| 2001-01-08 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SUBMIT PLANS THAT CORRE- |
| | -LATE WITH WORK BEING DONE. |
| | PANEL SCHEDULE SUBMITTED SHOWS GARAGE |
| | DOORS?? PANEL"B" IS SHOWN ON RISER FOR |
| | GARAGE??? |
| | ALSO PANEL "B" IS SHOWN ON PLAN FOR |
| | GARAGE BUT WHERE IS MAIN DISC THAT IS |
| | SHOWN ON RISER??? |
| | ALSO PLEASE SUBMIT PANEL "B" PANEL |
| | SCHEDULE. |
| | |
| | 2)NOTE: PLEASE SHOWING ALL GROUNDING AT |
| | GARAGE, CWP/BLDG STEEL. PER 250-50 |
| | PLEASE NOTE MISSING EQUIPMENT GROUND |
| | FROM MAIN HOUSE IN CONDUIT. |
| | PLEASE SHOW SERVICE LOCATION ON PLAN. |
| | |
| | 3)NOTE: MISSING SMOKE DETECTOR ON LOWER |
| | LEVEL PER NFPA-72 2-2.1.1.1 MAIN HOUSE. |
| | |
| | 4)NOTE: PLEASE NOTE MEANS OF EGRESS |
| | LIGHTING REQ`D IN GARAGE GOING UP TO |
| | STORAGE AREA. STAIR LIGHITNG?? 210-70 |
| | |
| | 5)NOTE: EXISTING ELECTRICAL RISER SHOWS |
| | SHOWS GARAGE DISCONNECT AND PANEL COMING |
| | FORM MAIN DISCONNECT?? THESE ARE SHOWN |
| | AS TAPPED CONDUCTORS? WHERE IS OCP FOR |
| | THIS.PNAEL"A" DOES NOT SHOWN FEEDING "B? |
| | |
| | 6)NOTE: 2/0 CONDUCTORS ARE SHOWN FEEDING |
| | A 2P50A?? PLEASE SHOW CLARIFICATION |
| | ON HOW 2/0`S WILL GO INTO 50A 2P.?? |
| | |
| | 7)NOTE: PLEASE SUBMIT REVISED LOAD CAL- |
| | -CULATIONS TO INCLUDE ALL NEW LOADS |
| | IN GARAGE.....A/C ECT. |
| | |
| | 8)NOTE: SPRINLLER AT GARAGE?? PUMP? |
| | PLEASE SHOW ALSO ON PANEL SCHEDULE AND |
| | SHOW AS DISC. |
| | |
| | (9)NOTE: PLEASE SEE RISER SHOWN AS EXIST |
| | -ING,,,NOTE A/C UNIT BEING FED FROM |
| | METER???? HOW IS THIS POSSIBLE?? |
| | ALSO 1 1/2" CONDUIT W/ 3-#3`S |
| | ALSO PLEASE SEE EQUIPMENT GROUNDING |
| | CONDCUTOE BEING SHOWN FROM METER TO |
| | MAIN?? PLEASE VERIFY THIS.. |
| | |
| | 10)NOTE: PLEASE SEE PLAN AT GARAGE. |
| | SUB PANEL "A" IS BEING SHOWN??YET |
| | PANEL AT MAIN HOUSE AS EXISTING IS SHOWN |
| | AS "A" PLEASE CORRECT. |
| | |
| | 11)NOTE: PLEASE SEE PLAN!! MAIN EXISTING |
| | PANEL IS BEING SHOWN IN NEW PANTRY??? |
| | PLEASE SEE ALL THE REQ`MENTS FOR |
| | 110-26 AND SEE 384-7 FOR EASILY IGNITIB- |
| | -LE MATERIALS. THIS PANTRY HAS SHELVING |
| | SHOWN AND DOES NOT MEET ANY OF THE ABOVE |
| | TWO CODE ARTS: PLEASE NOTE PANEL IS NOT |
| | PERMITTED IN THIS TYPE OF STORAGE SPACE. |
| | |
| | 12)NOTE: PLEASE NOTE THAT WATER HEATER |
| | THAT IS SHOWN ON E-2 IS NOT ON PANEL |
| | SCHEDULE. PLEASE CLARIFY. |
| | |
| | 13)NOTE: PLEASE NOTE WARMING DRAWER IS |
| | NOT SHOWN ON PANEL SCHEDULE??? |
| | |
| | 14)NOTE: PLEASE SHOW CKLARIFICATION ON |
| | WPGFI SHOWN ON PORCH W/ GAS SHOWN NEXT |
| | TO IT?? |
| | |
| | 15)NOTE: PANEL SHEDULE SHOWS ELEC COOK |
| | -TOP AND PLAN SHOWS GAS COOK-TOP?? |
| | PLEASE CORRELATE.. |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | ON THE ABOVE OR A MEETING IS PREFERRED |
| | PLEASE CALL. |
| | |