Plan Review Details - Permit 00120084
Plan Review Stops For Permit 00120084
Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-04-19 Cont ID  
Sent By dpalmer Date 2001-04-19 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2001-04-19 Time 11:49 Sent To  
Notes
2001-04-19 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT THE SAME PLANS
 WERE SUBMITTED AGAIN WITH NO CHANGES????
  
 ANOTHER 10% RE-SUBWILL BE DUE, AGAIN.
  
 PLEASE SUBMIT THE INFORMATION FOR THE FO
 RST SET OF REVIEW NOTES.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-05 Cont ID  
Sent By dpalmer Date 2001-03-05 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2001-03-05 Time 19:00 Sent To  
Notes
2001-03-05 00:00:00****************UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT NO CHANGES ON
 PLANS WERE DONE TO ADDRESS COMMENTS
 FROM FIRST REVIEW.
 PLEASE MAKE CORRECTIONS/CLARIFICATIONS
 AND SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 PLEASE NOTE A 10% RE-SUB FEE WILL BE DUE
 ON NEXT RE-SUB.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 20:55 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 20:54 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT CLARIFICAITON OF
 SERVICE.RISER SHOWS PANEL NEXT TO METER?
 YET PLANS SHOWS PANEL AND METER ON TWO
 SIDES OF HOUSE?
  
 2)NOTE: PLEASE SUBMIT CLARIFICATION ON
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 COLD WATER PIPE? PER 250-50. IS CWP CPVC
  
 3)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 MAINS/PANELS/ BRKRS. ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER NEC
 110-9.
  
 4)NOTE: PLEASE SEE OCP FOR HOT WATER
 HEATER. NOTE 20A BRKR? 125% 422-13
  
 5)NOTE: AS PER 61G15-23.002 OF THE F.A.C
 ALL PLANS CONTAINING SEAL MUST CONTAIN
 A TITLE BLOCK OF THAT PERSON OF RECORD.
 ALSO PER CHAPTER 471.025
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FORREVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-03-09 Cont ID  
Sent By pkrauss Date 2001-03-09 Time 10:14 Rev Time 0.30
Received By pkrauss Date 2001-03-09 Time 10:14 Sent To  
Notes
2001-03-09 00:00:00CORRECTIONS FROM 2ND SUBMITTAL - ENERGY
 CALCS (ADDRESS AND SEER ON PLANS), AND
 VENTS THRU THE ROOF NOT SIDE WALL
  
 TALKED WITH DOUG (AIRE CARE),INFORMED
 HIM HE NEEDED RETURN AIR DROP IN MASTER
 BEDROOM AREA OF THE HOUSE - HE HAS
 TRANSFERE GRILLE FROM MASTER BEDROOM
 AND CONTENDED THE AREA FROM THIS ROOM
 IS OPEN WITH NO DOORS BACK TO THE
 RETURN.I WARNED HIM IF THE INSPECTOR
 DOES NOT FEEL IT IS AN "OPEN" AREA,
 HE WOULD BE REQUIRED TO PUT A RETURN
 IN THIS AREA.
  
 NEEDS MECHANICAL PERMIT.
 PHK 3/9/01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-02-24 Cont ID  
Sent By jleech Date 2001-02-24 Time 13:26 Rev Time 0.50
Received By jleech Date 2001-02-24 Time 13:26 Sent To  
Notes
2001-02-24 00:00:00DENIED;
  
 SEE NOTES ON A/C PAGE.
 PLEASE DO YOUR HOME WORK BEFORE
 RESUBMITING.
  
 A/C PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By jleech Date 2000-12-09 Time 13:55 Rev Time 0.50
Received By jleech Date 2000-12-11 Time 07:06 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.ENERGY CAULKS ARE NOT THE SAME. TWO
 ARE FOR ABACOA AMD ONE IS FOR ANDROS
 ISLE.
  
