Plan Review Details - Permit 01010035
Plan Review Stops For Permit 01010035
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-01 Cont ID  
Sent By jgomez Date 2002-03-01 Time 16:50 Rev Time 1.50
Received By jgomez Date 2002-03-01 Time 16:50 Sent To  
Notes
2002-03-01 00:00:00APPROVED WITH PROVISO:
  
 1-SEE COMMENTS ON DRAWINGS.
 2-PROVIDE UPDATED PRODUCT APPROVAL FOR
 EXTERIOR DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-03-20 Cont ID  
Sent By btrobaug Date 2002-02-19 Time 15:38 Rev Time 1.00
Received By jgomez Date 2001-03-20 Time 10:40 Sent To  
Notes
2001-03-20 00:00:00CHECKLIST:
  
 1-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS. PROVIDE KEY PLAN AND A
 COMPLETE INSTALLATION SCHEDULE (SEE
 CITY SAMPLE ATTACHED).
 CLEARLY INDICATE MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
  
 2-ROOF FRAMING PLAN SHOWS 2X6 JOISTSTO
 BE SUPPORTED ON SINGLE 2X6:
 -SINGLE 2X6 IS NOT ADEQUATE TO SUPPORT
 THIS LOAD.
 -SPECIFY GRADE OF LUMBER TO BE USED.
 -SPECIFY WHERE IS THE 2X6 BEAM RESTING
 ON AT THE ENDS. SPECIFY POST AND
 ATTACHMENTS. TOP AND BOTTOM.
  
 3-PROVIDE COMPLETE SECTION SHOWING ALL
 INFORMATION: STUDS SIZE AND SPACING,
 INSULATION, CONNECTORS TOP AND BOTTOM,
 ROOF VENTILATION, ROOF SHEATHING
 FASTENING, WALL SHEATHING AND STUCCO,
 ETC.
  
 4-PROVIDE COMPLETE PRODUCT APPROVAL FOR
 OUTSWING ENTRY DOOR.
  
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By jgomez Date 2001-01-22 Time 09:58 Rev Time 1.00
Received By jgomez Date 2001-01-22 Time 12:13 Sent To  
Notes
2001-01-22 00:00:00CHECKLIST:
  
 1-PROVIDE CONNECTION DETAILS. SPECIFY
 CONNECTORS TOP AND BOTTOM. SPECIFY
 ROOF CONNECTORS.
 2-PROVIDE PRODUCT APPROVALS FOR:
 -EXTERIOR DOORS AND WINDOWS.
 -FLAT ROOF SYSTEM.
 -STORM SHUTTERS FOR GLAZED OPENINGS.
 3-NEED TO RECORD A NOTICE OF
 COMMENCEMENT(NOC).
 4-SEE COMMENTS BY ELECTRICAL PLAN
 REVIEWER.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT JULIO GOMEZ AT 659-8096 EXT.
 8232.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-02-19 Cont ID  
Sent By btrobaug Date 2002-02-19 Time 15:38 Rev Time 0.00
Received By btrobaug Date 2002-02-19 Time 13:54 Sent To B
Notes
2002-02-19 00:00:00PLEASE NOTE THE 3-#3 CONDUCTORS FROM THE
 MAIN TO THE SUBPANEL WITH A #6 GROUND
 NOT ALLOWED IN A 1" CONDUIT.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/ 659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-11 Cont ID  
Sent By dpalmer Date 2001-03-11 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2001-03-11 Time 11:44 Sent To  
Notes
2001-03-11 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, NOW THAT A RISER
 DIAGRAM IS SUBMITTED SHOWING WHERE
 POWER IS COMING FROM. PLEASE NOTE THAT A
 LOAD CALCULATION OF EXISTING SERVICE
 ISNEEDED. PER 220-3-C-1
  
 2)NOTE: FROM FIRTS NOTES, PLEASE SHOW
 GROUNDING AT DETACHED STRUCTURE. MUST
 HAVE GROUND RODE AND COLD WATER BOND,
 PER ART250
  
 3)NOTE: PLEASE NOTE FROM FIRST REVIEW
 NOTES, BATH CIRCUIT PER 210-11-C-3.
 PLAN SHOWS FEEDING OUTSIDE OUTLET?
 SHARING
 CIRCUIT WITH BATH OUTLET IS NOT
 PERMITTED.
  
 4)NOTE: PLEASE CLARIFY LOAD FOR WATER
 HEATER? PLAN SHOWS 8/2 FEED.SUBMIT
 SIZE OF WATER HEATER.
  
 5)NOTE: PLEASE NOTE A MEANS OF EGRESS
 LIGHTING IS REQ`D AT DOOR. PER 210-70.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-11 Cont ID  
Sent By dpalmer Date 2001-01-11 Time 14:24 Rev Time 0.00
Received By dpalmer Date 2001-01-10 Time 14:24 Sent To  
Notes
2001-01-11 00:00:00************** UNSAT ****************
  
 1)NOTE: PER NEC ART 225-31. A MEANS OF
 DISCONNECT AND PANEL IS REQ`D AT THE
 DETACHED STRUCTURE.PLEASE SUBMIT RISER
 DIAGRAM SHOWING THIS. PLEASE SUBMIT
 PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE PER 210-11-C-3 ALL
 REQ`MENTS ARE TO BE MET. MUST BE 20AMP
 AND #12. DEDICATED CIRCUIT(S).
  
 3)NOTE: PLEASE SHOW GROUNDING AT
 DETACHED STRUCUTRE PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATIONFOR
 REVIEW, IF THERE ARE ANY QUESTIONS, PLE
 SE CALL;
  
 DEWEY PLLMER
 ELECTRCIAL PLAN REVIEW
 659-8096

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-01-11 Cont ID  
Sent By jleech Date 2001-01-11 Time 20:07 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-11 Cont ID  
Sent By jleech Date 2001-01-11 Time 19:11 Rev Time 0.33
Received By jleech Date 2001-01-11 Time 19:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-04 Cont ID  
Sent By sgraham Date 2001-01-04 Time 16:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO LIVING QUARTERS FOR RENTAL PURPOSES,