Plan Review Details - Permit 00120708
Plan Review Stops For Permit 00120708
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 18:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2001-02-12 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2001-02-12 Time 14:19 Sent To  
Notes
2001-02-12 00:00:00****************** UNSAT **************
  
 1)NOTE: ELECTRICAL PLANS WERE SUBMITTED
 ACCROSS FROUNT COUNTER AS SUBMITTALS/
 MIAN PLAN IS STILL IN FOR REVIEW.
 PLANS ARE RE-SUB IF FAILED BY PLAN
 REVIEW, NOT ADDITIONAL INFORMATION.
 EACH TIME WILL BE 10% RE-SUB FEE.
  
 2)NOTE: PLEASE ALSO NOTE THAT PLANS ARE
 STILL NOT CORRECT PER NOTES FROM FIRST
 TWO REVIEWS.
  
 PLEASE SET UP AN APPOINTMENT IF THERE
 ARE
 ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-07 Cont ID  
Sent By dpalmer Date 2001-02-06 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2001-02-06 Time 11:00 Sent To  
Notes
2001-02-06 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 PLEASE SEE NOTE#16 FROM FIRST REVIEW.
 A NOTE WAS ADDED TO E-1 FOR A/C
 EQUIPMENT RATING? 110-9 OF NEC IS FOR
 AIC RATING
  
  
 2)NOTE: PLEASE SHOW LOCATION OF EXISTING
 SERVICE, YOU SHOW MAIN DISCONNECT ON
 GARAGE, AND NOT GROUPED WITH MAIN FROM
 HOUSE PER 230-72
  
 3)NOTE: PLEASE NOTE FROM FIRST NOTES,
 YOU SHOW AN EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO FIRST MEANS OF
 DISCONNECT.EQUIPMENT GROUNDING COND
 ONLY AFTER FIRST MEANS OF DISC.
  
 4)NOTE: PLEASE NOTE THAT PANEL "A"/"B"
 "SCHEDULES BOTH SHOW MCB`S W MAIN
 DISCONNECT INLINE. PLEASE VERIFY.
  
 5)NOTE: PLEASE NOTE LOAD ON GARAGE
 PANELSHOWN WITH NO ROOM FOR SPARES PER.
 YOU ARE SHOWING # 6 COMING FROM METER
 WITHNO MEANS OF OCP.? PLEASE CORRECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-28 Cont ID  
Sent By dpalmer Date 2000-12-28 Time 21:19 Rev Time 0.00
Received By dpalmer Date 2000-12-28 Time 21:19 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS THAT CORRE-
 -LATE WITH WORK BEING DONE.
 PANEL SCHEDULE SUBMITTED SHOWS GARAGE
 DOORS?? PANEL"B" IS SHOWN ON RISER FOR
 GARAGE???
 ALSO PANEL "B" IS SHOWN ON PLAN FOR
 GARAGE BUT WHERE IS MAIN DISC THAT IS
 SHOWN ON RISER???
 ALSO PLEASE SUBMIT PANEL "B" PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE SHOWING ALL GROUNDING AT
 GARAGE, CWP/BLDG STEEL. PER 250-50
 PLEASE NOTE MISSING EQUIPMENT GROUND
 FROM MAIN HOUSE IN CONDUIT.
 PLEASE SHOW SERVICE LOCATION ON PLAN.
  
 3)NOTE: MISSING SMOKE DETECTOR ON LOWER
 LEVEL PER NFPA-72 2-2.1.1.1 MAIN HOUSE.
  
 4)NOTE: PLEASE NOTE MEANS OF EGRESS
 LIGHTING REQ`D IN GARAGE GOING UP TO
 STORAGE AREA. STAIR LIGHITNG?? 210-70
  
 5)NOTE: EXISTING ELECTRICAL RISER SHOWS
 SHOWS GARAGE DISCONNECT AND PANEL COMING
 FORM MAIN DISCONNECT?? THESE ARE SHOWN
 AS TAPPED CONDUCTORS? WHERE IS OCP FOR
 THIS.PNAEL"A" DOES NOT SHOWN FEEDING "B?
  
 6)NOTE: 2/0 CONDUCTORS ARE SHOWN FEEDING
 A 2P50A?? PLEASE SHOW CLARIFICATION
 ON HOW 2/0`S WILL GO INTO 50A 2P.??
  
 7)NOTE: PLEASE SUBMIT REVISED LOAD CAL-
 -CULATIONS TO INCLUDE ALL NEW LOADS
 IN GARAGE.....A/C ECT.
  
