| Plan Review Stops For Permit 00121116 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-22 |
Time |
09:26 |
Rev Time |
0.76 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-09 |
Time |
08:42 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2001-01-09 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | BUILDING PLAN REVIEW | | | 1). THE DRINKING FOUNTAIN IN THE VESTI- | | | BULE BLOCKS THE EGRESS OF THE RESTROOMS, | | | A REQUIRED 3'-0" IS THE MINIMUM ALLOWED | | | SEE SECTIONS SBC 1003.3.4/ 1003.2.3. | | | 2). THE PLANS CALL FOR THE TENANT SPACE | | | TO BE FIRE SPRINKLERED, SUBMIT PLANS & | | | CALCULATIONS FOR THE FIRE SPRINKLERS. | | | 3). SBC 803.2 INTERIOR FINISH MATERIALS | | | OTHER THANTHOSE APPLIED TO FLOORS | | | SHALL BE CLASSIFIED IN ACCORDANCE WITH | | | ASTM E 84. PLEASE SUBMIT A LIST OF FIN-I | | | SHES. | | | 4). SBC 1606.4.1- IMPACT GLAZING FROM | | | WINDBORN DEBRIS THE STOREFRONT GLAZING & | | | DOOR UNIT WILL REQUIRE PRODUCT TESTING, | | | 2 DADE COUNTY OR SBCCI REPORTSWILL BE | | | REQUIRED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-01 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-01 |
Time |
17:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-09 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-09 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | ***************** UNSAT | | | ***************** | | | 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL | | | OUTLET SPACING TO MEET LOCAL CODE PER | | | 210-50. EVERY 12` FOR OFFICE AREAS AND | | | EVERY 20` FOR STORAGE AREAS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-01-19 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-02-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-20 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-20 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-12-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-27 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-27 |
Time |
08:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS PROVIDED WITH | | | DRAWINGS. | | | 2) NO INTERIOR FINISH CLASSIFICATIONS | | | PROVIDED WITH DRAWINGS. | | | 3) FIRE ALARM SYSTEM EQUIPMENT SHOWN | | | ON DRAWINGS. PLEASE PROVIDE COMPLETE | | | FIRE ALARM SYSTEM SHOP DRAWINGS WITH | | | A PERMIT. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-28 |
Time |
15:11 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-02-28 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2001-02-28 00:00:00 | *******************NOTE***************** | | | | | | AUXILIARY DRAIN PAN MUST OVERFLOW | | | PROTECTION BY MEANS OF FLOAT SWITCH OR | | | DRAIN LINE, AS PER 1997 SMC 304.8.9.1. | | | | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR TIE | | | D TO HORN/STROBE PER NFPA 901 4-4.4.3. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-19 |
Time |
10:27 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-01-19 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2001-01-19 00:00:00 | PROVISO: | | | 1.ACCESSIBILITY FOR SERVICE REQUIRED | | | PER 1997 SMC 304.2 WITH RESPECT TO | | | BUILDING CONSTRUCTION. | | | 2. DUCT SMOKE DETECTORS REQUIRED FOR | | | BOTH AHU'S. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-03-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-02 |
Time |
10:57 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
2001-03-02 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-01-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-13 |
Time |
12:41 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2001-01-13 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2001-01-13 00:00:00 | DENIED; | | | 1.HANDICAP LAV. CLEARANCE FROM FLOOR TO | | | BOTTOM OF LAV.IS 29" PER. 97 FACBC | | | FIG. 31 PAGE 109. | | | 2.SINK SHALL BE MOUNTED WITH COUNTER NO | | | HIGHER THAN 34" FACBC 4.24.2 ALSO | | | COMPLY WITH 4.24.4 AND 4.24.6. | | | 3.DRINKING FOUNTAIN SHALL COMPLY WITH | | | FACBC SECS. 4.1.3 (10) AND 4.15. | | | PROVISIONS SHALL BE MADE FOR PEOPLE | | | WHO HAVE TROUBLE BENDING OR STOOPING. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-01-19 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|