Plan Review Details - Permit 00121282
Plan Review Stops For Permit 00121282
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-28 Cont ID  
Sent By jgomez Date 2001-02-28 Time 11:58 Rev Time 2.00
Received By jgomez Date 2001-02-28 Time 11:58 Sent To  
Notes
2001-02-28 00:00:00PROVISO:
  
 1-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-02-15 Cont ID  
Sent By jgomez Date 2001-02-15 Time 18:20 Rev Time 2.50
Received By jgomez Date 2001-02-15 Time 18:20 Sent To  
Notes
2001-02-15 00:00:00SECOND CHECKLIST:
 1-IMPACT FEES ARE STILL NOT PAID. PAY
 IMPACT FEES TO PALM BEACH COUNTY, GET
 DRAWINGS STAMPED AND BRING RECEIPT.
 2-STORM PANELS INFORMATION IS STILL
 INCOMPLETE:
 -NEED KEY PLAN THAT MATCHES MODEL.
 -STORM PANEL DWG # 01-246 CAN'T BE USED
 AS A REFERENCE BECAUSE IT IS NOT PART
 OF THE DRAWINGS APPROVED IN THE SBCCI
 EVALUATION REPORT.
 -SEE LIMITATIONS ON SHEET 3 OF 3 OF
 SBCCI REPORT REGARDING THE USE OF TRU-
 FAST TAP GRIP ANCHORS. CHECK THE MIN.
 COMPRESSIVE STRENGTH OF CONCRETE
 MASONRY UNITS.
 -CLEARLY INDICATE ON ANCHOR SCHEDULE
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AN SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,
 MIN. EDGE DISTANCE, MAX. PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (NOTE: THIS IS CONCRETE
 BLOCK CONSTRUCTION, NOT CONCRETE).
 -THIS COMPLETE INFORMATION MAY BE
 SUBMITTED UNDER A SEPARATE PERMIT.
 3-ROOF FRAMING PLAN:
 -SPECIFY CONNECTORS THAT WILL RESIST
 THE LOADS AS CALCULATED ON THE
 ENGINEERED TRUSSES. EG: SEE TRUSSES
 MG2 AND HG1.
 4-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -GARAGE SIDE DOOR AND OTHER FRENCH
 DOORS. SEE SIZES SPECIFIED ON PLANS.
 -WINDOW MULLIONS, SINGLE HUNG WINDOWS,
 ARCHED WINDOWS & SLIDING GLASS DOORS.
 PRODUCT APPROVAL FROM NORANDEX IS NOT
 ACCEPTABLE UNLESS IT IS SIGNED, SEALED
 AND DATED BY THE ENGINEER OF RECORD
 FOR THIS SPECIFIC LOCATION.
 5-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS TO SBC 1997.
 NOTE: THIS REPORT WAS NEVER SUBMITTED
 TO THE CITY.
 -ALSO, DENSITY TESTS SUBMITTED HAVE THE
 WRONG LOT AND THE NAME OF THE BUILDER
 IS DIFFERENT. WHY?.
  
  
  
  
  
