Plan Review Details - Permit 00120087
Plan Review Stops For Permit 00120087
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-22 Cont ID  
Sent By dpalmer Date 2001-02-22 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2001-02-22 Time 19:40 Sent To  
Notes
2001-02-22 00:00:00*********** PROVISO/ REVISION ********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 PLEASE SUBMIT THE REVISIONFOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 21:12 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 21:12 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PER F.A.C. ALL PLANS THAT ARE
 SIGNED AND SEALED BY AN ARCH OR ENGINEER
 MUST HAVE THE RAISED SEAL CLEARLY
 VISIBLE. ALSO ALL PLANS THAT ARE SIGNED
 AND SEALED MUST CONTAIN A TITLE BLOCK
 OF THE ARCH OR ENGINEER OF RECORD.
 PLEASE SEE F.A.C 61G15-23.002 AND 61G16
 ALSO CHAPTERS 481.221 AND 471.025
  
 2)NOTE: PLEASE SHOW COLD WATER PIPE AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 PER 250-5O OR CLRIFY IF CPVC.
  
 3)NOTE: PLEASE SEE RISER DIAGRAM. PANEL
 IS SHOWN NEXT TO METERCAN. PLANS SHOW
 ON THE OTHER SIDE OF HOUSE. PLEASE
 CLARIFY IF PANEL IS FED UNDER GROUND
 AND IF PANEL IS MCB?
  
 4)NOTE: PLEASE NOTE PER NFPA-72 2-2.1.1-
 .1 . A SMOKE DETECTOR IS REQ`D ON EACH
 LEVEL OF DWELLING.
  
 5)NOTE: PLEASE NOTE THAT NO CATV OR
 TELEPHONE OUTLETS ARE SHOWN? IF THESE
 ITEMS ARE GOING TO BE INSTALLED ? THEN
 ALL MUST BE ON PLANS.
  
