Plan Review Details - Permit 00111379
Plan Review Stops For Permit 00111379
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-12 Cont ID  
Sent By dpalmer Date 2001-03-12 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2001-03-12 Time 18:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-02-28 Cont ID  
Sent By dpalmer Date 2001-02-28 Time 18:28 Rev Time 0.00
Received By dpalmer Date 2001-02-28 Time 18:28 Sent To  
Notes
2001-02-28 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50.OR SUBMIT CLARIFICATION ON
 WATER LINE BEING CPVC.
  
 3)NOTE: THESE WERE NOTES FROM FIRST
 REVIEW.
  
 MISSING ONE SMOKE DETECTOR OUTSIDE
 BEDROOM. PER NFPA-72 2-2.1.1.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-26 Cont ID  
Sent By dpalmer Date 2000-12-26 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2000-12-26 Time 14:49 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. ALL MAINS/PANELS MUST
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9/110-10
  
 2)NOTE: PLEASE SUBMIT CLARIFICATION FOR
 GROUNDING ELECTRODE CONDUCTOE. MUST BE
 SHOWN TO COLD WATER PIPE PER 250-50.
 (IF NOT CPVC.)
  
 PLEASE SUBM,IT THE ABOVE INFORMATIO FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 X
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-15 Cont ID  
Sent By jleech Date 2000-12-15 Time 07:40 Rev Time 0.33
Received By jleech Date 2000-12-15 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 10:09 Rev Time 0.33
Received By kstevens Date 2001-10-11 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-15 Cont ID  
Sent By jleech Date 2000-12-15 Time 07:40 Rev Time 0.33
Received By jleech Date 2000-12-15 Time 07:40 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-05-24 Cont ID  
Sent By jgomez Date 2001-05-22 Time 18:44 Rev Time 1.00
Received By jgomez Date 2001-05-24 Time 10:27 Sent To  
Notes
2001-05-24 00:00:00SUBMITTAL CHECKLIST:
  
 1-PROVIDE CURRENT DADE COUNTY OR SBCCI
 PRODUCT APPROVAL FOR:
 - SLIDING GLASS DOORS FOR THE SIZES
 SHOWN ON PLANS. INFORMATION SUBMITTED
 IS ONLY FOR TESTING OF THAT SPECIFIC
 UNIT. (SEC 1707.4 CITY AMENDMENTS TO
 SBC 1997. SEE ATTACHED COPY).
 NOTE: IN ORDER TO EXPEDITE THE REVIEW
 PROCESS, MAKE SURE THAT PRODUCT
 APPROVAL TO BE SUBMITTED WILL MEET THE
 DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD AND THAT THE
 STRUCTURAL BUCK DETAIL IS ADEQUATE.
 2-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 THIS ITEM WAS REQUESTED ON PROVISO
 DATED 3-5-01 AND IS NOT DONE YET.
 3-ROYAL WALL ENGINEERED DRAWINGS:
 A)ENGINEER NEED TO SIGN, SEAL AND DATE
 EACH SHEET AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES.
 B)ENGINEER NEEDS TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER
 471 OF FLORIDA STATUTES.
 C)ENGINEER OF RECORD FOR THE STRUCTURE
 TO REVIEW ALL ENGINEERED ROYAL WALL
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE.
 D)PROVIDE TWO COPIES OF EVERY DOCUMENT
 SUBMITTED. ONE GOES TO THE FIELD AND
 THE OTHER ONE GOES TO THE PUBLIC
 RECORDS FILE.
 E)ROYAL WALL ENGINEER DIDN'T SIGN, SEAL
 AND DATE DRAWINGS SD1 AND SD2.
  
