Plan Review Details - Permit 00120591
| Plan Review Stops For Permit 00120591 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-12 |
Time |
18:55 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-02 |
Time |
15:53 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: | | | 1). SECTION 2/1 SHOWS A 1 HR. WALL, | | | WP1200 IS NOT LISTED IN THE UL LISTINGS. | | | THERE IS A NOTE ON THAT SAME DETAIL :TO | | | CONTINUE EVERY OTHER STUD TO UNDERSIDE | | | OF ROOF STRUCTURE ABOVE, THIS PUTS THESE | | | STUDS AT 4'-0" O.C.PLEASE COPY THE UL | | | LISTING | | | 2). FL ACCESSIBILITY CODE 4.13.6 | | | MANEUVERING CLEARENCES AT DOORS- 18" ON | | | THE LATCH SIDE OF DOORS, FRONT APPROACH | | | SEE DOOR "E" IN FRONT OF ROOM 104 STO. | | | 3). SBC 1001.1.3- MEANS OF EGRESS- MEANS | | | OF EGRESS SHALL NOT BE PERMITTED THROUGH | | | KITCHENS, CLOSETS,RESTROOMS AND SIMILAR | | | AREAS, SEE ROOM 104. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-08 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-08 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-01-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-04 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-04 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH PANEL | | | SCHEDULE. PLEASE SUBMIT PANEL SCHEDULE | | | NOT SHOWN ON PLAN NOW. 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW ELECTRICAL EQUIPMENTPER 110-9 | | | | | | | | | 3)NOTE: PLEASE CLARIFY NEW SERVICE | | | VOLTAGE AND IS IT 1 PHASEOR 3 PHASE? | | | METERCAN ID SHOWN 3 PHASE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-12-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-22 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-22 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-09 |
Time |
13:38 |
Rev Time |
0.30 |
| Received By |
ndenmark |
Date |
2001-01-09 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
|