Plan Review Details - Permit 00120607
Plan Review Stops For Permit 00120607
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By mcarsill Date 2000-12-13 Time 16:59 Rev Time 1.00
Received By lsmith Date 2000-12-13 Time 16:59 Sent To  
Notes
2001-01-08 00:00:001) SMOKE DETECTORS ARE TO BE INSTALLED A
 MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONING DIFFUSERS.
 2) FOUR SIGNALS ARE REQUIRED, GENERAL
 ALARM, WATERFLOW, GENERAL TROUBLE AND
 SUPERVISORY.
 3) FIRE ALARM SYSTEM IS REQUIRED TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
 4) SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE.
 5) SYSTEM TO BE TESTED WITH MEMBERS OF
 THE FIRE RESCUE DEPARTMENT.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910
 PASSED: SIGNED BY MEC 12/13/00 WITH
 PROVISO