Plan Review Details - Permit 00120094
Plan Review Stops For Permit 00120094
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-28 Cont ID  
Sent By jwitmer Date 2000-12-28 Time 12:36 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1). FL.SS 481 REQUIRES ARCHETECTS TO
 SIGN & SEAL THEIR WORK.
 2). SBC 1804.2 AMEND SOIL TEST REPORT
 BEARING VALUE.
 3). TERMITE TREATMENT IN ACCORDANCE WITH
 FL SS 482/487 SEC 5E-14.106 FL ADMINIS-
 TRATIVE CODE.
 4).DESIGN CRITERIA:OF BUILDING, INCLUDE
 DESIGN INFO SBC1606.1 OR ASCE-7, DESIGN
 PRESSURE, MEAN ROOF HEIGTH & IMPORTANCE
 FACTOR.
 5). ENERGY CALCULATIONS.
 6).SBC 1606.2.6.2- COMPONENTS/CLADDING
 104.2.2 ADD INFO FOR DOOR AND WINDOW
 BUCK ATTACHMENT.
 1606.4.1-PRODUCT APPROVAL FOR WINDOWS
 2 COPIES, DADE COUNTY OR SBCCI REPORT
 GLAZED OPENINGS THAT DON'T MEET THE
 REQUIREMENTS FOR LARGE MISSLE TESTING
 WILL ALSO NEED STORM SHUTTERS THAT MEET
 THE TESTING REQUIREMENTS AND HAVE
 PRODUCT APPROVAL REPORTS. CITY POLICY
 FOR STORM SHUTTERS REQUIRES A FASTENING
 SCHEDULE AND A KEY PLAN THAT CORRALATES
 WITH THE FASTENING SCHEDULE.
 7).SBC 1707.5- PRODUCT TESTING FOR ROOF
 COVERINGS & TILE INSTALATION.
 8). ADMIN CODE 104.2.2 ADD INFO FOR
 DETAILS ON A-5 SEC 2 CEILING 3/4"
 PLASTER OVER PAPER BACKED METAL LATH
 OVER 1X3. WHAT TYPE OF METAL LATH IS TO
 BE INSTALLED & WHAT MINIMUM WEIGHT METAL
 PLASTER BASE IS TO BE USED?
 9). POSSIBLE DISCREPANCY, SHEET A5.1.2
 A NOTE TO USE GWB TO DECK IS TYPICAL
 AND A NOTE TO USE PLYWOOD SHEATHING?
 10). INTERIOR OF BUILDING WHERE DROPPED
 CEILING IS TO BE USED WHAT TYPE OF
 BOTTOM CORD BRACING WILL BE USED ON THE
 TRUSSES.
 11)104.2.2 ADD INFO ON THE SUSPENDED
 CEILING.MATERIAL/ SUPPORT?
 12). FL ACCESSIBILITY CODE 4.13.9 DOOR
 HARDWARE= HANDLES
 13). FL ACCESSIBILITY CODE 4.35 DRESSING
 ROOMS SEE: 4.35.2 CLEAR FLOOR SPACE
 4.35.4 BENCH
 14). FL ACCESSIBILITY CODE 4.1.2
 ACCESSIBLE SITE AND EXTERIOR FACILITIES-
 THE SITE PLAN A1.0 DOESN'T INDICATE
 PATHWAYS TO THE RESTROOMS NOR THE
 VENDING MACHINES.THE ACCESSIBLE PATH
 SHOULD LEAD TO ALL ELEMENTS.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412
 PLEASE RETURN THE REVIEWED PAGES AFTER
 THE CORRECTIONS ARE COMPLETED, THIS WILL
 EXPEDITE THE PLAN REVIEW PROCESS, THANK
 YOU!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-27 Cont ID  
Sent By dpalmer Date 2000-12-27 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2000-12-27 Time 12:30 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW MEANS OF DISCONNECT
 FOR POWER/LIGHTING AT GAZEBO(S).
  
 2)NOTE: PLEASE SHOWALL CONTINUOUS LOAD
 -S AT 125% AND 125% FOR LARGEST MOTOR.
  
 PLEASE MAKE SURE THE PLANS THAT ARE
 SUBMITTED FOR PERMIT ARE SIGNED AND
 SEALED BY THE ENGINEER OF RECORD PER
 61G15-23.002 AND CHAPTER 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-21 Cont ID  
Sent By mcarsill Date 2000-12-21 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2000-12-21 Time 14:48 Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 REQUIRED PER CITY CODE REQUIREMENTS.
 2) PROVIDE COMPLETE FIRE SPRINKLER
 SYSTEM PLANS AND PERMIT TO THE
 CONSTRUCTION SERVICES DEPARTMENT PRIOR
 TO COMMENCING ANY WORK. HYDRAULIC
 CALCULATIONS ARE TO BE PROVIDED.
 3) FIRE SPRINKLER SYSTEM TO BE
 SUPERVISED BY AN APPROVED CENTRAL
 STATION APPROVED BY THE FIRE RESCUE
 DEPARTMENT.
 4) PROVIDE FIRE EXTINGUISHER WITH
 CURRENT SERVICE TAG IN PRO-SHOP.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-28 Cont ID  
Sent By ndenmark Date 2000-12-28 Time 07:51 Rev Time 0.33
Received By ndenmark Date 2000-12-28 Time 07:51 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1. SIGNED AND SEALED DRAWINGS REQUIRED
 FOR REVIEW
 2. BATHROOM EXHAUST FANS TO RUN ANY TIME
 THE BUILDING IS OCCUPIED AND THE AHU IS
 RUNNING.
 3. ALL CONDENSING UNITS ON GROUND SHALL
 BE MOUNTED ON SOLID CONCRETE PADS MIN.
 3" ABOVE FINISHED GRADE.
 4. NFPA 90A 4-4.4.3 REQUIRES NOTIFICATIO
 TO BLDG FIRE ALARM OR HORN AND STROBE ON
 ACTIVATION OF DUCT SMOKE DETECTOR

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-14 Cont ID  
Sent By jleech Date 2000-12-14 Time 10:56 Rev Time 1.00
Received By jleech Date 2000-12-14 Time 10:56 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.FITTING ROOM MUST COMPLY WITH 97 FACBC
 4.35.2 AND 4.35.4.
  
 2.MINIMUM SIZE OF BATHROOM FLOOR DRAINS
 IS 3" SPC 409.4.1.1. PAGE P1.2 SAN.
 RISER SHOWS 2" FLOOR DRAINS.
  
 3.ONE HIGH LOW DRINKING FOUNTAIN
 REQUIRED TO MEET FACBC 4.1.3(10) AND
 TABLE 407 94 SPC.
  
 4.FLOOR DRAIN IN MECH ROOM MUST BE FLOOR
 DRAIN NOT FUNNUL DRAIN. COUNTY
 ADMENDMENTS 507.6.2.
  
 5.DRAIN FROM WATER HEATER PAN DRAIN MUST
 BE 1" SPC 507.8.2.
  
 6.RELIEF VALVE SHALL BE PIPED FULL SIZE
 SEPARATELY. SPC 507.8.4.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***