 2.ENERGY CAULKS CALL FOR 12 SEER A/C
 UNIT A/C PLAN SHOWS 10 SEER.
  
 3.DRYER VENT CANNOT GO THRU A ZERO LOT
 LINE WALL. VENT MUST GO THRU ROOF.
  
 A/C PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-09 Cont ID  
Sent By jleech Date 2000-12-09 Time 13:50 Rev Time 0.25
Received By jleech Date 2000-12-09 Time 13:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-04-19 Cont ID  
Sent By jgomez Date 2001-04-17 Time 18:41 Rev Time 3.00
Received By jgomez Date 2001-04-17 Time 18:41 Sent To  
Notes
2001-04-17 00:00:00 
 1-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 2-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -SLIDING GLASS DOORS THAT COVERS SIZE
 SPECIFIED ON PLANS. (8'-0" HIGH DOORS)
 -DOUBLE DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON ENTRY ELEVATION.
 -FIXED WINDOWS.
 3-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS (SIGNED, SEALED AND DATED)
 FOR ROYAL WALL PANELS FOR THIS
 SPECIFIC HOUSE.
 -NOTE: ENGINEER OF RECORD TO REVIEW
 DRAWINGS PRIOR TO SUBMITTAL.
 4-AS REQUESTED ON THE PRELIMINARY SOIL
 INVESTIGATION, STANDARD PENETRATION
 TEST BORINGS ARE REQUIRED TO DETERMINE
 THE BEARING VALUES OF THE SOIL.
 5-FLOOD ZONE AO. WILL NEED AN ELEVATION
 CERTIFICATE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-03-12 Cont ID  
Sent By jgomez Date 2001-03-12 Time 15:11 Rev Time 3.00
Received By jgomez Date 2001-03-07 Time 18:50 Sent To  
Notes
2001-03-12 00:00:00CHECKLIST:
 1-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -GARAGE DOOR WITH THE MINIMUM DESIGN
 PRESSURES AS CALCULATED BY THE
 ENGINEER OF RECORD.
 -DOUBLE DOORS W/ TRANSOM ABOVE ASSEMBLY
 AS SHOWN ON EXTERIOR FRONT ELEVATION.
 -SLIDING GLASS DOORS (EXPIRED).
 2-CLARIFY WHY SURVEY DOESN'T SHOW THE
 DRIVEWAY. PERMIT FOR DRIVEWAY CANNOT
 BE ISSUED IF IT'S NOT SHOWN.
 3-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS FOR " ROYAL WALL" PANELS
 SHOWING ALL REINFORCING.
 -ENGINEER OF RECORD TO REVIEW THESE
 SHOP DWGS PRIOR TO SUBMITTAL.
 4-ENERGY CALCULATIONS:
 -ENERGY CALCULATIONS NEED TO BE DONE
 ACCORDING TO THE ROYAL WALL SYSTEM.
 SEE ROYAL WALL PANELS FOR INSULATION
 VALUES AND MATERIALS USED.
 5-STORM PANELS:
 -PROVIDE A KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE.
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 -NOTE: ALL THIS INFORMATION MAY BE
 SUBMITTED AT A LATER DATE, BUT UNDER
 A SEPARATE PERMIT.
 6-SOIL TEST REPORT TO HAVE ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES.
 7-PAY ADDITIONAL FEES OF $1241.39 FOR
 LOW BUILDING VALUATION, RADON FEES AND
 WESTERN EXPANSION FEES. PLEASE, PAY
 ATTACHED RECEIPT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By jgomez Date 2001-01-09 Time 17:16 Rev Time 3.00
Received By jgomez Date 2001-01-09 Time 17:16 Sent To  
Notes
2001-01-09 00:00:00CHECKLIST:
 1-SURVEY DOESN'T MATCH PLANS.
