Plan Review Details - Permit 00120947
Plan Review Stops For Permit 00120947
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2001-02-12 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2001-02-12 Time 12:54 Sent To  
Notes
2001-02-12 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PAGE 4 OF 7
 IS NOT SIGNED AND SEALED BY THE
 ENGINEEROF RECORD. PLANS ARE TO SIGNED
 AND SEALED PER 471.025, 61G-15-23.00.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 NO OTHER CIRCUITS ARE PERMITTED TO BE
 ONWITH KITCHEN CIRCUITS. PLEASE NOTE
 THEREQ`MENTS FOR BATHS ARE LISTED IN
 THE NEC UNDER 210-52D AND 210-11-C-3.
  
 3)NOTE : PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR SHOWN AS #5 IS NOT
 A SIZE LISTED UNDER "AWG" AND NEC 250-66
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 65-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-29 Cont ID  
Sent By dpalmer Date 2000-12-29 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2000-12-29 Time 07:31 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE : PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED. MAINS/PAN
 -ELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURENT PER 110-9
  
 2)NOTE: PLEASE NOTE PER 250-50 BLDG.
 STEEL IS TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT PER 210-11-C-3 #12/20A
  
 4)NOTE: PLEASE SHOW SOME MORE DETAIL
 ON CONDUCTORS AND CONDUIT FROM METER TO
 MAIN AND PANEL. A NOTE IS SHOWN ON LEFT
 THAT SHOWS AS 3-3/0`S AND 1 1/2" RIGID.
 PLEASE SHOW EQUIPMNET GROUND FROM MAIN
 TO PANEL IF NOT RIGID.
  
 5)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE INCLUDING ISLAND
 ARE TO BE SHOWN AS GFI/GFI PROTECTED
 PER 210-8-A-6
  
 6)NOTE: PLEASE NOTE PER NFPA-72 2-2.1.1.
 .1. SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS ALSO
 EXISTING BEDROOMS WILL NEED SMOKE DETECT
 -TORS FOR MORE THAN 50% OF NEW DWELLING
 INSIDE AND OUTSIDE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-26 Cont ID  
Sent By jleech Date 2001-02-26 Time 08:03 Rev Time 0.33
Received By jleech Date 2001-02-26 Time 08:03 Sent To  
Notes
2001-02-26 00:00:00PROVISO;
  
 NEED CONFINED SPACE CALCULATIONS FOR
 LAUNDRY ROOM. GAS WATER HEATER AND GAS
 DRYER IN ROOM LESS THAN 600 CU. FT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-01-02 Cont ID  
Sent By jleech Date 2001-01-02 Time 10:45 Rev Time 0.25
Received By jleech Date 2001-01-02 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-26 Cont ID  
Sent By jleech Date 2001-02-26 Time 08:07 Rev Time 0.25
Received By jleech Date 2001-02-26 Time 08:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-02 Cont ID  
Sent By jleech Date 2001-01-02 Time 10:46 Rev Time 0.25
Received By jleech Date 2001-01-02 Time 10:45 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-02-27 Cont ID  
Sent By rmcdouga Date 2001-02-27 Time 13:13 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-27 00:00:00****************PROVISO*****************
  
 1) PROVIDE (2) CURRENT COPIES OF METRO-
 DADE OR SBCCI PRODUCT APPROVALS FOR:
 - EXT.DOOR W/MIAMI SLIDE AS SHOWN
 - GLASS BLOCK
 - SINGLE HUNG WINDOWS AND GLASS BLOCK
 NOTE: IF PRODUCT DOES NOT HAVE THESE
 APPROVALS SITE SPECIFIC ENGINEERING IS
 ACCEPTABLE. THE FORM MUST HAVE WET
 SIGNATURE, DATE AND EMBOSSED SEAL OF THE
 ENGINEER CERTIFYING THE PRODUCT AND THE
 WET SIGNATURE, DATE AND EMBOSSED SEAL OF
 THE DESIGNER OF RECORD FOR THE STRUCTURE

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By rmcdouga Date 2001-01-10 Time 13:15 Rev Time 4.00
Received By rmcdouga Date 2001-01-10 Time 13:15 Sent To  
Notes
2001-01-10 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) IN ADDITION TO SIGNING, SEALING AND
 DATING EACH PAGE OF THE PLANS, THE
 ENGINEER IN RESPONSIBLE CHARGE MUST
 LEGIBLY INDICATE IN A TITLE BLOCK THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON
 EACHPLAN SHEET. 61G15-23.002 F.A.C.
  
 4)PROVIDE (2) CURRENT COPIES OF SBCCI
 OR METRO-DADE PRODUCT APPROVALS FOR THE
 FOLLOWING:
 - SINGLE HUNG WINDOWS
 - SLIDING GLASS DOORS
 - OUTSWING METAL DOOR W/MIAMI SLIDE
 - STORM PANELS
 THE ITEMS SUBMITTED ARE NOT ACCEPTABLE.
  
 5) PROVIDE PRODUCT APPROVAL,KEY PLAN
 ANDINSTALLATION SCHEDULE FOR STORM
 PANELS. PLEASE INDICATE THE SPECIFIC
 TYPE OF
 ANCHORS THAT WILL BE USED.
  
 6) TRUSS LAYOUT AND TRUSS DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD.
 UPLIFTS INDICATED ON TRUSS DRAWINGS
 EXCEED THE VALUES SHOWN ON PLANS FOR
 TRUSSES: T1,T2,T4,T5,T^,T7,T9,TG10.
 PLEASE HAVE ENGINEER REVIEW.
  
 7)TRUSS DRAWINGS REFERENCE ASCE 7-93.
 THIS IS NOT AN ACCEPTABLE DESIGN
 CRITERIA FOR WEST PALM BEACH. THE
 ADOPTED DESIGN CRITERIA IS SEC.1606 OF
 THE 97 STANDARD BUILDING CODE OR ASCE
 7-95.PLEASE HAVE TRUSS ENGINEER CORRECT.
  
 IF YOU HAVE ANY QUESTIONS,PLEASE CALL
 ROBERT MCDOUGAL AT (561) 659-8096
 EXT.8202.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-28 Cont ID  
Sent By sgraham Date 2000-12-28 Time 12:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***