Plan Review Details - Permit 00120374
Plan Review Stops For Permit 00120374
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-26 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 19:02 Sent To  
Notes
2001-01-25 00:00:00****************REVSION NEEDED********
  
  
  
  
  
  
  
  
  
  
  
  
  
 3)NOTE: PLEASE NOTE THAT THE PANEL AT
 POOL HOUSE STILL DOES NOT INDICATE BEING
 MAIN BREAKER? MAIN DISCONNECT THAT IS
 SHOWN IS TO BE GROUPED WITH MAIN AT
 HOUSE PER 230-72. SEE NOTE FROM FISRT
 REVIEW.GROUNDING AT THAT DISCONNECT IS
 TO BE THE GROUNDING AT PANEL AT
 POOLHOUSE.
 PANEL SCHEDUEL DOESN'T INDICATE BEING
 MCB EITHER. PLEASE CLARIFY LOCATIONS OF
 EQUIPMENT. THE POOL HOUSE PANEL IS THE
 ONLY ONE BEING SHOWN?
  
  
 PLEASE CLARIFY AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW BEFORE ANY
 INSPECTION IS CALLED. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-27 Cont ID  
Sent By dpalmer Date 2000-12-27 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2000-12-27 Time 17:35 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ELECTRICAL NOTE
 BELOW RISER. NOTE MENTIONS ALL OUTLETS
 WITHIN 6` OF WATER SOURCE. THAT WAS FROM
 THE "96" NEC. ALL OUTLET SERVING
 COUNTERPSPACE/ GARAGES/ BATHS ARE TO BE
 GFI/GFI PROTECTED. PER 210-8
 PLEASE CHANGE OR REMOVE NOTE.
  
 2)NOTE: PLEASE SEE RISER,,, PANEL"B " IS
 SHOWN ON RISER AS EXISTING. PLEASE SHOW
 LOCATION OF MAINS. MAINS NEED TO BE
 GROUPED PER 230-72 MAIN FOR PANEL "B"
 IS WHERE NOW? IF EXISTING WHAT DOES IT
 FEED?
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED. MAINS
 /PANELS.BRKRS ARE ALL TO BE RAATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
  
 4)NOTE; PLEASE SHOW ALL GROUNDING AT
 DETACHED POOL HOUSE PER 250-50. COLD
 WATER PIPE AND NEW BLDG STEEL.
  
 5)NOTE: PLEASE SHOW MEANS OF DISCONNECT
 AT DETACHED BLDG. MCB? DISC? ETC.
  
 6)NOTE: NOTE,, RISER SHOWS EQUIPMENT
 GROUNDING CONDUCTOR FROM METER TO MAIN
 /PANEL.PLEASE VERIFY.
  
 7)NOTE: PLEASE SHOW MEANS OF EGRESS
 LIGHTING FROM GARAGE INTO STORAGE?" 210-
 -70. 3-WAY?
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By jleech Date 2000-12-14 Time 12:12 Rev Time 0.25
Received By jleech Date 2000-12-14 Time 12:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By jleech Date 2000-12-14 Time 12:12 Rev Time 0.25
Received By jleech Date 2000-12-14 Time 12:12 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2001-04-11 Cont ID  
Sent By rmcdouga Date 2001-04-11 Time 15:08 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-04-11 00:00:00TRUSSES OK 4-11-01 RM

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2001-03-14 Cont ID  
Sent By rmcdouga Date 2001-03-14 Time 15:01 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-03-14 00:00:00*****************TRUSSES****************
  
 1) MEAN ROOF HEIGHT ON TRUSS DRAWINGS IS
 15 FT. AND THE MRF ON THE DESIGN
 COMPLIANCE FORM SUBMITTED WITH THE
 PLANSIS 16 FT. PLEASE CORRECT.
  
 2) TRUSS LAYOUT MUST HAVE WET
 SIGNATURE,DATE AND EMBOSSED SEAL OF THE
 ENGINEER
 AND THE ENGINEERS TITLE BLOCK PER
 61G15-23.002 F.A.C.
  
 3) TRUSS DRAWINGS NEED TO HAVE
 ENGINEERSWET SIGNATURE, SIGNATURE STAMP
 IS NOT
 ACCEPTABLE.
  
 4) INSTALLATION AND BRACING SHEETS ARE
 MISSING.
  
 5) SPECIFY UPLIFT AND ANCHORS FOR
 GIRDERFG5.
  
 6) SPECIFY UPLIFT AND ANCHORS USED TO
 CONNECT TRUSSES TO GIRDERS AT OPEN
 PORCHAND AT LEFT OF GARAGE. GIRDERS
 FG2B,FG5 AND FG2A.
  
 7) TRUSSES HJH, HJI, HJJ HAVE UPLIFT
 VALUES ON TRUSS DRAWINGS WHICH EXCEED
 THOSE ON PLANS. PLEASE CORRECT.
  
 8) PROVIDE DETAILS OF CONNECTION BETWEEN
 GROUTED BLOCK COLUMNS AND WOOD GIRDERS
 AT COVERED PORCH. SPECIFY ANCHOR
 CAPACITIES AND UPLIFT LOADS. REVISED BY
 ARCHITECT IN LETTER DATED FEB.5,2001.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-29 Cont ID  
Sent By rmcdouga Date 2001-01-29 Time 10:44 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-17 Cont ID  
Sent By rmcdouga Date 2001-01-17 Time 13:15 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-17 00:00:00DENIED
  
 1) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF METRO-DADE OR SBCCI PRODUCT
 APPROVALS FOR THE FOLLOWING:
 - GLASS BLOCK
 - GARAGE DOORS
 - STORM PANELS
 - 3'X8' SINGLE DOOR
  
 NOTE: DRAFT OF PRODUCT APPROVAL FOR
 STORM PANELS IS NOT ACCEPTABLE.
  
 2) IN ADDITION TO PRODUCT APPROVALS FOR
 STORM PANELS,PROVIDE KEY PLAN AND
 INSTALLATION SCHEDULE. INDICATE
 SPECIFIC TYPE OF ANCHORS THAT WILL BE
 USED.
  
 3) DOORS INTO A/C STORAGE SHALL COMPLY
 WITH THE FLORIDA ENERGY CODE SEC.603.1.
  
 4) PROVIDE (2) COMPLETED DESIGN
 COMPLIANCE FORMS WITH WET
 SIGNATURE,DATE AND EMBOSSED SEAL OF THE
 DESIGNER OF RECORD.
  
  
 5) PROVIDE MANUFACTURERS INFORMATION,
 INCLUDING UL OR OTHER AGENCY LISTING,
 FOR GAS GRILL.
  
 6) TRUSS LAYOUT AND SHOP DRAWINGS MUST
 BE REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD PRIOR TO TRUSS INSTALLATION.
 TRUSS LAYOUT PLAN AND DRAWINGS MUST BE
 WET SIGNED,DATED AND EMBOSSED BY THE
 ENGINEER.
  
 7) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BUILDING PLAN REVIEW
 (561) 659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-01-16 Cont ID  
Sent By sgraham Date 2001-01-16 Time 09:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***