| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: |
| | 1).S.B.C. 104.2.2- MISSING PRODUCT |
| | APPROVAL REPORTS FOR EXT. DOOR MASTER |
| | BATH,GLASS BLOCK & FOR THE ROOFING |
| | MATERIALS, ROOF TILE & STORM SHUTTERS. |
| | 2). S.B.C. 2405.2 SAFETY GLASS- HAZARD- |
| | OUS AREAS. SHOWER/TUB |
| | 3).CARPORT ENTRANCE- LANDINGS S.B.C. |
| | 1012.1.6.-LANDING REQUIRED, THE LANDING |
| | MAY BE ONE STEP LOWER THAN THE INSIDE |
| | FLOOR LEVEL (7" LOWER). |
| | 4).WHIRLPOOL ACCESS REQUIRED FOR MOTOR |
| | 5).SBC 104.2.2- FRENCH DOORS TO BE CUT |
| | IN, ARE LARGER THAN EXISTING OPENING. |
| | WILL ADDITIONAL COLUMN REEQUIRRED? |
| | 6).SBC 104.2.2- ADDITIONAL INFO: |
| | SHEET A-5 DETAILS 1&3 SHOWS A 1/4" RED |
| | IRON BRACKET, NEED ANCHOR INFORMATION |
| | TRUSS TO EXISTING BEAM/ BEAM TO COLUMN. |
| | IS THERE A REDUCTION REQUIRED FOR EDGE |
| | DISTANCE FOR THE ANCHORS COLUMN/BEAM |
| | IN DETAIL #1. BOLT SIZE & PLACEMENT |
| | 7).DISCREPANCY, SBC 104.2.2- SHEET A-5 |
| | ROOF FRAMING FOR OPEN TERRACE SHOWS A |
| | DROPPED TRUSS GABLE WITH OVERHANG. |
| | DETAIL 2/6 SHOWS A STANDARD GABLE NO |
| | OVERHANG. |
| | 8).DETAIL 1/6 SHOWS FLOOR JOIST CLOSER |
| | TO THE SOIL THAN 18" REQUIRES PRESSURE |
| | TREARED JOIST, SBC 2304.3.4. |
| | 9).CLARIFY, A-4 STEEL COLUMN 2 LOCATIONS |
| | APPROX. 4'-6" APART "L" SHAPED PLATE |
| | DOESN'T SHOW ANY LOAD. |
| | 10). NOTE: TO SHORE UP EXISTING BM. IS |
| | THIS A WOOD BEAM OR CONCRETE & STEEL? |
| | HOW IS THE ROOF LOADS TO BE CARRIED? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659- 8096 EX 8412 |