| Plan Review Stops For Permit 00120164 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-01-18 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-18 |
Time |
15:54 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-03-21 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2001-03-21 00:00:00 | REVISION UNDER PERMIT 01030581. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-12-22 |
Time |
10:18 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLEASE PROVIDE SPECIFIC CONNECTION | | | DETAILS FOR THE SOFFIT AND PARTITION | | | ATTACHMENT TO THE DECK ABOVE.SEE SBC | | | 104.2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-15 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-15 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-19 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-19 |
Time |
13:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-27 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-27 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAMAND | | | PLANS. WHERE IS TRANSFORMER LOCATED AND | | | IS FEEDERS FROM TRANS FORMER TO PANEL | | | LONGER THAN 25`???? | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATION. | | | SQ. FT. ECT.ALL CONTINUOUS LOADS AT 125% | | | | | | 3)NOTE: PLEASE NOTE AND SHOW TRANSFORMER | | | LOCATION. | | | | | | 4)NOTE: PLEASE SHOW AIC RATINGS FOR ALL | | | ELECTRICAL EQUIPMENT. ALL MAINS/PANELS | | | AND BRKRS ARE TO BE RATED FOR THE AVAIL- | | | -ABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-11 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-11 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH TO BE AT LEAST | | | CLASS C SINCE THE SPACE IS EQUIPPED | | | WITH FIRE SPRINKLER HEADS. | | | 2) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR THE FIRE ALARM | | | EQUIPMENT SHOWN ON THE PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-03-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-03-21 |
Time |
10:40 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-03-21 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2001-03-21 00:00:00 | REVISION UNDER PERMIT 01030581. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-28 |
Time |
07:33 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-12-28 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. NO COMBUSTIBLES ALLOWED IN RETURN AIR | | | PLENUM (ABOVE CEILING AREA) PER 1997 SMC | | | 609.1.1 | | | 2. M-1 ASHRAE 62-89 CALCS SHOW 1000CFM | | | CORRECT NOTE ON M-2 FROM 100 CFM TO 1000 | | | CFM TO BE CONSISTANT W/ CALCS | | | 3. LOCAL ORDINANCE REQUIRES MINIMUM OF | | | 18" BETWEEN ROOF SURFACE AND BOTTOM OF | | | STAND, NOT 14" AS SHOWN ON PLAN. PROVIDE | | | 18" MINIMUM CLEARANCE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-22 |
Time |
11:57 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-22 |
Time |
11:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-14 |
Time |
14:18 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2000-12-14 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.WOMENS HANDICAP STALL MUST COMPLY WITH | | | FACBC 4.17.30 SHOW TURNING CIRCLE IN | | | ALL HANDICAP STALLS. | | | | | | 2.LOUNGE SINK MUST COMPLY TO FACBC 4.24 | | | THRU 4.24.7. | | | | | | 3.3" FLOOR DRAINS IN BATHROOMS ARE | | | SHOWN ON SANITARY RISER DIAGRAM P-2 | | | BUT NOT ON PLUMBING LAYOUT P-1. | | | | | | 4.FLOOR DRAINS IN RESTROOMS MUST BE | | | PRIMER PER 94 SPC 409.4.1.1. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|