Plan Review Details - Permit 00120524
Plan Review Stops For Permit 00120524
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-04-03 Cont ID  
Sent By mcarsill Date 2001-04-03 Time 13:57 Rev Time 0.00
Received By mcarsill Date 2001-04-03 Time 13:53 Sent To  
Notes
2001-04-03 00:00:001) PLEASE INDICATE ON PLANS THAT ANY
 ACTIVATION OF THE FIRE ALARM SYSTEM OR
 FIRE SPRINKLER SYSTEM SHALL IMMEDIATELY
 CAUSE THE STAIRWAY AND ELEVATOR SHAFT
 PRESSURIZATION FANS TO ACTIVATE. THESE
 SYSTEMS ARE ALSO TO BE CONNECTED TO
 EMERGENCY POWER SYSTEMS FOR THE
 BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-03-06 Cont ID  
Sent By pkrauss Date 2002-03-06 Time 16:47 Rev Time 5.00
Received By pkrauss Date 2002-03-06 Time 16:47 Sent To  
Notes
2002-03-06 00:00:00 
 REVISION 11 UNDER BUIDLING PERMIT.
  
 NOTES UNDER BUILDING PERMIT 99121621

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-02-04 Cont ID  
Sent By pkrauss Date 2002-02-04 Time 11:28 Rev Time 0.40
Received By pkrauss Date 2002-02-04 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 07:55 Rev Time 0.10
Received By pkrauss Date 2002-01-05 Time 07:52 Sent To  
Notes
2002-01-05 00:00:00NO MECH REVISIONS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-05-08 Cont ID  
Sent By pkrauss Date 2001-05-08 Time 09:02 Rev Time 0.30
Received By pkrauss Date 2001-05-08 Time 09:02 Sent To  
Notes
2001-05-08 00:00:00SUBMITTAL DATA FOR COOLING TOWERS 1 & 2,
 CHANGING FAN MOTOR FROM 15 HPTO 25 HP.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-03 Cont ID  
Sent By pkrauss Date 2001-04-03 Time 08:54 Rev Time 3.00
Received By pkrauss Date 2001-04-03 Time 08:54 Sent To  
Notes
2001-04-03 00:00:00PLEASE PROVIDE INFORMATION ON THE
 BOILER AND EMERGENCY GENERATOR.
  
 SEE FIRE DEPARTMENTS COMMENTS ON FIRE
 ALARM IN CONNECTION WITH STAIRWELL
 PRESSURIZATION.
  
 STAIRWELL PRESSURIZATION/FIRE ALARM
 SYSTEM ARE TO BE TESTED BEFORE C.O.
  
 ROLLED PLAN UNDER MECH PERMIT NUMBER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By ndenmark Date 2000-12-11 Time 12:42 Rev Time 1.00
Received By ndenmark Date 2000-12-11 Time 12:42 Sent To  
Notes
2001-01-08 00:00:00NO APPROVED PLANS W/ MASTER FOR MECHAN-
 ICAL PERMIT APPLICATION RETURNED TO
 MECHANICAL CONTRACTOR