Plan Review Details - Permit 00120997
Plan Review Stops For Permit 00120997
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 10:04 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 10:04 Sent To  
Notes
2001-01-08 00:00:001) FIRE ALARM SYSTEM TO BE MONITORED
 BY A UL LISTED CENTRAL STATION APPROVED
 BY THE FIRE RESCUE DEPARTMENT.
 2) ADDITIONAL HORN STROBE DEVICES MAY
 BE NEEDED IN MAIN PORTION OF STORE
 WHERE THE DUCT DETECTORS ARE LOCATED.
 3) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONING DIFFUSERS.
 4) SYSTEM TO BE COMPLETELY TESTED IN
 THE PRESENCE OF FIRE RESCUE.
 5) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910