Plan Review Details - Permit 00121089
Plan Review Stops For Permit 00121089
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-06 Cont ID  
Sent By jwitmer Date 2001-03-06 Time 07:51 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-06 00:00:00PROVISO: A SEPERATE PERMIT WILL BE RE-
 QUIRED FOR THE STOREFRONT AND STORM
 SHUTTERS. A SBCCI REPORT OR DADE COUNTY
 PRODUCT APPROVAL REPORT WILL BE REQUIRED
 (2 COPIES). PERMIT FEES WILL ALSO APPLY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By jwitmer Date 2001-01-09 Time 13:45 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-09 00:00:00BUILDING PLAN REVIEW:
 1). FL. S.S. 481 REQUIRES ALL PLANS
 DRAWN BY A DESIGN PROFESSIONAL TO BE
 SIGNED ,SEALED AND DATED.
 2). FL.ACCESSIBILITY CODE 4.16.2 THE
 CLEAR FLOOR SPACE FOR WATER CLOSETS NOT
 IN STALLS SHALL COMPLY WITH FIGURE 28
 CLEAR FLOOR SPACE MAY BE ARRANGED TO AL-
 LOW EITHER A LEFT-HAND OR RIGHT-HAND
 APPROACH.
 3). S.B.C. 1606.4.1 IMPACT GLAZING FROM
 WINDBORN DEBRIS- 2 COPIES OF EITHER DADE
 COUNTY OR SBCCI PRODUCT APPROVAL REPORT
 FOR BOTH THE STORE FRONT GLAZING AS WELL
 AS THE GLASS DOOR SYSTEM.
 4). S.B.C. 104.2.2- A-5 SHOWS SEC. E1 &
 E2 DETAILS FOR SOFFITS, HOW ARE THE
 SOFFITS ATTACHED TO THE DECK ABOVE? HOW
 OFTEN ARE THE FRAMING MEMBERS? WHAT
 THICKNESS DRYWALL?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-08 Cont ID  
Sent By dpalmer Date 2001-01-08 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2001-01-08 Time 15:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 16:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-03-08 Cont ID  
Sent By ndenmark Date 2001-03-08 Time 08:00 Rev Time 0.50
Received By ndenmark Date 2001-01-19 Time 10:53 Sent To  
Notes
2001-01-19 00:00:00COPPER CHILLED WATER LINES TO BE BRAZED
 PER 1997 SMC TABLE 1205

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-08 Cont ID  
Sent By jleech Date 2001-03-08 Time 07:55 Rev Time 0.50
Received By jleech Date 2001-03-08 Time 07:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By jleech Date 2001-01-09 Time 09:02 Rev Time 0.50
Received By jleech Date 2001-01-09 Time 09:02 Sent To  
Notes
2001-01-09 00:00:00DENIED;
  
 1.HANDICAP BATHROOMS MUST BE 5'-6" MIN.
 NOT 5'-4". CLEAR FLOOR SPACE FOR W/C
 IS 36" AND 30" FOR LAV.
  
 2.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC SECS. 4.1.3.(10) AND 4.15.
 PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377