Plan Review Details - Permit 00120576
Plan Review Stops For Permit 00120576
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-01-05 Cont ID  
Sent By jwitmer Date 2001-01-05 Time 10:05 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-01-04 Cont ID  
Sent By dpalmer Date 2001-01-04 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2001-01-04 Time 15:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-11 Cont ID  
Sent By mcarsill Date 2001-01-11 Time 13:20 Rev Time 0.00
Received By mcarsill Date 2001-01-11 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-27 Cont ID  
Sent By mcarsill Date 2000-12-27 Time 07:56 Rev Time 0.00
Received By mcarsill Date 2000-12-27 Time 07:56 Sent To  
Notes
2001-01-08 00:00:001) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING NOT SHOWN ON DRAWINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-01-08 Cont ID  
Sent By ndenmark Date 2001-01-08 Time 14:42 Rev Time 0.25
Received By ndenmark Date 2001-01-08 Time 14:42 Sent To  
Notes
2001-01-08 00:00:00INSUFFICIENT INFORMATION PROVIDED FOR
 REVIEW. PROVIDE COMPLETE PLANS AT TIME
 OF MECHANICAL PERMIT APPLICATION PRIOR
 TO ANY MECHANICAL WORK BEING DONE.
 INFORMATION REQUIRED ON EXISTING
 EQUIPMENT CAPACITY AND CFM FOR EACH
 DROP. PROVIDE INFORMATION ON EXHAUST
 AIR. PROVIDE ASHRAE 62-89 OUTSIDE AIR
 QUANTITIES.