Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-02-22 Cont ID  
Sent By jwitmer Date 2001-02-22 Time 09:26 Rev Time 0.76
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By jwitmer Date 2001-01-09 Time 08:42 Rev Time 4.00
Received By jwitmer Date 2001-01-09 Time 08:41 Sent To  
Notes
2001-01-09 00:00:00BUILDING PLAN REVIEW
 1). THE DRINKING FOUNTAIN IN THE VESTI-
 BULE BLOCKS THE EGRESS OF THE RESTROOMS,
 A REQUIRED 3'-0" IS THE MINIMUM ALLOWED
 SEE SECTIONS SBC 1003.3.4/ 1003.2.3.
 2). THE PLANS CALL FOR THE TENANT SPACE
 TO BE FIRE SPRINKLERED, SUBMIT PLANS &
 CALCULATIONS FOR THE FIRE SPRINKLERS.
 3). SBC 803.2 INTERIOR FINISH MATERIALS
 OTHER THANTHOSE APPLIED TO FLOORS
 SHALL BE CLASSIFIED IN ACCORDANCE WITH
 ASTM E 84. PLEASE SUBMIT A LIST OF FIN-I
 SHES.
 4). SBC 1606.4.1- IMPACT GLAZING FROM
 WINDBORN DEBRIS THE STOREFRONT GLAZING &
 DOOR UNIT WILL REQUIRE PRODUCT TESTING,
 2 DADE COUNTY OR SBCCI REPORTSWILL BE
 REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 17:40 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 17:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-01-09 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2001-01-09 Time 10:49 Sent To  
Notes
2001-01-09 00:00:00***************** UNSAT
 *****************
 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 OUTLET SPACING TO MEET LOCAL CODE PER
 210-50. EVERY 12` FOR OFFICE AREAS AND
 EVERY 20` FOR STORAGE AREAS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-01-19 Cont ID  
Sent By lsmith Date 2001-01-19 Time 14:39 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-20 Cont ID  
Sent By mcarsill Date 2001-02-20 Time 15:26 Rev Time 0.00
Received By mcarsill Date 2001-02-20 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-27 Cont ID  
Sent By mcarsill Date 2000-12-27 Time 08:33 Rev Time 0.00
Received By mcarsill Date 2000-12-27 Time 08:33 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED WITH
 DRAWINGS.
 2) NO INTERIOR FINISH CLASSIFICATIONS
 PROVIDED WITH DRAWINGS.
 3) FIRE ALARM SYSTEM EQUIPMENT SHOWN
 ON DRAWINGS. PLEASE PROVIDE COMPLETE
 FIRE ALARM SYSTEM SHOP DRAWINGS WITH
 A PERMIT.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-28 Cont ID  
Sent By pkrauss Date 2001-02-28 Time 15:11 Rev Time 0.45
Received By pkrauss Date 2001-02-28 Time 14:44 Sent To  
Notes
2001-02-28 00:00:00*******************NOTE*****************
  
 AUXILIARY DRAIN PAN MUST OVERFLOW
 PROTECTION BY MEANS OF FLOAT SWITCH OR
 DRAIN LINE, AS PER 1997 SMC 304.8.9.1.
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR TIE
 D TO HORN/STROBE PER NFPA 901 4-4.4.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-19 Cont ID  
Sent By ndenmark Date 2001-01-19 Time 10:27 Rev Time 0.33
Received By ndenmark Date 2001-01-19 Time 10:27 Sent To  
Notes
2001-01-19 00:00:00PROVISO:
 1.ACCESSIBILITY FOR SERVICE REQUIRED
 PER 1997 SMC 304.2 WITH RESPECT TO
 BUILDING CONSTRUCTION.
 2. DUCT SMOKE DETECTORS REQUIRED FOR
 BOTH AHU'S.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-02 Cont ID  
Sent By jleech Date 2001-03-02 Time 10:57 Rev Time 0.75
Received By pschmitz Date 2001-03-02 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-13 Cont ID  
Sent By jleech Date 2001-01-13 Time 12:41 Rev Time 1.00
Received By pschmitz Date 2001-01-13 Time 12:40 Sent To  
Notes
2001-01-13 00:00:00DENIED;
 1.HANDICAP LAV. CLEARANCE FROM FLOOR TO
 BOTTOM OF LAV.IS 29" PER. 97 FACBC
 FIG. 31 PAGE 109.
 2.SINK SHALL BE MOUNTED WITH COUNTER NO
 HIGHER THAN 34" FACBC 4.24.2 ALSO
 COMPLY WITH 4.24.4 AND 4.24.6.
 3.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC SECS. 4.1.3 (10) AND 4.15.
 PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377