Plan Review Details - Permit 00120374
| Plan Review Stops For Permit 00120374 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-25 |
Time |
19:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-25 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | ****************REVSION NEEDED******** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 3)NOTE: PLEASE NOTE THAT THE PANEL AT | | | POOL HOUSE STILL DOES NOT INDICATE BEING | | | MAIN BREAKER? MAIN DISCONNECT THAT IS | | | SHOWN IS TO BE GROUPED WITH MAIN AT | | | HOUSE PER 230-72. SEE NOTE FROM FISRT | | | REVIEW.GROUNDING AT THAT DISCONNECT IS | | | TO BE THE GROUNDING AT PANEL AT | | | POOLHOUSE. | | | PANEL SCHEDUEL DOESN'T INDICATE BEING | | | MCB EITHER. PLEASE CLARIFY LOCATIONS OF | | | EQUIPMENT. THE POOL HOUSE PANEL IS THE | | | ONLY ONE BEING SHOWN? | | | | | | | | | PLEASE CLARIFY AND SUBMIT ALL THE ABOVE | | | INFORMATION FOR REVIEW BEFORE ANY | | | INSPECTION IS CALLED. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-27 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-27 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL NOTE | | | BELOW RISER. NOTE MENTIONS ALL OUTLETS | | | WITHIN 6` OF WATER SOURCE. THAT WAS FROM | | | THE "96" NEC. ALL OUTLET SERVING | | | COUNTERPSPACE/ GARAGES/ BATHS ARE TO BE | | | GFI/GFI PROTECTED. PER 210-8 | | | PLEASE CHANGE OR REMOVE NOTE. | | | | | | 2)NOTE: PLEASE SEE RISER,,, PANEL"B " IS | | | SHOWN ON RISER AS EXISTING. PLEASE SHOW | | | LOCATION OF MAINS. MAINS NEED TO BE | | | GROUPED PER 230-72 MAIN FOR PANEL "B" | | | IS WHERE NOW? IF EXISTING WHAT DOES IT | | | FEED? | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. MAINS | | | /PANELS.BRKRS ARE ALL TO BE RAATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9 | | | | | | 4)NOTE; PLEASE SHOW ALL GROUNDING AT | | | DETACHED POOL HOUSE PER 250-50. COLD | | | WATER PIPE AND NEW BLDG STEEL. | | | | | | 5)NOTE: PLEASE SHOW MEANS OF DISCONNECT | | | AT DETACHED BLDG. MCB? DISC? ETC. | | | | | | 6)NOTE: NOTE,, RISER SHOWS EQUIPMENT | | | GROUNDING CONDUCTOR FROM METER TO MAIN | | | /PANEL.PLEASE VERIFY. | | | | | | 7)NOTE: PLEASE SHOW MEANS OF EGRESS | | | LIGHTING FROM GARAGE INTO STORAGE?" 210- | | | -70. 3-WAY? | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-14 |
Time |
12:12 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-12-14 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-14 |
Time |
12:12 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2000-12-14 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2001-04-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-04-11 |
Time |
15:08 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-11 00:00:00 | TRUSSES OK 4-11-01 RM |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-03-14 |
Time |
15:01 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | *****************TRUSSES**************** | | | | | | 1) MEAN ROOF HEIGHT ON TRUSS DRAWINGS IS | | | 15 FT. AND THE MRF ON THE DESIGN | | | COMPLIANCE FORM SUBMITTED WITH THE | | | PLANSIS 16 FT. PLEASE CORRECT. | | | | | | 2) TRUSS LAYOUT MUST HAVE WET | | | SIGNATURE,DATE AND EMBOSSED SEAL OF THE | | | ENGINEER | | | AND THE ENGINEERS TITLE BLOCK PER | | | 61G15-23.002 F.A.C. | | | | | | 3) TRUSS DRAWINGS NEED TO HAVE | | | ENGINEERSWET SIGNATURE, SIGNATURE STAMP | | | IS NOT | | | ACCEPTABLE. | | | | | | 4) INSTALLATION AND BRACING SHEETS ARE | | | MISSING. | | | | | | 5) SPECIFY UPLIFT AND ANCHORS FOR | | | GIRDERFG5. | | | | | | 6) SPECIFY UPLIFT AND ANCHORS USED TO | | | CONNECT TRUSSES TO GIRDERS AT OPEN | | | PORCHAND AT LEFT OF GARAGE. GIRDERS | | | FG2B,FG5 AND FG2A. | | | | | | 7) TRUSSES HJH, HJI, HJJ HAVE UPLIFT | | | VALUES ON TRUSS DRAWINGS WHICH EXCEED | | | THOSE ON PLANS. PLEASE CORRECT. | | | | | | 8) PROVIDE DETAILS OF CONNECTION BETWEEN | | | GROUTED BLOCK COLUMNS AND WOOD GIRDERS | | | AT COVERED PORCH. SPECIFY ANCHOR | | | CAPACITIES AND UPLIFT LOADS. REVISED BY | | | ARCHITECT IN LETTER DATED FEB.5,2001. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2001-01-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-01-29 |
Time |
10:44 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-01-17 |
Time |
13:15 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | DENIED | | | | | | 1) PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF METRO-DADE OR SBCCI PRODUCT | | | APPROVALS FOR THE FOLLOWING: | | | - GLASS BLOCK | | | - GARAGE DOORS | | | - STORM PANELS | | | - 3'X8' SINGLE DOOR | | | | | | NOTE: DRAFT OF PRODUCT APPROVAL FOR | | | STORM PANELS IS NOT ACCEPTABLE. | | | | | | 2) IN ADDITION TO PRODUCT APPROVALS FOR | | | STORM PANELS,PROVIDE KEY PLAN AND | | | INSTALLATION SCHEDULE. INDICATE | | | SPECIFIC TYPE OF ANCHORS THAT WILL BE | | | USED. | | | | | | 3) DOORS INTO A/C STORAGE SHALL COMPLY | | | WITH THE FLORIDA ENERGY CODE SEC.603.1. | | | | | | 4) PROVIDE (2) COMPLETED DESIGN | | | COMPLIANCE FORMS WITH WET | | | SIGNATURE,DATE AND EMBOSSED SEAL OF THE | | | DESIGNER OF RECORD. | | | | | | | | | 5) PROVIDE MANUFACTURERS INFORMATION, | | | INCLUDING UL OR OTHER AGENCY LISTING, | | | FOR GAS GRILL. | | | | | | 6) TRUSS LAYOUT AND SHOP DRAWINGS MUST | | | BE REVIEWED AND APPROVED BY THE DESIGNER | | | OF RECORD PRIOR TO TRUSS INSTALLATION. | | | TRUSS LAYOUT PLAN AND DRAWINGS MUST BE | | | WET SIGNED,DATED AND EMBOSSED BY THE | | | ENGINEER. | | | | | | 7) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BUILDING PLAN REVIEW | | | (561) 659-8096 EXT.8202 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-01-16 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-01-16 |
Time |
09:09 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|