Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-19 Cont ID  
Sent By pkrauss Date 2001-03-19 Time 09:39 Rev Time 0.30
Received By pkrauss Date 2001-03-19 Time 09:39 Sent To  
Notes
2001-03-19 00:00:00NOTE:MUST COMPLY WITH 1997 SMC SECTION
 406FOR FAN SHUTDOWN BY DUCT
 SMOKE DETECTOR AND NOTIFICATION
 TO HORN/STROBE ALARM AS PER NFPA
 90A, 4-4.4.1 THRU 4-4.4.3.
  
 FILED WITH MASTER # 00051379.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-26 Cont ID  
Sent By ndenmark Date 2000-12-26 Time 14:09 Rev Time 0.25
Received By ndenmark Date 2000-12-26 Time 14:09 Sent To  
Notes
2001-01-08 00:00:00PER APPROVED PLANS W/ 00051379
 DUCT DETECTOR TO BE TIED TO HORNH AND
 STROBE FOR NOTIFICATION