 JULIO GOMEZ, BUILDING PLAN REVIEWER,
 659-8096 EXT. 8232.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-24 Cont ID  
Sent By jgomez Date 2001-01-24 Time 15:16 Rev Time 3.00
Received By jgomez Date 2001-01-24 Time 15:16 Sent To  
Notes
2001-01-24 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING RECEIPT AND STAMPED DRAWINGS.
 2-STORM PANELS:
 -PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE (SEE CITY SAMPLE).
 -SPECIFY/CIRCLE SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TO BE USED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO.
 -DRAWINGS AND PRODUCT APPROVAL REPORT
 DON'T MATCH.
 -INFORMATION MAY BE SUBMITTED AT A
 LATER TIME UNDER A SEPARATE PERMIT.
 3-SEE COMMENTS ON PLANS. INCLUDING THOSE
 BY THE OTHER TRADES.
 4-TRUSS DRAWINGS:
 -ENGINEERED TRUSSES TO HAVE ORIGINAL
 SIGNATURE, DATE AND SEAL. CHAPTER 471
 OF FLORIDA STATUTES.
 -UPDATE GENERAL DETAILS AND SIGN, SEAL
 AND DATE ACCORDINGLY. CHAPTER 471.
 -TRUSS LAYOUT TO HAVE ENGINEER'S SEAL,
 DATE AND SIGNATURE ALONG WITH INFO.
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 -CLEARLY INDICATE ON ENGINEERED TRUSSES
 AND TRUSS LAYOUT WHO REVIEW THEM.
 NAME OF COMPANY.
 -TRUSS LAYOUT AND ROOF FRAMING PLAN ON
 SHEET 3A DON'T MATCH. REVISE EITHER
 ONE TO MATCH AND SPECIFY CONNECTORS
 ACCORDINGLY.
 -REVISE CONNECTOR SCHEDULE SO THAT
 SUCH CONNECTORS WILL RESIST THE UPLIFT
 LOADS AS CALCULATED IN THE ENGINEERED
 TRUSSES.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 INTERIOR BEARING WALL. STUD SPACING IS
 MISSING ON DETAIL SHOWN ON SHEET 3A.
 6- PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -DOUBLE ENTRY DOORS. SEE SIZE ON PLANS.
 -GARAGE SIDE DOOR. SEE SIZE ON PLANS.
 -WINDOW MULLIONS.
 -FRENCH DOORS. SEE SIZE ON PLANS.
 -SINGLE HUNG WINDOWS.
 -ARCHED WINDOWS.
 -GLASS BLOCK.
 -SLIDING GLASS DOORS. SEE SIZE ON
 PLANS7-SPECIFY SAFETY GLASS WHERE
 REQUIRED BY
 2405.2 SBC 1997. SEE PLANS.
 8-SPECIFY POSTS TO SUPPORT GIRDER TRUSS.
 SEE COMMENTS ON ROOF FRAMING PLAN.
 9-PROVIDE SOIL TEST REPORT AS PER CITY
 AMENDMENTS SECTION 1804.2.7 AND TABLE
 1804.2.7.3.
 NOTE: DENSITY TEST REPORT SUBMITTED
 WAS DONE AS PER SOUTH FLORIDA BUILDING
 CODE (BROWARD EDITION). CITY OF W.P.B.
 STANDARD O EXPEDITE THE REVIEW.
 USES THE STANDARD BUILDING CODE, 1997.
 REVISE AS REQUIRED.
  
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE, IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-06-25 Cont ID  
Sent By jleahy Date 2001-06-25 Time 12:51 Rev Time 0.45
Received By jleahy Date 2001-06-25 Time 12:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 16:29 Sent To  
Notes
2001-06-04 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE SET
 OF REVISIONS WERE SUBMITTED. WE NEED
 ONE THAT STAYS FOR RECORD AND ONE THAT
 GOES BACK TO CONTRACTOR.
  
 2)NOTE: PLEASE ALSO NOTE THAT PER F.S.
 AND F.A.C. ALL CHANGES ON PLANS MUST BE
 DONE BY THE ARCH/ENG OF RECORD.
 481.221 AND 471.025.
 PLANS NEED TO BE REPRINTED AND SIGNED
 AND SEALED BY ENGINEER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 19:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 18:30 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 18:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 11:06 Rev Time 0.25
Received By jleech Date 2001-01-13 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-01 Cont ID  
Sent By kstevens Date 2001-06-01 Time 17:10 Rev Time 0.25
Received By kstevens Date 2001-06-01 Time 17:09 Sent To  
Notes
2001-06-01 00:00:00REVIEW NOTES:
  
 SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 11:06 Rev Time 0.25
Received By jleech Date 2001-01-13 Time 11:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-09 Cont ID  
Sent By sgraham Date 2001-01-09 Time 11:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***