Plan Review Details - Permit 00120295
Plan Review Stops For Permit 00120295
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-19 Cont ID  
Sent By jwitmer Date 2001-01-19 Time 11:20 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-20 Cont ID  
Sent By jwitmer Date 2000-12-20 Time 09:21 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 FLORIDA ACCESSIBILITY CODE:
 1). PASSENGER LOADING ZONE: 4.6.6:ACCESS
 AISLE 60" X 20'-0".
 2).RAMPS: ADMINISTRATIVE CODE104.2.2
 DETAILS & DRAWINGS SHOWING STRUCTURAL
 DETAILS, SLOPE, LENGTH, GAURDRAIL DETAIL
 ENTRY DETAIL TO SALES TRAILER 4.13.8
 FL. ACC. CODE RAMP TO SALES TRAILER
 TRANSSITION NOT TO EXCEED 3/4".
 LANDINGS 4.8.4.2:ALL LANDINGS ON RAMPS
 (BOTTOM OF RAMP)SHALL BE 72" OF STRAIGHT
 & LEVEL CLEARENCE.
 3).FL. ACC. CODE 4.9.2: TREADS SHALL NOT
 BE LESS THAN 11" WIDE AND OPENRISERS
 ARE NOT PERMITTED.
 S.B.C.1007.3.1 THE SUM OF 2 RISERS & 1
 TREAD SHALL NOT BE LESS THAN 24" & NOT
 MORE THAN 25".
 4).ADMINISTRATIVE CODE 104.2.2: MOBILE
 HOMES (USED FOR RESIDENTIAL UNITS) DO
 NOT COMPLY WITH COMMERCIAL USAGE. SBC
 TABLE 1604.1 RESIDENTIAL SLEEPING 30 PSF
 LIVE LOAD VS 50 PSF OFFICES. THE DOORWAY
 HALLS & BATHROOM MUST COMPLY WITH FL.
 ACCESSIBILITY CODE WHICH RESIDENTIAL
 MOBILE HOMES DO NOT.
 S.S.553.35-553.42 MANUFACTURED BUILDINGS
 MOBILE COMPLY WITH STATE BUILDING STAND-
 ARDS.553.381 MANUFACTURES CERTIFICATION
 NUMBER.
 WE WILL NEED 2 SETS OF PRINTS, ALSO THE
 TIE DOWN PLANS. WE WILL NEED THE MAXIMUM
 PIER LOADS IN POUNDS BASED ON THE SOIL
 VALUES.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 09:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-12 Cont ID  
Sent By dpalmer Date 2000-12-12 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2000-12-12 Time 17:25 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT ELECTRICAL DETAIL
 ON FEED TO THE TRAILER. NONE SHOWN
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-01-31 Cont ID  
Sent By dlauderm Date 2001-01-31 Time 09:13 Rev Time 1.00
Received By dlauderm Date 2001-01-31 Time 09:52 Sent To  
Notes
2001-01-31 00:00:00PASSED WITH PROVISOS:
 REVIEWED BY MOHAMMAD R. AMINI
 1. PASSED PER COMMENTS MADE BY
 MANY GONZALEZ, TO THE ENGLE HOMES
 REPRESENTATIVES.
 2. DRIVEWAY APPROACH MUST MEET CWPB
 STANDARDS. SEE ATTACHED STANDARD

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-12 Cont ID  
Sent By mcarsill Date 2001-01-12 Time 09:23 Rev Time 0.00
Received By mcarsill Date 2001-01-12 Time 09:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-19 Cont ID  
Sent By mcarsill Date 2000-12-19 Time 14:26 Rev Time 0.00
Received By mcarsill Date 2000-12-19 Time 14:26 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE IN WRITING HOW LONG
 THE TRAILER IS EXPECTED TO REMAIN ON
 SITE TO THE FIRE RESCUE DEPARTMENT.
 2) ELECTRIC POWERED SMOKE DETECTORS ARE
 REQUIRED WITHIN THE TRAILER.
 3) PLEASE PROVIDE A PORTABLE FIRE
 EXTINGUISHER FOR TRAILER WITH A CURRENT
 SERVICE TAG.
 4) STAIRS TO COMPLY WITH BUILDING AND
 FIRE CODE REQUIREMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-15 Cont ID  
Sent By jleech Date 2000-12-15 Time 09:05 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-01-27 Cont ID  
Sent By jleech Date 2001-01-27 Time 11:16 Rev Time 0.25
Received By jleech Date 2001-01-27 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-01-21 Cont ID  
Sent By pschmitz Date 2001-01-21 Time 14:14 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-21 00:00:00PLUMBING PLAN REVIEW DENIED 2ND TIME
 (1) SPC 94 SEC 104.3 DRAWINGS,SPECIFI-
 CATIONS SHOWING LOCATION OF WATER AND
 SANITARY SEWER CONNECTION,WITH A BACK
 FLOW PREVENTER ON WATER SERVICE. LOCAL
 ORDINANCE # 2853-95.
 SEWER CONNECTION SPC 94 SEC 301.11.1
 WATER CONNECTION SPC 94 SEC 301.11.2
 END 0F COMMENTS,QUESTIONS CONTACT
 PAUL SCHMITZ 561-659 8096-X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-12 Cont ID  
Sent By jleech Date 2000-12-12 Time 19:12 Rev Time 0.33
Received By pschmitz Date 2000-12-12 Time 19:11 Sent To  
Notes
2001-01-08 00:00:00NO DISPOSAL SYSTEM FOR PLUMBING FIXTURES

Review Stop Z ZONING
Rev No 1 Status P Date 2000-12-12 Cont ID  
Sent By sgraham Date 2000-12-12 Time 09:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***