| Plan Review Stops For Permit 00120997 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-12-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-21 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-21 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM TO BE MONITORED | | | BY A UL LISTED CENTRAL STATION APPROVED | | | BY THE FIRE RESCUE DEPARTMENT. | | | 2) ADDITIONAL HORN STROBE DEVICES MAY | | | BE NEEDED IN MAIN PORTION OF STORE | | | WHERE THE DUCT DETECTORS ARE LOCATED. | | | 3) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONING DIFFUSERS. | | | 4) SYSTEM TO BE COMPLETELY TESTED IN | | | THE PRESENCE OF FIRE RESCUE. | | | 5) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|