| Plan Review Stops For Permit 01010048 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-07-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-18 |
Time |
12:46 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-18 00:00:00 | PLANS ARE TO BE FOR THE REMODEL OF THE | | | INTERIOR OF STORE & MANSARD ATTACHED TO | | | THE BUILDING. CONTRACTTOR STRUCK OR | | | (DELETED) THE FREE STANDING CANOPY. JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-10 |
Time |
18:53 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01010048 | | | 1300 N. TAMARIND AV | | | CONT. FLORIDA GENERAL CONT. | | | P: 346-4988 | | | ENG: J. E. CLAYTON | | | P: (561) 996-7048 | | | DRAFTSMAN: HUGH MILLINGTON | | | P: 687-2965 | | | 1)- CANOPY DETAIL "A" SHOWS WHITE OUT & | | | NOTES ADDED WITHOUT THE ENGINEERS | | | INITIALS OR DATE. I CALLED THEENGINEER | | | TO VERIFY THIS WAS HIS WORK OR THAT HE | | | HAD REVIEWED THIS WORK, HE STATED HE HAD | | | NOT SEEN THE DRAWINGS OR DRAFTSMAN IN | | | OVER A WEEK. THE DRAFTSMAN WAS IN THE | | | DAY BEFORE ON THIS PROJECT AND FOR | | | ANOTHER PROJECT. CALLED THE CONTRACTOR | | | COME AND PICK UP THE DRAWINGS. | | | JIM WITMER | | | PLAN REVIEW | | | (561) 659-8096 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-03 |
Time |
11:26 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01010048 | | | 1300 N TAMARIND AV | | | CONT: FLORIDA GENERAL CONT. | | | PHONE : 722-5454 | | | | | | THE RENDERING OF THE CANOPY DOES NOT | | | HAVE SUFFICIENT STUCTURAL INFORMATION TO | | | BE ABLE TO DO A COMPENTENT STRUCTURAL | | | PLAN REVIEW AT THIS TIME. | | | | | | 1)- A STUCTURAL DESIGN CERTIFICATION | | | CODE ANALYSIS NEEDS TO BE COMPLETED FOR | | | THE CANOPY. ATTACHED COPY. | | | | | | 2)- MISSING IS THE ENGINEERS' ANALYSIS | | | FOR MOMENT OF OVERTURNING FOR THE CANOPY | | | | | | 3)- MISSNG IS THE FOOTING AND MONOLITHIC | | | PAD INFORMATION, GRADE OF STEEL, SPACING | | | SIZE OF STEEL,PLACEMENTAND INFORMATION | | | ON THE CONCRETE MIX. | | | | | | 4)- ENGINEER TO GIVE THE P.S.F. THAT | | | WILL BE REQUIRED FOR THE (3) FOOTINGS OF | | | THE CANOPY. | | | | | | 5)- SOILS REPORT FOR THE CANOPY. | | | | | | 6)- TUBULAR COLUMNS: MISSING IS THE SIZE | | | OF THE STEEL,GRADE, THICKNESS OF THE | | | WALL,LBS/FT CONNECTIONS AT THE FOOTER | | | AND TO THE CANOPY FRAME, WELDS/ TYPE. | | | | | | 7)- CANOPY FRAMING: NO INFORMATION IS | | | GIVEN: SBC 404.2.2. REQUIRES THE CANOPY | | | AND SUPPORTS TO BE 1HR. OR TYPE III | | | CONSTRUCTION. | | | | | | 8)- NO INFORMATION IS GIVEN AS TO THE | | | FINISH MATERIALS,SIDES, ROOF DECKING, | | | GUTTERS & LITTERS OR SIGNAGE. | | | | | | 9)- SBC 404.2.2(2) THE CANOPY MUST MEET | | | THESE REQUIREMENTS. | | | | | | 10)- SBC 404.2.4. PUMPS INSTALLED ABOVE | | | GRADE SHALL BE MOUNTED ON A CONCRETE | | | FOUNDATION & PROTECTED AGAINST VEHICLE | | | DAMAGE. | | | EXISTING BUILDING: | | | 11)- CANOPY "A" THE DRAWINGS INDICATE | | | THE CANOPY TO BE MADE OUT OF 2X4 TRUSSES | | | THEY ALSO INDICATE THAT THERE WILL BE A | | | DOUBLE 2X4 BOLTED TO THE WALL. THE | | | PROBLEM IS WITH THE 9" TAP-CONS WE CAN | | | NOT FIND IN ANY