Plan Review Details - Permit 00120676
| Plan Review Stops For Permit 00120676 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-08 |
Time |
10:52 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-12-21 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-14 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-14 |
Time |
13:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-12-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-19 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-19 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-14 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-14 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-20 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-20 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH IN TENANT SPACE IF | | | SPRINKLERED CAN BE CLASS C. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-14 |
Time |
11:35 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2001-02-14 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2001-02-14 00:00:00 | PROVISO:AS PER NFPA 90A 4-4.4.2, DUCT | | | SMOKE DETECTOR SHALL BE TIED WITH | | | BUILDING FIRE ALARM, IF BUILING FIRE | | | ALARM DOES NOT EXIST, DUCT SMOKE | | | DETECTORS SHALL ACTIVATED STROBE/ALARM | | | IN OCCUPIED AREAS. | | | | | | AS PER 97 SMC 609.1.1, NO COMBUSTIBLES | | | SHALL BE ABOVE CEILING IN RETURN AIR | | | PLENUM. | | | | | | FIRE DAMPER IS REQUIRED FOR MOTORIZED | | | DAMPER INTAKE OPENING FOR AHU 1 AS PER | | | 97 610.1.2 (CORRIDOR TO BE PROTECTED | | | PER 97SBC 1006.2.2) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-20 |
Time |
08:09 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-20 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. NO PVC OR OTHER COMBUSTIBLE CONSTRUC- | | | TION ALLOWED IN MECH RM USED AS RETURN | | | AIR PLENUM AREA.1997 SMC 609.1.1 | | | 2. 10 FT MINIMUM REQUIRED BETWEEN OUT | | | SIDE AIR INTAKE AND EXHAUST AIR OUTLET | | | 1997 SMC 506.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-02-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-07 |
Time |
07:40 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-02-07 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-12-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-17 |
Time |
11:58 |
Rev Time |
2.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW,PAUL SCHMITZ | | | PROVISO | | | (1) SHT A-1 BREAK RM #239 SINK TO COMPLY | | | W/ FACBNC 4.24, SHOW ELEVATION DETAIL | | | HGTH 34" ABOVE FF, BY 30" WIDE. | | | KNEE CLEARANCE 27" HIGH, 30" WIDE, | | | 19" MAX DEPTH. | | | (2) SHT A-1 H/C REST RM'S # 248,253 TO | | | COMPLY W/FACBC 4.17.5 DOORS SHALL NOT | | | SWING INTO THE CLEAR FLR SPACE OF ANY | | | FIXTURE. | | | (3) SHT P-1 NOTE (2) & (4) HOT & COLD | | | WATER SUPPLY TO BE PROTECTRED WITH A | | | RPZV, SPC 94 SEC 606. | | | (4) SHT P-1 NOTE 16, AIR CHAMBERS TO | | | COMPLY WITH SPC 94 SEC 607.8.3 TO BE | | | READLY ACCESSIBLE AND RECHARGEABLE. | | | END OF COMMENTS | | | | | | | | | CHANGED TO PROVISO PER BILL STAPLES |
|
|
|