Plan Review Details - Permit 00120608
Plan Review Stops For Permit 00120608
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-28 Cont ID  
Sent By lsmith Date 2000-12-28 Time 09:20 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER WRS 12/28/00 LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-26 Cont ID  
Sent By bstaples Date 2000-12-26 Time 10:28 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PHASE TWO (2) OF ROAD ONLY.
 DEMOLITION, ELECTRICAL (STREET LIGHTS
 ECT.) REQUIRE ADDITIONAL PERMITS.
 ALL WORK IN PHASE 1 REQUIRES THAT A NEW
 PERMIT BE APPLIED FOR AND ISSUED.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-12-26 Cont ID  
Sent By bstaples Date 2000-12-26 Time 10:33 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS AND PERMITS MUST BE APPLIED FOR
 AND ISSUED PRIOR TO START OF WORK.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-12-22 Cont ID  
Sent By dlauderm Date 2000-12-22 Time 12:30 Rev Time 0.00
Received By dlauderm Date 2000-12-22 Time 12:34 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS:
 PHASE ONE OF ROAD WILL NEED TO BE
 RESUBMITTED AT A LOWER ROAD ELEVATION TO
 HAVE A ONE FOOT DIFFERENCE BETWEEN
 THE EXISTING BUILDINGS FLOOR ELEVATION
 AND CROWN OF ROAD.
 THE PHASE ONE WATER MAIN CAN NOT BE
 INSTALLED UNTIL A FINAL ROAD ELEVATION
 IS SET DUE TO THE REQUIRED COVER (36").
 CONSTRUCTION OF STORM AND SANITARY CAN
 PROCEED IN PHASE ONE.
 ROAD CONSTRUCTION CAN NOT BE BUILT (BOTH
 PHASES) INCLUDING SIDEWALKS, CURBS AND
 GUTTERS AND PAVED SECTIONS, UNTIL STREET
 LIGHT PLAN HAS BEEN PERMITTED SO THE
 UNDERGROUND WIRING CAN GO IN.
 THE GREASE TRAP, STORMWATER LINES AND BA
 RESTAURANT MUST BE PERMITTED SEPARATELY
 UNDER THE CHINESE RESTAURANT'S ADDRESS.
 THE SERVICES IN THE ROAD FOR THE CHINESE
 RESTAURANT CAN BE CONSTRUCTED UNDER THIS
 PERMIT.
 CONSTRUCTION OF THE WATER AND SANITARY
 SEWER SYSTEM CAN NOT START TILL THE
 DEP/PBC HEALTH DEPARTMENT HAVE PERMITTED
 THE PROJECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 09:27 Sent To  
Notes
2001-01-08 00:00:001) FIRE HYDRANTS LOCATED ON EXECUTIVE
 CENTER DRIVE EXTENSION SHALL NOT EXCEED
 500 FEET APART.
 2) THE EXECUTIVE CENTER DRIVE EXTENSION
 IS TO BE A MINIMUM OF 20 FEET IN CLEAR
 WIDTH.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-12-26 Cont ID  
Sent By bstaples Date 2000-12-26 Time 10:36 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS AND PERMITS MUST BE APPLIED FOR
 AND ISSUED PRIOR TO START OF ANY WORK.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-26 Cont ID  
Sent By bstaples Date 2000-12-26 Time 10:37 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO REVIEW REQUIRED FOR STREET
 CONSTRUCTION AS PER SHIRLEY AND ANGELLA
 12/26/00.