 -PLAT NEED TO BE RECORDED IN ORDER TO
 ISSUE ANY PERMITS.
 -UPDATE SURVEY AS REQUIRED WHEN PLAT IS
 RECORDED.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 3-ENGINEER OF RECORD TO PROVIDE ALL HIS
 INFORMATION ON DRAWINGS AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 4-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -ENTRY DOOR WITH SIDELITE ASSEMBLY.
 -DOUBLE DOORS WITH TRANSOM ASSEMBLY.
 -SINGLE HUNG WINDOWS.
 -WINDOW MULLIONS.
 -GLASS BLOCK.
 -SLIDING GLASS DOORS.
 5-SPECIFY SAFETY GLASS AS REQUIRED. SEE
 PLANS AND SECTION 2405.2 SBC 1997.
 6-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS FOR "ROYAL WALL" SYSTEM FOR
 THIS SPECIFIC HOUSE.
 -INCLUDE ALL THE ENGINEER'S INFORMATION
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 7-IF HOUSE IS TO BE LOCATED AT ZERO LOT
 LINE, THEN THE 2" CONCRETE THICKNESS
 OF ROYAL WALL SYSTEM DOESN'T PROVIDE
 ONE HOUR FIRE RATING.
 TABLE 709.2.1.1 OF SBC 1997.
 NOTE: THIS COMMENT WAS ADDRESSED ON
 PREVIOUS REVIEWS WHEN ROYAL WALL
 SYSTEMS WERE USED.
 8-ENERGY CALCULATIONS:
 -CLARIFY IF THIS IS A GENERIC MODEL
 CALLED ABACO. IF SO, THEN, ENERGY
 CALCS NEED TO BE FOR A WORST CASE.
 -COMPLETELY FILL TOP PORTION OF FORM.
 -PROVIDE ORIGINAL SIGNATURES AT BOTTOM
 OF FORM.
 9-STORM PANELS:
 -PROVIDE A KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE (AS PER CITY
 SAMPLE ATTACHED).
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 10-SOIL TEST REPORT:
 -DOCUMENTS SUBMITTED FOR PUBLIC RECORDS
 SHALL HAVE THE ENGINEER'S ORIGINAL
 SIGNATURE. CHAPTER 471 FL. STATUTES.
 -PROVIDE COMPLETE SOIL TEST REPORT AS
 PER TABLE 1804.2.7.3 CITY AMENDMENTS.
 -PROVIDE FOOTING RECOMMENDATIONS.
 11-CONTRACTOR'S CONSTRUCTION VALUE IS
 VERY LOW. PERMIT FEES WILL BE ADJUSTED
 TO A MORE REALISTIC VALUE.
 12-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM:
 -USE CITY FORM (ATTACHED).
 -REVISE MEAN ROOF HEIGHT AND VELOCITY
 PRESSURE AS REQUIRED.
 -FILL IN ENGINEER'S INFORMATION AT
 BOTTOM OF FORM.
 13-SEE ADDITIONAL COMMENTS ON PLANS.
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE TO THE ORIGINALS
 IN ORDER TO EXPEDITE THE REVIEW.
 -FOR QUESTIONS OR CLARIFICATIONS PLEASE
 CALL JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 3 Status F Date 2001-04-19 Cont ID  
Sent By sgraham Date 2001-04-19 Time 14:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-04-19 00:00:00SETBACK OF 12' APPLYS TO PARCEL D-2 ONLY

Review Stop Z ZONING
Rev No 2 Status F Date 2001-03-09 Cont ID  
Sent By sgraham Date 2001-03-09 Time 08:29 Rev Time 0.00
Received By sgraham Date 2001-03-09 Time 08:30 Sent To  
Notes
2001-03-09 00:00:00MUST MEET 20' FRONT SETBACK

Review Stop Z ZONING
Rev No 1 Status F Date 2001-01-10 Cont ID  
Sent By sgraham Date 2000-12-06 Time 15:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-01-10 00:00:00SURVERY & HOUSE NOT THE SAME