Plan Review Details - Permit 00120065
Plan Review Stops For Permit 00120065
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-12-08 Cont ID  
Sent By mcarsill Date 2000-12-08 Time 18:01 Rev Time 0.00
Received By mcarsill Date 2000-12-08 Time 18:01 Sent To  
Notes
2001-01-08 00:00:001) FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 2) SMOKE DETECTOR REQUIRED ABOVE FIRE
 ALARM CONTROL PANEL.
 3) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT THE BUILDING.
 4) FIRE ALARM SYSTEM IS TO BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION.
 5) SMOKE DETECTORS TO BE A MINIMUM OF
 THREE FEET FROM AIR CONDITIONER
 DIFFUSERS.
 6) FIRE ALARM SYSTEM TO BE TESTED WITH
 FIRE RESCUE DEPARTMENT WHEN COMPLETED.
  
 APPROVED PROVISO:
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910