| Plan Review Stops For Permit 01010035 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-03-01 |
Time |
16:50 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2002-03-01 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2002-03-01 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-SEE COMMENTS ON DRAWINGS. | | | 2-PROVIDE UPDATED PRODUCT APPROVAL FOR | | | EXTERIOR DOOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-19 |
Time |
15:38 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-03-20 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | CHECKLIST: | | | | | | 1-PROVIDE COMPLETE INFORMATION FOR | | | STORM PANELS. PROVIDE KEY PLAN AND A | | | COMPLETE INSTALLATION SCHEDULE (SEE | | | CITY SAMPLE ATTACHED). | | | CLEARLY INDICATE MOUNTING CONDITIONS | | | AND ANCHOR TYPE AND SPACING TO BE USED | | | | | | 2-ROOF FRAMING PLAN SHOWS 2X6 JOISTSTO | | | BE SUPPORTED ON SINGLE 2X6: | | | -SINGLE 2X6 IS NOT ADEQUATE TO SUPPORT | | | THIS LOAD. | | | -SPECIFY GRADE OF LUMBER TO BE USED. | | | -SPECIFY WHERE IS THE 2X6 BEAM RESTING | | | ON AT THE ENDS. SPECIFY POST AND | | | ATTACHMENTS. TOP AND BOTTOM. | | | | | | 3-PROVIDE COMPLETE SECTION SHOWING ALL | | | INFORMATION: STUDS SIZE AND SPACING, | | | INSULATION, CONNECTORS TOP AND BOTTOM, | | | ROOF VENTILATION, ROOF SHEATHING | | | FASTENING, WALL SHEATHING AND STUCCO, | | | ETC. | | | | | | 4-PROVIDE COMPLETE PRODUCT APPROVAL FOR | | | OUTSWING ENTRY DOOR. | | | | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-01-22 |
Time |
09:58 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-01-22 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2001-01-22 00:00:00 | CHECKLIST: | | | | | | 1-PROVIDE CONNECTION DETAILS. SPECIFY | | | CONNECTORS TOP AND BOTTOM. SPECIFY | | | ROOF CONNECTORS. | | | 2-PROVIDE PRODUCT APPROVALS FOR: | | | -EXTERIOR DOORS AND WINDOWS. | | | -FLAT ROOF SYSTEM. | | | -STORM SHUTTERS FOR GLAZED OPENINGS. | | | 3-NEED TO RECORD A NOTICE OF | | | COMMENCEMENT(NOC). | | | 4-SEE COMMENTS BY ELECTRICAL PLAN | | | REVIEWER. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT JULIO GOMEZ AT 659-8096 EXT. | | | 8232. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-19 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-02-19 |
Time |
13:54 |
Sent To |
B |
|
| Notes |
| 2002-02-19 00:00:00 | PLEASE NOTE THE 3-#3 CONDUCTORS FROM THE | | | MAIN TO THE SUBPANEL WITH A #6 GROUND | | | NOT ALLOWED IN A 1" CONDUIT. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/ 659-8096 EXT.8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-03-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-11 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-11 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2001-03-11 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE, NOW THAT A RISER | | | DIAGRAM IS SUBMITTED SHOWING WHERE | | | POWER IS COMING FROM. PLEASE NOTE THAT A | | | LOAD CALCULATION OF EXISTING SERVICE | | | ISNEEDED. PER 220-3-C-1 | | | | | | 2)NOTE: FROM FIRTS NOTES, PLEASE SHOW | | | GROUNDING AT DETACHED STRUCTURE. MUST | | | HAVE GROUND RODE AND COLD WATER BOND, | | | PER ART250 | | | | | | 3)NOTE: PLEASE NOTE FROM FIRST REVIEW | | | NOTES, BATH CIRCUIT PER 210-11-C-3. | | | PLAN SHOWS FEEDING OUTSIDE OUTLET? | | | SHARING | | | CIRCUIT WITH BATH OUTLET IS NOT | | | PERMITTED. | | | | | | 4)NOTE: PLEASE CLARIFY LOAD FOR WATER | | | HEATER? PLAN SHOWS 8/2 FEED.SUBMIT | | | SIZE OF WATER HEATER. | | | | | | 5)NOTE: PLEASE NOTE A MEANS OF EGRESS | | | LIGHTING IS REQ`D AT DOOR. PER 210-70. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION, IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-11 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-10 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2001-01-11 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PER NEC ART 225-31. A MEANS OF | | | DISCONNECT AND PANEL IS REQ`D AT THE | | | DETACHED STRUCTURE.PLEASE SUBMIT RISER | | | DIAGRAM SHOWING THIS. PLEASE SUBMIT | | | PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE NOTE PER 210-11-C-3 ALL | | | REQ`MENTS ARE TO BE MET. MUST BE 20AMP | | | AND #12. DEDICATED CIRCUIT(S). | | | | | | 3)NOTE: PLEASE SHOW GROUNDING AT | | | DETACHED STRUCUTRE PER 250-50. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATIONFOR | | | REVIEW, IF THERE ARE ANY QUESTIONS, PLE | | | SE CALL; | | | | | | DEWEY PLLMER | | | ELECTRCIAL PLAN REVIEW | | | 659-8096 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-11 |
Time |
20:07 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-11 |
Time |
19:11 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-01-11 |
Time |
19:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-01-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-01-04 |
Time |
16:43 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO LIVING QUARTERS FOR RENTAL PURPOSES, | | | UTILITY ROOM ONLY |
|
|