CATALOGS 9" TAP-CONS, | | | PLEASE SUBMIT THE MANUFACTURES SPECS. | | | | | | 12)- RESTROOM: SBC 1203.4.2/SMC 503.3.2 | | | REQUIRES COMMERCIAL RESTROOMS TO HAVE A | | | MINIMUM 2 CU.FT./ MIN EXCHANGE OF AIR | | | WHERE THERE IS NO WINDOW. | | | | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-04-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-04-23 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-23 00:00:00 | THE PLANS DO NOT COMPLY WITH THE | | | RESPONSIBILITY RULES OF PROFESSIONAL | | | ENGINEERS CONCERNING THE DESIGN OF | | | STRUCTURES AS FOUND IN CHAPTER 61G15-31 | | | OF THE FLORIDA ADMINISTRATIVE CODE. | | | THE CANOPY, FOUNDATIONS AND GAS PUMPS | | | HAVEFAR TOO FEW DETAILS | | | DIMENSIONS OR SIZES.THERE IS NO | | | DELEGATION OF DESIGN TO A SPECIALTY | | | ENGINEER.THERE ARE NO CONNECTION | | | DETAILS. | | | | | | THE FRAMING DETAIL FOR THE EXTERIOR | | | MANSARD TYPE ROOF IS NOT CLEAR. | | | | | | PROVIDE | | | MORE DETAIL AND THE DESIGN STANDARDS | | | USED FOR THE DESIGN OF THE GASOLINE | | | PUMPS AND THEIR PIPING. | | | | | | ASPHALT SHINGLES CANNOT BE USED ON A | | | 1:12 PITCH ROOF. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-05 |
Time |
14:07 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | TANK & TUMMY | | | 1300 N TAMARIND AV | | | FL GENERAL CONTRACTORS INC | | | PERMIT # 01010048 | | | | | | 1)- THE PLANS STUCTURAL NOTES "STANDARD | | | BUILDING CODE 1934" | | | 2)- PAGE 1 OF THIS PLAN DEPICTS AN | | | ADDITION FOR A RESIDENCE FROM VARIOUS | | | NOTES AND THE PANEL SCHEDULE. CORRECT. | | | 3)- CANOPY DETAIL; THIS DETAILDEPICTS EI | | | THER 1X3 OR 1X4 STRIP SHEATHING,PBC | | | AMENDMENTS TO THE SBC1503.1.2.2 REQUIRES | | | ALL ROOF COVERINGS SHALL BE APPLIED TO | | | SOLID DECKING OR SHEATHING. | | | 4)- 1503.3.2 AMENDMENTS TO THE SBC ; | | | ROOF COVERINGS AND SYSTEMS SHALL BE | | | DESIGNED TO WITHSTAND THE APPROPRIATE | | | WINDLOADS PRESCRIBED IN SBC 1606. PRO- | | | DUCT APPROVAL REPORTS ARE REQUIRED | | | SHOWING TESTING FOR 110 MPH WIND LOADS. | | | DADE COUNTY OR SBCCI REPORTS ARE ACCEPT- | | | ED. | | | 5)- DISCREPANCY: CANOPY DETAIL GIVES (2) | | | METHODS OF ATTACHMENT TO WALL. THE FIRST | | | HAS THE FRAMEWORK ATTACHED BY 2 /9" | | | TAPCONS, NO SPACING IS GIVEN, THE SHANK | | | DIAMETER ISN'T GIVEN. THE SECOND METHOD | | | DECRIBES (2) 2X6'S ATTACHED TO THE WALL | | | BUT THE SPACING ISN'T GIVEN NOR THE | | | HURRICANE STRAPPING FROM THE LEDGER TO | | | THE TRUSS. | | | 6)- DISCREPANCY CANOPY DETAIL VS. FRONT | | | ELKEVATION. THE FRONT ELEVATION SHOWS | | | 23' OF WINDOW & DOOR OPENINGS UNSUPPORT- | | | ED PLUS THE ADDITIONAL WEIGHT OF THE | | | NEW CANOPY.WHAT TYPE OF MATERIAL IS | | | SUPPORTING THIS TYPE OF LOAD? WHERE IN | | | RELATIONSHIP DDOES THE ROOF LINE TIE IN? | | | 7)- SBC 1507.4 SCUPPERS REQUIRED? | | | 8)- SBC 1606.4.1 / 1707.4.1 GLAZED OPEN- | | | INGS REQUIRE PRODUCT TESTING FOR LARGE | | | MISSLE IMPACT TESTING. DADE COUNTY OR | | | SBCCI REPORT ACCEPTED. | | | 9)- FL ENERGY CODE CALCULATIONS REQUIRED | | | 10)- SBC 1203.4.2/ SMC 503.3.2 COMMER- | | | CIAL RESTROOMS REQUIRE 2CU.FT/ MIN EX- | | | CHANGE OF AIR WHERE THERE IS NO WINDOW. | | | 11)- FL ACCESSIBILITY CODE 4.1.6 ALTERA- | | | TIONS, IF ALTERATIONS OF SINGLE ELEMENTS | | | WHEN CONSIDERED TOGETHER, AMOUNT TO AN | | | ALTERATION OF A ROOM OR SPACE IN A BUILD | | | ING OF FACILITY, THE ENTIRE SPACE SHALL | | | BE MADE ACCESSIBLE. | | | 12)- FL. ACC CODE 4.1.6VERTICAL ACCESS- | | | IBILITY, AN ACCESSIBLE ENTRANCE, RAMPS | | | NO STEPS. | | | 13)- FL ACC CODE 4.1.6.2.2 (II) AN | | | ACCESSIBLE ROUTE TO THE ALTERED AREA. | | | 14)- FL ACC CODE (III) AT LEAST ONE | | | ACCESSIBLE UNISEX RESTROOM, OUTSING DOOR | | | 15)- IS THERE A DOOR ON THE WALK IN COOL | | | ER? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-18 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-18 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-18 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-18 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2001-06-18 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS STILL DO | | | NOT CONTAIN TITLE BLOCK. THIS IS REQ`D | | | UNDER F.S. F.A.C. 61G15-23.002. | | | | | | 2)NOTE: PLEASE NOTE THAT WHEN COMMENT ON | | | FIRST REVIEW STATED THAT WORK IS TO BE | | | DONE TO "MEC". TYPE-O. IT MEANT THAT IT | | | WAS A MISPRINT. WORK IS TO BE DONE TO | | | THE "NEC" NATIONAL ELECTRIC CODE" | | | | | | 3)NOTE: PLEASE CLARIFY SERVICE ENTRANCE | | | CONDUCTORS SHOWING 2-3/0`S?IS THIS A | | | MISPRINT ALSO? NOTE: 2 HOTS AND ONE | | | NEUTRAL IS NEEDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-18 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-18 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2001-04-18 00:00:00 | ************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | WERE ADDRESSED. | | | | | | | | | PLEASE SEE ORIG NOTES ATTACHED AND | | | SUBMIT INFORMATION FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-31 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-31 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2001-01-31 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT UNDER F.A.C. | | | SECTIONS 61G15-23.002 AND 471.025 ALL | | | PLANS ARE TO CONTAIN TITLE BLOCK WITH | | | ALL INFORMATION FOR ENGINEER OF RECORD. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE | | | SHOWING,,,," ELECTRICAL REQUIREMENSTS | | | OPTIONAL."?? PLEASE CLARIFY THIS. | | | PLEASE NOTE | | | RISER/PANEL SCHEDULE NOTES,,,ALL WORK | | | TOCOMPLY WITH "MEC" TYPE-O | | | | | | 3)NOTE: PLEASE SEE RISER, SHOWING 125A | | | DISCONNECT AND 240A PANEL? | | | | | | | | | 4)NOTE: ALSO IN NOTES, PANEL RATED | | | 10,000 W. W- WATTS? PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE SHOW ALL ELECTRICAL | | | OUTLET REQ`MENTS ON PLANS AND SHOW ALL | | | BRANCH CIRCUIT #`S ON PLANS AND | | | CORRELATE WITHPANEL SCHEDULES.215-5 | | | | | | 6)NOTE: NEED TO SHOW MORE DETAIL ON | | | CLASS LOCATIONS/WIRING METHODS OF GAS | | | PUMPS ETC. SEE ARTS IN ART 500 | | | | | | 7) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | | | | 8)NOTE: SUBMIT LOAD CALCULATIONS. 