Plan Review Details - Permit 00120198
| Plan Review Stops For Permit 00120198 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-28 |
Time |
16:15 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: | | | 1).1707.4.1 IMPACT RESISTANT GLAZING | | | SYSTEMS REQUIRED. IF THE STORE FRONT | | | GLAZING SYSTEM DOESN'T COMPLY WITH THE | | | LARGE MISSLE IMPACT TEST, STORM SHUTTERS | | | THAT HAVE APPROVAL ARE REQUIRED. | | | 2).SBC 3106.2 FABRIC AWNINGS OR CANOPIES | | | REQUIRE FLAME RESISTANT MATERIALS. | | | 3).SPRINKLER SYSTEM PLANS NOT INCORPARA- | | | TED IN PLANS. | | | 4). 104.2.2 ADD INFO ON SOFFIT DETAILS, | | | NOTE SAID TO:ATTACHSOFFIT VERTICAL | | | STUDS TO STRUCTURE ABOVE.WHAT TYPE OF | | | SHOT, &HOW OFTEN? HOW OFTEN IS THE | | | DROPPED CEILING TO BE SUPPORTED & WITH | | | WHAT GAUGE HANGER WIRE? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-28 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-28 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE:PLEASE SHOW LOAD CALCULATIONS | | | COMPLETED. PLEASENOTE ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%. | | | ALSO LOADS FOR TRACK LIGHITNG PER 220- | | | 12B. | | | | | | 2)NOTE: EMERGENCY LIGHTING??? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-11 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-11 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FABRIC AWNING TO BE FIRE RETARDANT. | | | 2) NO FIRE ALARM EQUIPMENT SHOWN WITHIN | | | TENANT SPACE. | | | 3) CLEARLY IDENTIFY EMERGENCY LIGHTING | | | WITHIN TENANT SPACE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-04 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-04 |
Time |
08:55 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-01-04 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | 1. CONDENSATE DRAIN LINE SHALL NOT GO TO | | | SANITARY PER LOCAL UTILITY REQUIREMENT | | | MUST GO TO LANDLORDS CONDENSATE RISER OR | | | STORM SEWER OR OUTSIDE TO APPROVED FRENC | | | DRAIN | | | 2. EMERGENCY DRAIN SHALL NOT TIE INTO | | | PRIMARY DRAIN, BUT SHALL RUN AS A MIN. | | | 3/4" SEPARATE LINE TO A CONSPICUOS | | | LOCATION PER 1997 SMC 304.8.6 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-12-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-19 |
Time |
16:14 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2000-12-19 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.REDO WASTE AND VENT DIAGRAM ON M3 TO | | | 94 SPC CODE. NO DRY VENTS ON WATER | | | CLOSET. | | | | | | 2.HANDICAP DRINKING FOUNTAIN WITH CUP | | | DISPENSOR IS REQUIRED SPC TABLE 407. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 569-8096 EXT 8377 |
|
|
|