Plan Review Details - Permit 00120198
Plan Review Stops For Permit 00120198
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-28 Cont ID  
Sent By jwitmer Date 2000-12-28 Time 16:15 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1).1707.4.1 IMPACT RESISTANT GLAZING
 SYSTEMS REQUIRED. IF THE STORE FRONT
 GLAZING SYSTEM DOESN'T COMPLY WITH THE
 LARGE MISSLE IMPACT TEST, STORM SHUTTERS
 THAT HAVE APPROVAL ARE REQUIRED.
 2).SBC 3106.2 FABRIC AWNINGS OR CANOPIES
 REQUIRE FLAME RESISTANT MATERIALS.
 3).SPRINKLER SYSTEM PLANS NOT INCORPARA-
 TED IN PLANS.
 4). 104.2.2 ADD INFO ON SOFFIT DETAILS,
 NOTE SAID TO:ATTACHSOFFIT VERTICAL
 STUDS TO STRUCTURE ABOVE.WHAT TYPE OF
 SHOT, &HOW OFTEN? HOW OFTEN IS THE
 DROPPED CEILING TO BE SUPPORTED & WITH
 WHAT GAUGE HANGER WIRE?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-28 Cont ID  
Sent By dpalmer Date 2000-12-28 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2000-12-28 Time 14:38 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE:PLEASE SHOW LOAD CALCULATIONS
 COMPLETED. PLEASENOTE ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%.
 ALSO LOADS FOR TRACK LIGHITNG PER 220-
 12B.
  
 2)NOTE: EMERGENCY LIGHTING???
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By mcarsill Date 2000-12-11 Time 12:27 Rev Time 0.00
Received By mcarsill Date 2000-12-11 Time 12:27 Sent To  
Notes
2001-01-08 00:00:001) FABRIC AWNING TO BE FIRE RETARDANT.
 2) NO FIRE ALARM EQUIPMENT SHOWN WITHIN
 TENANT SPACE.
 3) CLEARLY IDENTIFY EMERGENCY LIGHTING
 WITHIN TENANT SPACE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-01-04 Cont ID  
Sent By ndenmark Date 2001-01-04 Time 08:55 Rev Time 0.50
Received By ndenmark Date 2001-01-04 Time 08:55 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1. CONDENSATE DRAIN LINE SHALL NOT GO TO
 SANITARY PER LOCAL UTILITY REQUIREMENT
 MUST GO TO LANDLORDS CONDENSATE RISER OR
 STORM SEWER OR OUTSIDE TO APPROVED FRENC
 DRAIN
 2. EMERGENCY DRAIN SHALL NOT TIE INTO
 PRIMARY DRAIN, BUT SHALL RUN AS A MIN.
 3/4" SEPARATE LINE TO A CONSPICUOS
 LOCATION PER 1997 SMC 304.8.6

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-19 Cont ID  
Sent By jleech Date 2000-12-19 Time 16:14 Rev Time 0.75
Received By jleech Date 2000-12-19 Time 16:14 Sent To  
Notes
2001-01-08 00:00:001.REDO WASTE AND VENT DIAGRAM ON M3 TO
 94 SPC CODE. NO DRY VENTS ON WATER
 CLOSET.
  
 2.HANDICAP DRINKING FOUNTAIN WITH CUP
 DISPENSOR IS REQUIRED SPC TABLE 407.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 569-8096 EXT 8377