 6)NOTE: PLEASE SEE SECOND FLOOR PLAN.
 OUTLETS MISSING PER 210-52 IN BEDROOM?
 AND OUTLET PER 2` OF WALL 210-52
  
 7)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE/ISLAND AS GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 ETX 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-15 Cont ID  
Sent By jleech Date 2000-12-15 Time 11:05 Rev Time 0.33
Received By jleech Date 2000-12-15 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 A/H UNITS. LOCATION NOT THE SAME AS
 FLOOR PLAN. PLEASE REVISE BEFORE A/C
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-11 Cont ID  
Sent By jleech Date 2000-12-11 Time 08:30 Rev Time 0.33
Received By jleech Date 2000-12-11 Time 08:30 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 1.EXHAUST FAN REQUIRED IN MASTER SUITE
 TUB AND SHOWER AREA. 97 SMC 503.3.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-11 Cont ID  
Sent By jleech Date 2000-12-11 Time 08:58 Rev Time 0.33
Received By jleech Date 2000-12-11 Time 08:57 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 1.REVISED SANITARY RISER DIAGRAM
 REQUIRED TO MEET THE CODES OF THE 94
 SPC. CHAPTER 7 AND 9.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-04-19 Cont ID  
Sent By jgomez Date 2001-04-19 Time 19:10 Rev Time 3.00
Received By jgomez Date 2001-04-19 Time 19:10 Sent To  
Notes
2001-04-19 00:00:00CHECKLIST:
 1-REAR ELEVATION EXCEEDS THE AMOUNT OF
 OPENINGS ALLOWED BY TABLE 600 SBC/97.
 NOT DONE FROM PREVIOUS CHECKLIST.
 2-SUBMIT COMPLETE SET OF ENGINEERED
 DRAWINGS FOR ROYAL WALL SYSTEM
 SHOWING ALL PANELS AND REINFORCING.
 3-PROVIDE PRODUCT APPROVAL FOR:
 -SLIDING GLASS DOORS WITH THE SIZE
 SHOWN ON PLANS AND ELEVATIONS. (8' HI)
 -ARCHED AND RECTANGUALAR WINDOWS WITH
 THE SIZE SHOWN ON PLANS & ELEVATIONS.
 NOTE: MULLIONS PRODUCT APPROVAL IS FOR
 WINDOWS FROM THE SAME MANUFACTURER.
 ARCHED WINDOWS SUBMITTED ARE FROM
 LAWSON AND FIXED WINDOWS ARE FROM PGT
 THIS IS NOT ALLOWED.
 -FLAT ROOF SYSTEM. ITEM SUBMITTED ARE
 THE SPECS. WE NEED THE ACTUAL PRODUCT
 APPROVAL AS WELL.
 4-OWES $1806.45 FOR LOW VALUATION, RADON
 AND WESTERN EXPANSION FEES.
 5-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 6-PROVIDE COMPLETE DETAILS FOR THE
 CONSTRUCTION OF THE WINDOW SEAT.
 SKETCH SUBMITTED NEEDS ADDITIONAL
 INFORMATION LIKE: FRAMING FOR WINDOW,
 REINFORCEMENT TO RECEIVE STORM PANELS,
 WHY IS ONLY ONE 2X TOP PLATE?, WINDOW
 HEADER, GABLE END DETAIL, ETC.
 MAKE THESE DRAWINGS PART OF THE SET,
 NOT A SEPARATE SHEET.
 7-RAILING DRAWINGS TO BE SITE SPECIFIC
 FOR THIS JOB, NOT GENERAL DETAILS. SEE
 ACTUAL INSTALLATION CONDITIONS SHOWN
 ON PROFESSIONAL OF RECORD DRAWINGS.
 -HOW IS THE RAILING ATTACHED TO THE
 GLULAM BEAM AND TO THE STEEL COLUMN?
 -BOTTOM RAIL SHALL NOT ALLOW 2" SPHERE
 TO PASS THRU. SEC 1015.3 SBC 1997.
 -ENGINEER OF RECORD TO REVIEW THESE
 DRAWINGS PRIOR TO SUBMITTAL.
 -ENGINEER FOR RAILING SYSTEM TO DATE
 DRAWINGS AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES.
 8-FLOOR PLANS AND EXTERIOR ELEVATIONS
 DON'T MATCH. SEE NUMBER OF WINDOWS AND
 LOCATION SHOWN ON PLANS VS ELEVATION
 AT LEFT SIDE.
 9-SEE COMMENTS BY ZONING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-03-12 Cont ID  
Sent By jgomez Date 2001-03-12 Time 11:39 Rev Time 3.50
Received By jgomez Date 2001-03-09 Time 17:35 Sent To  
Notes
2001-03-12 00:00:00CHECKLIST:
 1-REAR ELEVATION EXCEEDS THE AMOUNT OF
 OPENINGS ALLOWED BY TABLE 600 SBC/97.
 2-SUBMITCOMPLETE SET OF ENGINEERED
 DRAWINGS FOR "ROYAL WALL" SYSTEM
 SHOWING ALL PANELS REINFORCING.
 3-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -SLIDING GLASS DOORS (EXPIRED).
 -GARAGE DOOR THAT MEET THE MINIMUM
 DESIGN PRESSURE CALCULATED BY THE
 ENGINEER (SEE ROOF FRAMING PLAN).
 -ARCHED WINDOW ABOVE ENTRY DOORS.
 -FLAT ROOF SYSTEM.
 4-OWES $1806.45 FOR LOW VALUATION, RADON
 FEES AND WESTERN EXPANSION FEES.
 PLEASE PAY ATTACHED RECEIPT.
 5-STORM PANELS:
 -PROVIDE COMPLETE INFORMATION INCLUDING
 A KEY PLAN AND INSTALLATION SCHEDULE.
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 -MAY APPLY FOR A SEPARATE PERMIT.
 6-REVISE ENERGY CALCULATIONS:
 -SEE ROYAL WALL DRAWINGS FOR INSULATION
 & MATERIALS USED IN THIS CONSTRUCTION.
 -EXTERIOR FRAMING IS NOT INCLUDED IN
 THE CALCULATIONS. WHY IS IT MISSING?
 7-SOIL TEST REPORT: ENGINEER DIDN'T
 PROVIDE ORIGINAL SIGNATURE AS REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES.
 8-PROVIDE COMPLETE DETAIL/SECTION THRU
 WINDOW SEAT AT GARAGE.
 9-SURVEY DOESN'T SHOW THE DRIVEWAY, BUT
 A TEMPORARY WALKWAY. DRIVEWAY PERMIT
 CAN NOT BE ISSUED IF DRIVEWAY IS NOT
 SHOWN.
 10-SCREEN BUILDERS INC. DRAWINGS TO BE
 SITE SPECIFIC. SHOW DETAILS THAT APPLY
 TO ACTUAL INSTALLATION.
 -BOTTOM RAIL SHALL NOT ALLOW A 2"
 SPHERE TO PASS THRU. SEC 1015.3 SBC/97
 NOTE: ENGINEER OF RECORD TO REVIEW
 THESE SHOP DRAWINGS PRIOR TO SUBMITTAL
 TO THIS OFFICE. PROVIDE GENERAL STAMP
 FOR SHOP DRAWINGS REVIEW.
 11-FLOOR PLANS AND EXTERIOR ELEVATIONS
 DON'T MATCH. SEE SLIDING GLASS DOORS
 AT GRAND RM & WINDOWS AT CAFE AREA.
 12-REVISE SPACING OF STEEL COLUMNS THAT
 ARE BETWEEN THE STAIRS. THERE SHALL BE
 36" MINIMUM CLEAR WIDTH OF STAIRS AS
 REQUIRED BY SEC 1007.6.3 SBC 1997.
  
