Plan Review Details - Permit 00120669
Plan Review Stops For Permit 00120669
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-03-05 Cont ID  
Sent By jwitmer Date 2001-03-05 Time 15:00 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-05 Cont ID  
Sent By jwitmer Date 2001-01-05 Time 08:15 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1).S.B.C. 104.2.2- MISSING PRODUCT
 APPROVAL REPORTS FOR EXT. DOOR MASTER
 BATH,GLASS BLOCK & FOR THE ROOFING
 MATERIALS, ROOF TILE & STORM SHUTTERS.
 2). S.B.C. 2405.2 SAFETY GLASS- HAZARD-
 OUS AREAS. SHOWER/TUB
 3).CARPORT ENTRANCE- LANDINGS S.B.C.
 1012.1.6.-LANDING REQUIRED, THE LANDING
 MAY BE ONE STEP LOWER THAN THE INSIDE
 FLOOR LEVEL (7" LOWER).
 4).WHIRLPOOL ACCESS REQUIRED FOR MOTOR
 5).SBC 104.2.2- FRENCH DOORS TO BE CUT
 IN, ARE LARGER THAN EXISTING OPENING.
 WILL ADDITIONAL COLUMN REEQUIRRED?
 6).SBC 104.2.2- ADDITIONAL INFO:
 SHEET A-5 DETAILS 1&3 SHOWS A 1/4" RED
 IRON BRACKET, NEED ANCHOR INFORMATION
 TRUSS TO EXISTING BEAM/ BEAM TO COLUMN.
 IS THERE A REDUCTION REQUIRED FOR EDGE
 DISTANCE FOR THE ANCHORS COLUMN/BEAM
 IN DETAIL #1. BOLT SIZE & PLACEMENT
 7).DISCREPANCY, SBC 104.2.2- SHEET A-5
 ROOF FRAMING FOR OPEN TERRACE SHOWS A
 DROPPED TRUSS GABLE WITH OVERHANG.
 DETAIL 2/6 SHOWS A STANDARD GABLE NO
 OVERHANG.
 8).DETAIL 1/6 SHOWS FLOOR JOIST CLOSER
 TO THE SOIL THAN 18" REQUIRES PRESSURE
 TREARED JOIST, SBC 2304.3.4.
 9).CLARIFY, A-4 STEEL COLUMN 2 LOCATIONS
 APPROX. 4'-6" APART "L" SHAPED PLATE
 DOESN'T SHOW ANY LOAD.
 10). NOTE: TO SHORE UP EXISTING BM. IS
 THIS A WOOD BEAM OR CONCRETE & STEEL?
 HOW IS THE ROOF LOADS TO BE CARRIED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659- 8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-03 Cont ID  
Sent By dpalmer Date 2001-01-03 Time 19:23 Rev Time 0.00
Received By dpalmer Date 2001-01-03 Time 19:23 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 PLANS NEED TO HAVE MORE ELECTRICAL DE-
 -TAIL SHOWN. SEE NOTES TO FOLLOW.
  
  
 1)NOTE: PLEASE NOTE THAT NEW A/C UNIT
 IS NOTED ON PLAN BUT NOT SHOWN ON ELEC
 PLAN.PLEASE SHOW DISC`S PER 440-11
 NEED TO SHOW NEW CU LOCATION.
  
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING NEW A/C LOAD BEING ADDED AND
 SHOW SIZE OF EXISTING SERVICE. 215-5
  
 3)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE,
 MUST BE 20A AND #12 PER 210-11-C-3
  
 4)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING PER 210-70 FOR MASTER CLOSETS
  
 5)NOTE:PLEASE NOTE SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS PER NFPA-72 2-2.1.1.1
 SLEEPING ROOMS ARE ROOMS WITH CLOSET AND
 /OR BATHS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-01-04 Cont ID  
Sent By jleech Date 2001-01-04 Time 07:35 Rev Time 0.25
Received By jleech Date 2001-01-04 Time 07:35 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN. A/C CONTRACTOR TO PROVIDE
 PLANS WITH APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-24 Cont ID  
Sent By jleech Date 2001-02-24 Time 13:01 Rev Time 0.25
Received By jleech Date 2001-02-24 Time 13:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-01-04 Cont ID  
Sent By jleech Date 2001-01-04 Time 07:38 Rev Time 0.33
Received By jleech Date 2001-01-04 Time 07:38 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.GAS WATER HEATER CANNOT BE INSTALLED
 IN A BEDROOM OR A BEDROOM CLOSET.
 97 SGC 504.1.
  
 2.PLUMBING SCHEMATIC, NO HORIZONTAL DRY
 VENTS (MASTER TUB AND SHOWER)
 94 SPC 906.2.1.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-03-05 Cont ID  
Sent By jwitmer Date 2001-03-05 Time 11:13 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-01-04 Cont ID  
Sent By sgraham Date 2001-01-04 Time 08:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED A VARIANCE ZBA