215-5 | | | | | | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 10)PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. NEED TO SHOWA/C | | | EQUIPMENT ON PLANS. | | | | | | 11)PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | | | | 12)NOTE: PLEASE SHOW CONDUCTORS BETWEEN | | | MAIN AND PANEL. 215-5 | | | | | | 13)NOTE: PLEASE SEE PANEL SCHEDULES AND | | | EXPLAIN " LIVING ROOM, DINING RM, | | | BEDROOMS 1,2,3??????? | | | | | | 14)NOTE: PLEASE EXPLAIN #16 AWG ON PANEL | | | SCH???? | | | | | | 15)NOTE: RAISED SEALED IS TO BE | | | COMPLETELY VISIBLE. | | | | | | 16)NOTE: ALL EQUIPMENT TO BE SHOWN ON | | | PANEL SCHEDULES AND LOAD CALCULATIONS. | | | | | | 17)NOTE: SHOW CONDUCTOR SIZES FOR RISER! | | | | | | PLEASE CORRECT PLANS COMPLETELY AND | | | SUBMIT FOR REVIEW WITH ALL THE | | | INFORMATION ABOVE ADDRESSED. IF THERE | | | ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-08-23 |
Time |
14:35 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-08-23 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | NOT APPLICABLE: | | | 1. # 01010048 BUILDING PERMIT ONLY | | | THERE WILL BE NO WORKS ON SITE AND/OR | | | BEYOND THE PROPERTY LINES. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2001-07-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-20 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-07-20 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2001-07-20 00:00:00 | FAILED: | | | 1. DUMPSTER ENCLOSURE MUST BE PER CITY | | | STANDARD AND REQUIREMENT, SEE ATTACHED. | | | 2. MUST COMPLY WITH VISIBILITY TRIANGLE | | | AT CORNER OF PALM BEACH LAKE & | | | N. TAMARIND AVENUE, SEE ATTACHED. | | | 3. PLEASE SHOW THE EXISTING SIDEWALK | | | ALONG THE PALM BEACH LAKE BLVD. & | | | N. TAMARIND.PLAN AS SUBMITTED DOES NOT | | | MATCH THE EXISTING CONDITIONS. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-04-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-04-24 |
Time |
14:43 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-04-24 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2001-04-24 00:00:00 | FAILED: | | | 1. INSUFFICIENT INFORMATION FOR CIVIL | | | ENGINEERING REVIEW.PLEASE INDICATE IF | | | THERE ARE CHANGES ON SITE PLAN (EXISTING | | | / NEW).ALSO SHOW UNDERGROUND UTILITY | | | WORKS, DRIVEWAY, SIDEWALK,NEW | | | LANDSCAPING,DUMPSTER, ETC.. | | | IF ANY QUESTION PLEASE CONTACT 561-659- | | | 8096 EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-06 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-06 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-06-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-21 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-21 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2001-06-21 00:00:00 | 1) WHAT IS THE VENTLESS HOOD USED FOR. | | | IF ANY COOKING IS DONE ON THE PREMISES | | | THAT PRODUCES SMOKE OR GREASE LADEN | | | VAPORS THEN IT MUST BE PROTECTED BY AN | | | APPROVED HOOD,DUCT AND EXTINGUISHING | | | SYSTEM. A VENTLESS HOOD IS NOT | | | ACCEPTABLE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-05 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-05 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | 1) BUILDING ADDRESS