Plan Review Details - Permit 01010021
Plan Review Stops For Permit 01010021
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-06-26 Cont ID  
Sent By rmcdouga Date 2001-06-26 Time 12:47 Rev Time 1.00
Received By rmcdouga Date 2001-06-06 Time 12:44 Sent To  
Notes
2001-06-26 00:00:00REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-28 Cont ID  
Sent By jwitmer Date 2001-02-28 Time 11:10 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-02-07 Cont ID  
Sent By jwitmer Date 2001-02-07 Time 16:27 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-07 00:00:00THE SAME THREE COMMENTS AS THE FIRST
 REVIEW:
 1)- SHEET A1 MAKES REFRENCE TO THE
 SOUTH FL BUILDING CODE IN SEVERAL PLACES
 THE CITY USES THE 1997 STANDARD BUILDING
 CODE. PLEASE REVISE AS NECESSARY.
 2)- THE PLANS DONOT CLEARLY NOTE THE
 REQUIRED USE OF FIRE RETARDANT TREATED
 WOOD BLOCKING IN PARTITIONS. SEE SBC
 609.1.2. SEE SHEETS A-9.
 3)- SHOW THE METHOD OF FIRE PROTECTION
 FOR THE NEW STEEL BEAMS, (2HR), AS
 REQUIREDBY SBC TABLE 600 FOR TYPE II
 CONSTRUCTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By hpiskura Date 2001-01-10 Time 09:44 Rev Time 0.00
Received By hpiskura Date 2001-01-10 Time 08:56 Sent To  
Notes
2001-01-10 00:00:001 SHEET A1 MAKES REFERENCE TO THE SOUTH
 FL BUILDING CODE IN SEVERAL PLACES.THE
 CITY USES THE 1997 STANDARD BUILDING
 CODE.PLEASE REVISE AS NECESSARY.
  
 2THE PLANS DO NOT CLEARLY NOTE THE
 REQUIRED USE OF FIRE RETARDANT TREATED
 WOOD BL0CKING IN PARTITIONS.SEE SBC
 609.2.
  
 3SHOW THE METHOD OF FIRE PROTECTION
 FOR THE NEW STEEL BEAMS, (2HR), AS
 REQUIRED BY SBC TABLE 600 FOR TYPE II
 CONSTRUCTION.
  
 HAROLD PISKURA

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 20:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 18:26 Sent To  
Notes
2001-03-06 00:00:00********* PROVISO / REVISION ***********
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST AND
 SECOND REVIEW. PLEASE NOTE AIC RATING
 FOR NEW 200A DISCONNECT FROM BUS DUCT
 DOES NOT SHOW AIC RATING?????
 PLEASE REVISE ELECTRICAL SHEET AND
 SUBMIT FOR REVIEW BEFORE ANY ELECTRICAL
 INSPECTIONS IS CALLED IN!!!!
  
 THIS IS A REVISION AND A FEE WILL BE DUE
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-14 Cont ID  
Sent By dpalmer Date 2001-02-14 Time 19:42 Rev Time 0.00
Received By dpalmer Date 2001-02-14 Time 19:42 Sent To  
Notes
2001-02-14 00:00:00****************** UNSAT ***************
  
 1)NOTE: SAME NOTES FROM FIRST REVIEW
 WERE NOT ADDRESSED.PANEL AIC RATINGS ARE
 SHOWN BUT NOT FOR DISCONNECT FEEDING
 PANEL "HE2" PLANS ARE COMING BACK FOR
 BLDG COMMENTS. PLEASE SUBMIT.
  
  
 PLEASE SUBMIT FOR REVIEW IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 21:16 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 21:16 Sent To  
Notes
2001-01-17 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 PLEASE NOTE AIC RATING FOR MAIN?
 PLEASE PROVIDE CLARIFICATION ON MAIN
 DISCONNECT. 200/220A. 220A? IS NOT A
 STANDARD SIZE UNDER 240-6. TYPE O
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-02-02 Cont ID  
Sent By lsmith Date 2001-02-02 Time 08:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-14 Cont ID  
Sent By mcarsill Date 2001-02-14 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2001-02-14 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-11 Cont ID  
Sent By mcarsill Date 2001-01-11 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2001-01-11 Time 10:06 Sent To  
Notes
2001-01-11 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS.
 3) ADDITIONAL EMERGENCY LIGHTING APPEARS
 TO BE NEEDED IN CORRIDORS OF SPACE.
 4) THE FIRE ALARM NOTES SECTION
 INDICATES CLASS B, STYLE C CIRCUITS.
 ONLY CLASS A, STYLE D CIRCUITS ALLOWED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-06-19 Cont ID  
Sent By pkrauss Date 2001-06-19 Time 12:28 Rev Time 0.30
Received By pkrauss Date 2001-06-19 Time 12:14 Sent To  
Notes
2001-06-19 00:00:00AS BUILT DRAWINGS. 6/19/01
 MECHANICAL PERMIT 01031276

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-29 Cont ID  
Sent By pkrauss Date 2001-03-29 Time 12:16 Rev Time 0.35
Received By pkrauss Date 2001-03-29 Time 11:55 Sent To  
Notes
2001-03-29 00:00:00DRAWING M0-1 VAV BOX SCHEDULE NEEDS TO
 REFLECT NEW VAV ADDED IN ROOM 220 ON
 DRAWING M2-1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-02-02 Cont ID  
Sent By ndenmark Date 2001-02-02 Time 07:44 Rev Time 0.35
Received By ndenmark Date 2001-02-02 Time 07:44 Sent To  
Notes
2001-02-02 00:00:00PROVISO:
 1. FIELD VERIFY RATING OF WALL AT COMMON
 AREA BATHROOMS. FIRE DAMPER WILL BE
 REQUIRED IF WALL IS RATED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-04-14 Cont ID  
Sent By jleech Date 2001-04-14 Time 11:06 Rev Time 0.33
Received By jleech Date 2001-04-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-21 Cont ID  
Sent By pschmitz Date 2001-01-21 Time 08:37 Rev Time 1.25
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-21 00:00:00PROVISO,SHT.P-1 AIR CHAMBERS COMPLY W/ S
 PC 94 SEC 607.8.3
 BREAK RM SINK COMPLY W/FACBC 4.25 KNEE
 CLEARANCE CLEAR FLR SPACE.PES

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-02-02 Cont ID  
Sent By lsmith Date 2001-02-02 Time 08:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***