Plan Review Details - Permit 00121285
Plan Review Stops For Permit 00121285
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-30 Cont ID  
Sent By jwitmer Date 2001-01-30 Time 11:54 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-30 00:00:00PROVISO: FL ACCESSIBILITY CODE 4.13.5
 DOORS REQUIRE A CLEAR 32" OPENING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-08 Cont ID  
Sent By jwitmer Date 2001-01-08 Time 15:37 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW
 1)- FL. ACCESSIBILITY CODE-4.13.5 DOORS
 CLEAR WIDTH: DOORWAYS SHALL HAVE A MIN-
 IMUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
 THE RESTROOM DOORS NEED TO BE REPLACED
 SINCE THEY DO NOT CONFORM WITH THE
 ACCESSIBILITY CODE.
 THE FLORIDA ACCESSIBILITY CODE 4.1.6.2.2
 ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION.ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH TO AN ALTERED
 AREAS SHALL BE DEEMED DISPROPORTINATE TO
 THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20% OF THE ALTERTIONTO THE PRI-
 MARY FUNCTION AREA.
 20% OR $2400.00 WILL HAVE TO GO INTO UP-
 GRADING THE BUILDING TO MEET THE CURRENT
 ACCESSIBILITY CODE.
 THERE IS ORDER IN CHOOSING WHICH SCCESS-
 IBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT
 WILL PROVIDE THE GREASTEST ACCESS, IN
 THE FOLLOWING ORDER:
 1 AN ACCESSIBLE ENTRANCE- OK.
 2AN ACCESSIBLE ROUTE TO THE ALTERED
 AREA-OK.
 3 AT LEAST ONE ACCESSIBLE RESTROOM FOR
 EACH SEX OR A SINGGLE UNISEX RESTROOM.
  
 THIS IS WHERE THE BUILDING NEEDS TO BE
 UPDATED.IF THE 20% HASN'T BEEN REACHED
 THE NEXT ITEM IS:
 4 ACCESSIBLE TELEPHONES.
 5 ACCESSIBLE DRINKING FOUNTAINAND
 6 ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS
 PARKING, STORAGE & ALARMS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 22:10 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 22:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-08 Cont ID  
Sent By dpalmer Date 2001-01-08 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2001-01-08 Time 18:35 Sent To  
Notes
2001-01-08 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED. ALL
 PANELS/MAINS/BRKRS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE SUBMIT MORE DETAIL ON THE
 PANEL SCHEDULES SHOWING WIRE SIZES AND
 BRKR SIZES TO CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-29 Cont ID  
Sent By mcarsill Date 2000-12-29 Time 15:24 Rev Time 0.00
Received By mcarsill Date 2000-12-29 Time 15:24 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE EMERGENCY LIGHTING EQUIPMENT
 IF NOT ALREADY PRESENT IN EACH REMODELED
 TENANT SPACE.
 2) NEW CEILING TILES TO MEET INTERIOR
 FLAME SPREAD OF AT LEAST CLASS A OR B.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By ndenmark Date 2001-01-19 Time 10:06 Rev Time 0.33
Received By ndenmark Date 2001-01-19 Time 10:06 Sent To  
Notes
2001-01-19 00:00:00PROVISO
 MIN. CLEARANCE 18" REQUIRED BETWEEN ROOF
 SURFACE AND BOTTOM OF SUPPORT STRUCTURE
 OF STAND.