Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By hpiskura Date 2001-01-19 Time 11:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-14 Cont ID  
Sent By dpalmer Date 2001-02-14 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2001-02-14 Time 20:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 21:45 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 21:45 Sent To  
Notes
2001-01-17 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 2)NOTE: PLEASESHOW ALL NEW BRANCH
 CIRCUIT #`S ON PLANS AND CORRELATE WITH
 PANEL SCHEDULES. SHOW PANEL SCHEDULES.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION ON
 ATS.GENERATOR/ BLDG MAIN(S) LOCATIONS.
 PLEASE PROVIDE CLARIFICATION OF GROUPING
 OF MAINS. PER 230-72/23-72
  
 4)NOTE: PLEASE NOTE, DEPENDING ON
 LOCATION OF THE ABOVE IN NOTE 3. A
 INLINE DISCONNECT MAY BE REQ`D FROM
 GENERATOR TO ATS.
  
 5)NOTE: PLEASE SEE 230-76 AND 230-79 FOR
 #12 NOTE ON E-5. SHUNT TRIP SHOWN?
 THISIS NOT AN ACCEPTABLE MEANS OF
 DISCONNECTPER THE ABOVE ARTS.
  
 6)NOTE: PLEASE NOTE, THAT I HAVE SEEN
 THE NOTE ON THE TOP OF E-5 PERTAINING
 TO-CIRCUITPANELS/ AND CALCULATIONS.
 THE FOLLOWING MUST BE SUBMITTED. ALL NEW
 EQUIPMENT MUST HAVE PANEL SCHEDULES
 SHOWN. I WILL ACCEPT EXISTING
 PANELS/CIRCUIT TO BE REVISED. ALL NEW
 MUST BE SHOWN. PLEASE ALSO NOTE THAT
 THE LOAD CALCULATIONS ARE REQ`D AT THE
 PRESENT TIME. PLEASE MAKE SURE ALL
 CONTINUOUS LOADS ARE SHOWN AT 125%.
  
 7)NOTE: PLEASE SHOW THE GFI OUTLET REQ`D
 FOR A/C EQUYIPMENT PER 210-63 OF NEC
 AND 309.1 OF MECH CODE.
  
 8)NOTE: PLEASE SEE E-5 #46 NOTE SAYS
 NEMA 3R DISCONNECT. SIZE? VOLTAGE? ETC.
 PLEASE PROVIDE MORE INFORMATION ON #43
 NOTE.
  
 9)NOTE: PLEASE SEE E-1 PLEASE SHOW PANEL
 C-1. ALSO POWER CONDITIONER LOCATION.
  
 10)NOTE:PLEASE SHOW GROUNDING FOR
 GENERATOR PER 250 OF NEC.
  
 11)NOTE: PLEASE LIST VOLTAGES OF ALL
 NEWAND EXISTING EQUIPMENT. IF ANY OF
 THESE ARE 277/480V PLANS ARE TO SIGNED
 AND SEALED BY A PE. UNDER SEC 553-79 6A
 OF THE F.A.C.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-01-24 Cont ID  
Sent By lsmith Date 2001-01-24 Time 16:35 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By mcarsill Date 2001-02-15 Time 13:34 Rev Time 0.00
Received By mcarsill Date 2001-02-15 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By mcarsill Date 2001-01-09 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2001-01-09 Time 13:27 Sent To  
Notes
2001-01-09 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 2) PLEASE SUBMIT FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILING OF TENANT SPACE.
 4) PLEASE PROVIDE MORE ADDITIONAL
 INFORMATION ON NOTE 120, SHEET A-3,
 "WATER CURTAIN".
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-13 Cont ID  
Sent By pkrauss Date 2001-02-13 Time 15:58 Rev Time 0.33
Received By pkrauss Date 2001-02-13 Time 15:58 Sent To  
Notes
2001-02-13 00:00:00PROVISO:RTU-11 IS IN A "HARD CEILING"
 (DRAWING A-2), IF SMOKE DETECTOR IS IN
 THE DUCT ABOVE THE CEILING AN ACCESS
 DOOR MUST BE PROVIDED AS PER 1997 SMC
 304.2, FOR ACCESSIBILITY AND SERVICE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-01-29 Cont ID  
Sent By ndenmark Date 2001-01-29 Time 09:09 Rev Time 1.00
Received By ndenmark Date 2001-01-29 Time 09:08 Sent To  
Notes
2001-01-29 00:00:00****************DENIED******************
 1. INSUFFICIENT INFORMATION TO PROVIDE
 COMPLETE REVIEW.
 2. PLEASE CLARIFY MECH PLAN NOTES , I.E.
 UNABLE TO LOCATE NOTES E,H, I, J, K, L,
 AND M. UNABLE TO TELL IF O OR Q IS
 SHOWN, UNABLE TO LOCATE THE OTHER
 LETTER.
 3. ELECTRICAL PLAN SHOWS 10 DUCT SMOKE
 DETECTORS. MECH SHOWS 7 RTU'S. SEVERAL
 DUCT SMOKE DETECTORS APPEAR ON CHASE
 WALLS,PROVIDE INFORMATION ON WHAT UNITS
 THESE SERVE.
 4. NOTE 14 INDICATES AUX. PAN FOR AHU'S,
 WHERE ARE THESE AHU'S ?
 5. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2. NOTE THAT
 IF EXHAUST FANS ARE SWITCHED W/ BATHROOM
 LIGHTS THEY CAN'T BE USED FOR AIR
 BALANCE.
 6. PROVIDE INFORMATION ON EMERGENCY
 GENERATOR REQARDING LOCATION OF
 EQUIPMENT AND EXHAUST LOCATION AND
 TERMINATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-21 Cont ID  
Sent By jleech Date 2001-02-21 Time 17:42 Rev Time 1.00
Received By jleech Date 2001-02-21 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By jleech Date 2001-01-17 Time 14:57 Rev Time 1.00
Received By jleech Date 2001-01-17 Time 14:57 Sent To  
Notes
2001-01-17 00:00:00DENIED;
 1.SHOW MESSURMENTS OF HANDICAP STALLS.
 2.SHOW HANDICAP URINAL AND SPECIFICA-
 TIONS. WIDTH OF STALL AND HIGHTH ABOVE
 THE FLOOR.
 3.BREAK ROOM SINK MUST COMPLY WITH FACBC
 4.24.1 THRU 4.24.7. SHOW DRAWING.
 4.SHOW H2O AND SANITARY RISER DIAGRAM.
 5.AIR CHAMBERS MUST COMPLY WITH 94 SPC
 607.8.2.
 6.PAGE P-1 NOTE B OFFSET FLOOR FLANGES
 ARE NOT PERMITTED IN WEST PALM BEACH.
 7.CLEAR SPACE UNDER LAV. IS 29" NOT 30"
 NOTE 39 PAGE A-1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-01-24 Cont ID  
Sent By lsmith Date 2001-01-24 Time 16:35 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***