 8)NOTE: SPRINLLER AT GARAGE?? PUMP?
 PLEASE SHOW ALSO ON PANEL SCHEDULE AND
 SHOW AS DISC.
  
 (9)NOTE: PLEASE SEE RISER SHOWN AS EXIST
 -ING,,,NOTE A/C UNIT BEING FED FROM
 METER???? HOW IS THIS POSSIBLE??
 ALSO 1 1/2" CONDUIT W/ 3-#3`S
 ALSO PLEASE SEE EQUIPMENT GROUNDING
 CONDCUTOE BEING SHOWN FROM METER TO
 MAIN?? PLEASE VERIFY THIS..
  
 10)NOTE: PLEASE SEE PLAN AT GARAGE.
 SUB PANEL "A" IS BEING SHOWN??YET
 PANEL AT MAIN HOUSE AS EXISTING IS SHOWN
 AS "A" PLEASE CORRECT.
  
 11)NOTE: PLEASE SEE PLAN!! MAIN EXISTING
 PANEL IS BEING SHOWN IN NEW PANTRY???
 PLEASE SEE ALL THE REQ`MENTS FOR
 110-26 AND SEE 384-7 FOR EASILY IGNITIB-
 -LE MATERIALS. THIS PANTRY HAS SHELVING
 SHOWN AND DOES NOT MEET ANY OF THE ABOVE
 TWO CODE ARTS: PLEASE NOTE PANEL IS NOT
 PERMITTED IN THIS TYPE OF STORAGE SPACE.
  
 12)NOTE: PLEASE NOTE THAT WATER HEATER
 THAT IS SHOWN ON E-2 IS NOT ON PANEL
 SCHEDULE. PLEASE CLARIFY.
  
 13)NOTE: PLEASE NOTE WARMING DRAWER IS
 NOT SHOWN ON PANEL SCHEDULE???
  
 14)NOTE: PLEASE SHOW CKLARIFICATION ON
 WPGFI SHOWN ON PORCH W/ GAS SHOWN NEXT
 TO IT??
  
 15)NOTE: PANEL SHEDULE SHOWS ELEC COOK
 -TOP AND PLAN SHOWS GAS COOK-TOP??
 PLEASE CORRELATE..
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 ON THE ABOVE OR A MEETING IS PREFERRED
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-12-29 Cont ID  
Sent By jleech Date 2000-12-29 Time 07:49 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-03 Cont ID  
Sent By jleech Date 2001-02-03 Time 10:57 Rev Time 0.25
Received By jleech Date 2001-02-03 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-29 Cont ID  
Sent By jleech Date 2000-12-29 Time 07:50 Rev Time 0.33
Received By jleech Date 2000-12-29 Time 07:50 Sent To  
Notes
2001-01-08 00:00:00SANATARY RISER NOT TO CODE.
 WATER HEATER? GAS OR ELECTRIC? WATER
 HEATER SHOWN ONLY ON ELECTRIC PLAN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-02-21 Cont ID  
Sent By fknapp Date 2001-02-21 Time 14:13 Rev Time 1.00
Received By fknapp Date 2001-02-21 Time 14:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By fknapp Date 2001-01-10 Time 10:40 Rev Time 4.00
Received By fknapp Date 2001-01-10 Time 10:40 Sent To  
Notes
2001-01-10 00:00:00 
 ***********BUILDING UNSAT***************
 1)
 PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
 2)
 PROVIDE ENERGY CALCULATIONS THAT HAVE
 SIGNATURE OF OWNER/AGENT.
 3)
 PROVIDE 2 COMPLETE COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 GARAGE DOORS
 WINDOWS
 EXTERIOR DOORS
 MULLIONS
 ROOF COVERING
 4)
 REVISE NOTE #3 AND #7 ON SHEET A-4 THAT
 REFERENCES SFBC, 1997 SBC IS ADOPTED IN
 THE CITY OF WEST PALM BEACH.
 5)
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS TO BE USED FOR ALL
 NON-IMPACT GLAZING.
 6)
 PROVIDE FLOOD ZONE ELEVATION CETIFICATE
 FOR NEW CONSTRUCTION WITH BFE OF 7.5'
 7)
 PROVIDE 1 1/2" WATER STOP WHERE MASONRY
 UNITS BEAR ON CONCRETE SURFACE.
 8)
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH CO.,THE PERMIT PLANS STAMPED
 BT THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-27 Cont ID  
Sent By sgraham Date 2000-12-27 Time 16:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***