Plan Review Details - Permit 00121276
Plan Review Stops For Permit 00121276
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-28 Cont ID  
Sent By jgomez Date 2001-02-28 Time 10:30 Rev Time 2.00
Received By jgomez Date 2001-02-28 Time 10:30 Sent To  
Notes
2001-02-28 00:00:00PROVISO:
  
 1-STORM SHUTTERS TO BE DONE UNDER A
 SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-02-15 Cont ID  
Sent By jgomez Date 2001-02-15 Time 19:49 Rev Time 2.50
Received By jgomez Date 2001-02-15 Time 19:49 Sent To  
Notes
2001-02-15 00:00:00SECOND CHECKLIST:
 1-IMPACT FEES ARE STILL NOT PAID. PAY
 IMPACT FEES TO PALM BEACH COUNTY AND
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-STORM PANELS INFORMATION IS STILL
 INCOMPLETE:
 -NEED KEY PLAN THAT MATCHES MODEL.
 -STORM PANEL DWG #01-246 CAN'T BE USED
 AS A REFERENCE BECAUSE IT IS NOT PART
 OF THE DRAWINGS APPROVED IN THE SBCCI
 EVALUATION REPORT.
 -SEE LIMITATIONS ON SHEET 3 OF 3 OF
 SBCCI REPORT REGARDING THE USE OF TRU-
 FAST TAP GRIP ANCHORS. CHECK THE MIN.
 COMPRESSIVE STRENGTH OF CONCRETE
 MASONRY UNITS.
 -CLEARLY INDICATE ON ANCHOR SCHEDULE
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,
 MIN. EDGE DISTANCE, MAX. PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (NOTE: THIS IS CONCRETE
 BLOCK CONSTRUCTION, NOT CONCRETE).
 -ALL THIS INFORMATION MAY BE SUBMITTED
 UNDER A SEPARATE PERMIT.
 3-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -GARAGE SIDE DOOR. SEE SIZE SPECIFIED
 ON PLANS.
 -WINDOW MULLIONS, SINGLE HUNG WINDOWS,
 RECTANGULAR WINDOWS & ARCHED WINDOWS.
 NORANDEX PRODUCT APPROVAL IS NOT
 ACCEPTABLE UNLESS IT IS SIGNED, SEALED
 AND DATED BY THE ENGINEER OF RECORD
 FOR THIS SPECIFIC LOCATION.
 4-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS TO SBC 1997.
 NOTE: THIS REPORT WAS NEVER SUBMITTED
 TO THE CITY FOR REVIEW.
 -ALSO, CLARIFY WHY DENSITY TEST
 SUBMITTED IS DONE WITH THE NAME OF
 ANOTHER BUILDER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-23 Cont ID  
Sent By jgomez Date 2001-01-23 Time 19:22 Rev Time 3.00
Received By jgomez Date 2001-01-23 Time 19:22 Sent To  
Notes
2001-01-23 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-REVISE ENERGY CALCULATIONS:
 -THERE ARE 4 BEDRMS, NOT 3. SEE PLANS.
 -REVISE A/C AREA AND CEILING AREA AS
 REQUIRED TO MATCH PLANS.
 -PROVIDE ORIGINAL SIGNATURES.
 3-STORM PANELS:
 -PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE (SEE CITY SAMPLE).
 -SPECIFY/HIGHLIGHT/CIRCLE SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TO BE
 USED ACCORDING TO MEAN ROOF HEIGHT,
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO.
 -DRAWINGS AND PRODUCT APPROVAL REPORT
 DON'T MATCH.
 4-INTERIOR BEARING PARTITION FOOTING TO
 HAVE 16" MIN. DEPTH AS PER SECTION
 1804.1.3 SBC 1997 AND SECTION
 1804.1.9 CITY AMENDMENTS TO SBC 1997.
 5-SEE COMMENTS ON PLANS. INCLUDING THOSE
 BY THE OTHER TRADES.AND REVISE/UPDATE.
 6-REAR ELEVATION AND FLOOR PLAN DON'T
 MATCH. SEE COLUMN BET. FRENCH DOORS.
 7-TRUSS DRAWINGS:
 -ENGINEERED TRUSSES TO HAVE ORIGINAL
 SIGNATURE, DATE AND SEAL. FL. STATUTES
 -UPDATE GENERAL DETAILS AND SIGN, SEAL
 AND DATE ACCORDINGLY. 471 FL. STATUTES
 -TRUSS LAYOUT TO HAVE ENGINEER'S
 SEAL, DATE AND SIGNATURE ALONG WITH
 INFORMATION AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES.
 -CLEARLY INDICATE ON ENGINEERED TRUSSES
 AND TRUSS LAYOUT WHO REVIEWED THEM.
 -REVISE ROOF CONNECTOR SCHEDULE SHOWING
 CONNECTORS THAT WILL RESIST THE UPLIFT
 LOADS CALCULATED IN THE ENGINEERED
 TRUSSES. SEE COMMENTS ON SHEET 3B.
 8-PROVIDE COMPLETE SPECIFICATIONS FOR
 INTERIOR BEARING WALL: STUD SPACING
 AND MAXIMUM UNSUPPORTED STUD HEIGHT.
 DETAIL ON SHEET 3B LACKS THIS INFO.
 9-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVALS FOR:
 -ENTRY DOOR WITH SIDELITE ASSEMBLY
 (WITH LEGIBLE DRAWINGS).
 -GARAGE SIDE DOOR.
 -WINDOW MULLIONS.
 -FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY
 (OR AS SHOWN ON REAR ELEVATION).
 -SINGLE HUNG WINDOWS.
 -RECTANGULAR AND ROUND FIXED WINDOWS.
 10-PROVIDE SOIL TEST REPORT AS PER SECT.
 1804.2.7 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS. (NOT SOUTH FLORIDA BLDG
 CODE -BROWARD EDITION).
 11-SOIL TEST REPORT AS PER SEC 1804.2.7
 AND TABLE 1804.2.7.3 CITY AMENDMENTS.
 NOT SFBC (BROWARD ED.).
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINALS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-06-25 Cont ID  
Sent By jleahy Date 2001-06-25 Time 12:51 Rev Time 0.45
Received By jleahy Date 2001-06-25 Time 12:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-06-04 Cont ID  
Sent By dpalmer Date 2001-06-04 Time 16:35 Rev Time 0.00
Received By dpalmer Date 2001-06-04 Time 16:35 Sent To  
Notes
2001-06-04 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE SET OF
 PLANS WERE SUBMITTED. THERE NEEDS TO BE
 ONE FOR RECORD AND ONE THAT COMES BACK
 TO CONTRACTOR FOR FIELD COPY
  
 2)NOTE: PLEASE NOTE THAT ALL CHANGES ON
 PLANS NEED TO BE DONE BY THE ARCH/ENG
 OFRECORD PER 471.025 AND 481.221.
 PLEASEHAVE PLANS REPRINTED WITH CHANGES
 AND SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 87372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 19:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 18:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 10:01 Rev Time 0.33
Received By jleech Date 2001-01-13 Time 10:01 Sent To  
Notes
2001-01-13 00:00:00R/A REQUIRED FROM MASTER SUITE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-01 Cont ID  
Sent By kstevens Date 2001-06-01 Time 17:08 Rev Time 0.25
Received By kstevens Date 2001-06-01 Time 17:08 Sent To  
Notes
2001-06-01 00:00:00REVIEW NOTES
  
 SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 10:03 Rev Time 0.25
Received By jleech Date 2001-01-13 Time 10:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-09 Cont ID  
Sent By sgraham Date 2001-01-09 Time 11:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***