIAGRAM FOR GREASY WASTE
 REQUIRED.
 4.GREASE TRAP REQUIRED TO BE SIZED BY
 RODNEY COMPO UTILITY'S DEPARTMENT.
 5.GAS DRAWING REQUIRED FOR GAS EQUIPMENT
 SHOWN.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-06-27 Cont ID  
Sent By pschmitz Date 2001-06-27 Time 10:49 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-27 00:00:00PLUMBING PLAN REVIEW 3RD TIME DENIED
 SEE ATTACHED (PREVIOUS PLAN REVIEWS)
 (1) NUMBER SHEETS FOR REFERENCE, 104.3
 (2) MINIMUM SIZE OF GREASE TRAP 750 GAL
 CONTACT WPB REGIONAL SEWER TREATMENT
 PLANT, SIZE. RODNEY COMPO 561-8374074
 (3) SPC 94 SEC 104.3 PLANS, SPECIFICA-
 TIONS, PROVIDE A ISOMETRIC DRAWING OF
 DWV,WATER PIPING, SHOW LOCATION OF BACK
 FLOW PREVENTER ON WATER SERVICE, FUTURE
 CONNECTION FOR CAR WASH, ALL INDIRECT
 WASTE TO FLR SINKS, ICE MACHINE AND
 COOLER. FUTURE SANI SEWER FOR CAR WASH.
 (4) SEE ATTACHED: GAS PERMIT APPLICATION
 REQUIRMENTS ADDRESS EA ITEM CIRCLED.
 (5) SEPERATE PRRMITS FOR GAS, IRRIGATION
 GREASE INTERCEPTOR.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-04-30 Cont ID  
Sent By kstevens Date 2001-04-30 Time 14:00 Rev Time 1.00
Received By kstevens Date 2001-04-30 Time 13:59 Sent To  
Notes
2001-04-30 00:00:00REVIEW NOTES:FACBC-97SPC-94
  
 DENIED:
  
 (1) BATHROOM SIZE NOT SUFFICIENT. DOES
 NOT COMPLY WITH FACBC-97 4.16 AND 4.19
  
 (2) HEALTH DEPT. REVIEW AND APPROVAL
 NOT SEEN.
  
 (3) FLOOR DRAIN NOT SEEN ON SANITARY
 RISER DIAGRAM.
  
 (4) GREASY WASTE RISER DIAGRAM NOT
 SUBMITTED.
  
 (5) NO CAR WASH DETAILS GIVEN.
  
 (6) LOCATION OF COOLER CONDENSATE
 DISPOSAL NOT SHOWN.
  
 (7) FLOOR SINK REQUIRED FOR ICE MACHINE
 DRAINS.
  
 (8) FLOOR SINK REQUIRED FOR INDIRECT
 WASTE AT 3 COMPARTMENT SINK. SPC 807
  
 (9) SUBMIT COPY OF REPORT FORM RODNEY
 COMPO ON LOCATION AND SIZE OF GREASE
 TRAP.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-02-05 Cont ID  
Sent By jleech Date 2001-02-05 Time 16:22 Rev Time 1.00
Received By pschmitz Date 2001-02-05 Time 16:22 Sent To  
Notes
2001-02-05 00:00:00DENIED;
  
 1.CONTACT RODNEY COMPO FOR SIZE AND
 LOCATION OF GREASE TRAP WASTE ORD.#
 2938-96 (835-7423).
  
 2.SHOW SIZE OF BATHROOM. BATHROOM SHALL
 COMPLY WITH 97 FACBC 4.16 AND 4.19.
  
 3.HEALTH DEPARTMENT REVIEW AND APPROVAL
 REQUIRED.
  
 4.HAND SINK REQUIRED IN FOOD PREP AREA.
  
 5.THREE INCH FLOOR DRAIN REQUIRED IN
 RESTROOM PER. 409.4.1.1.
  
 6.SHOW GREASY WASTE RISER DIAGRAM
 INCLUDING GREASE TRAP SIZE AND
 LOCATION.
  
 7.DETAIL REQUIRED FOR CAR WASH.
  
 8.SHOW LOCATION OF COOLER CONDENSATE
 DISPOSAL.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-28 Cont ID  
Sent By lsmith Date 2001-08-28 Time 14:59 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***