STILL NOT SHOWN ON | | | PLANS. | | | 2) ELECTRICAL OUTLETS NOT SHOWN ON PLANS | | | 3) PLEASE EXPLAIN OVEN AND FRIDGE WITH | | | HOOD NOTED ON PLANS. A FRIER IS ALSO | | | NOTED ON PLANS. | | | 4) NO FIRE EXTINGUISHER, EXIT SIGNS OR | | | EMERGENCY LIGHTING SHOWN ON PLANS. | | | 5) WARNING SIGNS REQUIRED AT FUEL ISLAND | | | 6) ELECTRICAL PANEL SCHEDULE INDICATES | | | BEDROOMS, DINING AND LIVING ROOMS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-09 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-09 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 2) PLEASE PROVIDE SEPARATE PLANS AND | | | PERMIT FOR THE FUEL EQUIPMENT PLANNED | | | TO BE USED. | | | 3) EXISTING FUEL TANKS ARE TO BE | | | PROPERLY SAFEQUARDED IN ACCORDANCE WITH | | | NFPA 30. THE FUEL TANKS SHOULD BE | | | RENDERED TEMPORARILY OUT OF SERVICE FOR | | | NO LONGER THAN 90 DAYS. THE TANKS ARE TO | | | REMOVED OR ABANDONED IN PLACE WITH | | | APPROPRIATE SAFEGUARDS. | | | 4) THIS PERMIT IS FOR MANSARD ONLY. | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-24 |
Time |
08:24 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-07-24 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2001-07-24 00:00:00 | *******************DENIED*************** | | | | | | NO HVAC WORK BEING DONE WITH THIS | | | PERMITAPPLICATION.PLEASE PROVIDE | | | PLANS WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | ADDITIONAL PLANS AND PERMIT REQUIRED | | | FOR MECH HOOD, EHXAUST SYSTEM AND MAKE | | | UP AIR. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-06-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-25 |
Time |
16:29 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-06-25 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2001-06-25 00:00:00 | ******************DENIED**************** | | | | | | | | | ADDITIONAL MECHANICAL PERMIT REQUIRED | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLER.PLEASE PROVIDE PLANS AND | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | NOTE:AS PER 1997 SMC 504.1, AN EXHAUST | | | HOOD SHALL BE INSTALLED FOR ALL | | | COMMERCIAL COOKING EQUIPMENT | | | PRODUCING GREASE-LADEN AIR OR | | | SMOKE. | | | | | | NO HVAC PLANS SUBMITTED FOR REVIEW WITH | | | THIS PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-01-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-30 |
Time |
14:49 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-01-30 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2001-01-30 00:00:00 | NO MECHANICAL WORK SHOWN PERMIT REQUIRED | | | PRIOR TO ANY MECHANCIAL WORK BEING DONE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-23 |
Time |
18:19 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-08-23 |
Time |
18:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-24 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2001-08-14 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2001-07-24 00:00:00 | DENIED; | | | 1.BATHROOM DOES NOT COMPLY WITH FACBC | | | 4.16 AND 4.19 MINIMUM WIDTH IS TO | | | SMALL AND DOOR SHALL BE DIAGONAL FROM | | | TOILET. | | | 2.SANITARY RISER DIAGRAM NOT TO CODE. | | | FLOOR DRAIN UNVENTED. FLOOR DRAIN | | | SHALL HAVE A TRAP PRIMER. SPC SEC. | | | 409.4.1.1. | | | 3.RISER DIAGRAM FOR GREASY WASTE | | | REQUIRED. | | | 4.GREASE TRAP REQUIRED TO BE SIZED BY | | | RODNEY COMPO UTILITY'S DEPARTMENT. | | | 5.GAS DRAWING REQUIRED FOR GAS EQUIPMENT | | | SHOWN. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-06-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-27 |
