Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-29 Cont ID  
Sent By mcarsill Date 2000-12-29 Time 15:44 Rev Time 0.00
Received By mcarsill Date 2000-12-29 Time 15:44 Sent To  
Notes
2001-01-08 00:00:001) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 2) WHEN ACTIVATED, THE FIRE ALARM SYSTEM
 IS TO BE AUDIBLE THROUGHOUT THE
 BUILDING.
 3) THE PERFORMANCE HALL PORTION OF THE
 FIRE ALARM SYSTEM IS TO BE TESTED WITH
 FIRE RESCUE PERSONNEL.
 4) HOOD SUPPRESSION SYSTEMS TO BE
 CONNECTED TO BUILDINGS FIRE ALARM
 SYSTEM.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497