Plan Review Details - Permit 00120596
Plan Review Stops For Permit 00120596
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-12-20 Cont ID  
Sent By lmartine Date 2000-12-20 Time 14:58 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 17:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-26 Cont ID  
Sent By dpalmer Date 2001-02-26 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2001-02-26 Time 11:22 Sent To  
Notes
2001-02-26 00:00:00***************** UNSAT ***************
  
 1)NOTE; PLEASE SEE SHEET A-11. THE SAME
 ITEMS ARE SHOWN.
 PLEASE HAVE ALL CHANGES MADE ON PLAN.
 PLEASE SHOW INFORMATIONN FROM REVIEW
 COMMENTS.
  
 2)NOTE: PLEASE NOTE THAT PLAN SHOWS
 150A 3PHASE PANEL AND RISER SHOWS 100A??
  
  
 PLESE HAVE THE ABOVE INFORMATION PLACED
 ON PLANS AND INFORMATION FROM FIRST
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-05 Cont ID  
Sent By dpalmer Date 2001-01-05 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2001-01-05 Time 12:18 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS OF ALL
 ELECTRICAL EQUIPMENT. MAIN/PANELS/BRKRS
 ARE TO BE RATED FOR AVAILABLE FAULT
 CURRENTS. PER 110-9
  
 2)NOTE: PLEASE SEE ELEC RISER, PLAN
 SHOWS FEEDS TO LIGHTING AND PERMIT APPL
 -ICATION HAS SITE LIGHTING CROSSED OFF.
 PLEASE CLARIFY.
  
 3)NOTE: PLEASE HAVE 100A PANEL INDICATE
 MCB.
  
 4)NOTE: PLEASE SHOW TWO GRND RODS FOR
 SERVICE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-01-05 Cont ID  
Sent By mgonzale Date 2001-01-05 Time 10:26 Rev Time 1.00
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISOS
 1. WHEN INSTALLING NEW FENCE DEFLECT
 AS REQUIRED SO THAT WATER METERS
 ARE ACCESSIBLE FROM AUSTRALIAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-03 Cont ID  
Sent By mcarsill Date 2001-04-03 Time 13:12 Rev Time 0.00
Received By mcarsill Date 2001-04-03 Time 13:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-22 Cont ID  
Sent By mcarsill Date 2000-12-22 Time 09:11 Rev Time 0.00
Received By mcarsill Date 2000-12-22 Time 09:11 Sent To  
Notes
2001-01-08 00:00:001) FIRE HYDRANTS LOCATED WITHIN COMPLEX
 NOT SHOWN. PLEASE SHOW FIRE HYDRANTS
 WITHIN COMPLEX.
 2) WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE, PARAMEDICAL, AND POLICE DEPARTMENT
 ACCESS THROUGH THE ENTRY GATE ARMS.
 3) WHAT PROVISIONS HAVE BEEN MADE IF
 LOSS OF POWER SHOULD OCCUR TO THE
 ENTRY GATE ARMS.
 4) CLEARLY DEMONSTRATE FIRE RESCUE
 ROUTES ON THE PLAN SO COMPLIANCE CAN
 BE VERIFIED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910