Time |
10:49 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-27 00:00:00 | PLUMBING PLAN REVIEW 3RD TIME DENIED | | | SEE ATTACHED (PREVIOUS PLAN REVIEWS) | | | (1) NUMBER SHEETS FOR REFERENCE, 104.3 | | | (2) MINIMUM SIZE OF GREASE TRAP 750 GAL | | | CONTACT WPB REGIONAL SEWER TREATMENT | | | PLANT, SIZE. RODNEY COMPO 561-8374074 | | | (3) SPC 94 SEC 104.3 PLANS, SPECIFICA- | | | TIONS, PROVIDE A ISOMETRIC DRAWING OF | | | DWV,WATER PIPING, SHOW LOCATION OF BACK | | | FLOW PREVENTER ON WATER SERVICE, FUTURE | | | CONNECTION FOR CAR WASH, ALL INDIRECT | | | WASTE TO FLR SINKS, ICE MACHINE AND | | | COOLER. FUTURE SANI SEWER FOR CAR WASH. | | | (4) SEE ATTACHED: GAS PERMIT APPLICATION | | | REQUIRMENTS ADDRESS EA ITEM CIRCLED. | | | (5) SEPERATE PRRMITS FOR GAS, IRRIGATION | | | GREASE INTERCEPTOR. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-04-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-04-30 |
Time |
14:00 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-04-30 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2001-04-30 00:00:00 | REVIEW NOTES:FACBC-97SPC-94 | | | | | | DENIED: | | | | | | (1) BATHROOM SIZE NOT SUFFICIENT. DOES | | | NOT COMPLY WITH FACBC-97 4.16 AND 4.19 | | | | | | (2) HEALTH DEPT. REVIEW AND APPROVAL | | | NOT SEEN. | | | | | | (3) FLOOR DRAIN NOT SEEN ON SANITARY | | | RISER DIAGRAM. | | | | | | (4) GREASY WASTE RISER DIAGRAM NOT | | | SUBMITTED. | | | | | | (5) NO CAR WASH DETAILS GIVEN. | | | | | | (6) LOCATION OF COOLER CONDENSATE | | | DISPOSAL NOT SHOWN. | | | | | | (7) FLOOR SINK REQUIRED FOR ICE MACHINE | | | DRAINS. | | | | | | (8) FLOOR SINK REQUIRED FOR INDIRECT | | | WASTE AT 3 COMPARTMENT SINK. SPC 807 | | | | | | (9) SUBMIT COPY OF REPORT FORM RODNEY | | | COMPO ON LOCATION AND SIZE OF GREASE | | | TRAP. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-05 |
Time |
16:22 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2001-02-05 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | DENIED; | | | | | | 1.CONTACT RODNEY COMPO FOR SIZE AND | | | LOCATION OF GREASE TRAP WASTE ORD.# | | | 2938-96 (835-7423). | | | | | | 2.SHOW SIZE OF BATHROOM. BATHROOM SHALL | | | COMPLY WITH 97 FACBC 4.16 AND 4.19. | | | | | | 3.HEALTH DEPARTMENT REVIEW AND APPROVAL | | | REQUIRED. | | | | | | 4.HAND SINK REQUIRED IN FOOD PREP AREA. | | | | | | 5.THREE INCH FLOOR DRAIN REQUIRED IN | | | RESTROOM PER. 409.4.1.1. | | | | | | 6.SHOW GREASY WASTE RISER DIAGRAM | | | INCLUDING GREASE TRAP SIZE AND | | | LOCATION. | | | | | | 7.DETAIL REQUIRED FOR CAR WASH. | | | | | | 8.SHOW LOCATION OF COOLER CONDENSATE | | | DISPOSAL. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-08-28 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|