  
  
  
  
  
  
 NOTES:
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ, BUILDING PLAN REVIEWER, AT
 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By jgomez Date 2001-01-10 Time 12:14 Rev Time 3.50
Received By jgomez Date 2001-01-10 Time 10:52 Sent To  
Notes
2001-01-10 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-SURVEY DOESN'T MATCH PLANS.
 -PLAT MUST BE RECORDED AND SURVEY
 UPDATED.
 3-ENGINEER OF RECORD TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES.
 -ENGINEER TO PROVIDE ORIGINAL SIGNATURE
 ON ALL DOCUMENTS SUBMITTED FOR PUBLIC
 RECORDS.
 4-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS FOR "ROYAL WALL" SYSTEM FOR
 THIS SPECIFIC HOUSE.
 -NOTE: IF HOUSE IS TO BE LOCATED AT
 ZERO LOT LINE, THEN, THE 2" CONCRETE
 PANEL WILL NOT PROVIDE THE ONE HOUR
 FIRE RATING REQUIRED BY TABLE 600.
 TABLE 709.2.1.1 SBC 1997.
 -MAKE SURE ENGINEERED SET OF DRAWINGS
 HAVE THE ENGINEER'S INFORMATION AS
 REQUIRED BY FLORIDA STATUTES. 471.
 5-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -ENTRY DOORS.
 -SLIDING GLASS DOORS OF SIZES SHOWN ON
 PLANS. (EXPIRED )
 -GARAGE DOOR THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD. ALSO, REPORT TO BE LEGIBLE.
 -FIXED AND ROUND WINDOWS.
 -SINGLE HUNG WINDOWS.
 -WINDOW MULLIONS.
 -GLASS BLOCK (1 HR AT ZERO LOT LINE)
 -FLAT ROOF SYSTEM AT BALCONY.
 6-VALUE DECLARED ON APPLICATION IS VERY
 LOW. OWES ADDITIONAL PERMIT FEES OF
 $1056.45 INCLUDING RADON FEES. AND,
 $750 FOR WESTERN EXPANSION IMPACT FEES
 7-STORM PANELS:
 -PROVIDE A KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE (AS PER CITY
 SAMPLE ATTACHED).
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 8-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT 2ND FLOOR FRAMING PLAN.
 SECTION 2305.2 SBC 1997.
 9-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING THOSE BY THE OTHER TRADES.
 10-REVISE ENERGY CALCULATIONS:
 -NUMBER OF BEDROOMS IS 5. SEE PLANS.
 -ORIGINAL SIGNATURES @ BOTTOM OF FORM.
 11-SOIL TEST REPORT:
 -PROVIDE COMPLETE SOIL TEST REPORT AS
 PER SECTION 1804.2 OF CITY AMENDMENTS.
 -REPORT TO HAVE ORIGINAL SIGNATURE AS
 PER 471 FLORIDA STATUTES.
 12-PROVIDE COMPLETE DETAIL/SECTION THRU
 CUPOLA. SPECIFY ALL CONNECTORS.
 SECTION 104.2.2 CITY AMENDMENTS.
 13-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM:
 -USE CITY FORM.
 -NEED ORIGINAL SIGNATURE AS PER 471 OF
 FLORIDA STATUTES.
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -ONLY TWO SETS OF DRAWINGS AND SUBMITTAL
 ARE REQUIRED.
2001-01-08 00:00:00CHECKLIST:
 1-

Review Stop Z ZONING
Rev No 2 Status F Date 2001-04-20 Cont ID  
Sent By sgraham Date 2001-04-20 Time 16:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-04-20 00:00:00MUST MEET FRONT SETBACK

Review Stop Z ZONING
Rev No 1 Status F Date 2001-03-13 Cont ID  
Sent By sgraham Date 2000-12-06 Time 13:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-03-13 00:00:00NEED 20' FRONT SETBACK