 NOTES:
 -STAMPED DOCUMENTS ARE THE ONES THAT ARE
 APPROVED. INSERT THEM IN THE FIELD SET.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-04-23 Cont ID  
Sent By jgomez Date 2001-04-23 Time 11:37 Rev Time 0.50
Received By jgomez Date 2001-04-23 Time 11:37 Sent To  
Notes
2001-04-23 00:00:00SUBMITTAL CHECKLIST:
 1-BEFORE INSTALLATION PROVIDE SBCCI OR
 DADE COUNTY PRODUCT APPROVAL FOR:
 -FLAT ROOF SYSTEM TO BE USED.
 -SLIDING GLASS DOORS WITH THE SIZE
 SPECIFIED ON PLANS. (8'-0").
 -ARCHED AND RECTANGULAR WINDOWS WITH
 SIZE SHOWN ON PLANS AND ELEVATIONS.
 2-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 3-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS SHOWING EACH ROYAL WALL PANEL
 AS DESIGNED FOR THIS PARTICULAR HOUSE.
 4-A REVISED SET OF ROYAL WALL DRAWINGS
 WAS SUBMITTED BUT IS NOT CLEAR WHAT
 WAS REVISED. CLARIFY WHAT WAS REVISED
 AND PAY THE CORRESPONDING FEES FOR
 REVISIONS.
  
 NOTES:
 -ONLY TWO SETS OF DRAWINGS AND SUBMITTAL
 ARE REQUIRED (NOT 3).
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-03-05 Cont ID  
Sent By jgomez Date 2001-03-05 Time 13:26 Rev Time 2.50
Received By jgomez Date 2001-03-05 Time 13:26 Sent To  
Notes
2001-03-05 00:00:00APPROVED WITH PROVISO:
  
 1-BEFORE INSTALLATION, PROVIDE PRODUCT
 APPROVAL FOR THE FOLLOWING:
 -FLAT ROOF SYSTEM TO BE USED. WHAT WAS
 SUBMITTED WAS THE SPECS NOT THE ACTUAL
 PRODUCT APPROVAL.
 -SLIDING GLASS DOORS PRODUCT APPROVAL
 IS EXPIRED AND THE DESIGN PRESSURES
 OF THESE DOORS DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD OF THIS HOUSE.
 -ROUND AND FIXED WINDOWS. NOTE: SEE
 SIZES SHOWN ON PLANS TO GET THE RIGHT
 PRODUCT APPROVAL.
 -GARAGE DOOR PRODUCT APPROVAL WITH THE
 DESIGN PRESSURES THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD OF THIS HOUSE.
  
 2-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
  
 3-SOIL TEST REPORT NEEDS TO HAVE
 ENGINEER'S ORIGINAL SIGNATURE AS PER
 CHAPTER 471 OF FL. STATUTES.
  
 4-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS SHOWING EACH PANEL
 REINFORCEMENT AND SPECS.
 SIGNED, SEALED DATED AND WITH THE
 ENGINEER'S INFORMATION AS REQUIRED
 BY CHAPTER 471 OF FL. STATUTES.
  
 5-ENGINEER OF RECORD TO REVISE THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. THE VELOCITY PRESSURE
 AND THE MEAN ROOF HEIGHT DO NOT MATCH.
 SEE TABLE 1606.2A OF SBC 1997.
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By jgomez Date 2001-01-09 Time 15:06 Rev Time 3.00
Received By jgomez Date 2001-01-09 Time 15:06 Sent To  
Notes
2001-01-09 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-NEED DEMUCKING PERMIT. FOLLOW ENGINEER
 RECOMMENDATIONS.
 3-CONSTRUCTION VALUE DECLARED IS VERY
 LOW. PAY ADDITIONAL FEES OF $852.02
 FOR BUILDING VALUE AND RADON FEES.
 4-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -ENTRY DOORS.
 -FLAT ROOF SYSTEM AT BALCONY.
 -SINGLE HUNG WINDOWS.
 -WINDOW MULLIONS.
 -SLIDING GLASS DOORS.
 -ROUND AND FIXED WINDOWS.
 -GARAGE DOOR THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER.
 5-SPECIFY ATTIC ACCESS AT ROOF AREA
 ABOVE DINING ROOM. SEC 2309.6 SBC 1997
 6-SPECIFY SAFETY GLASS AS REQUIRED. SEE
 PLANS AND SECTION 2405.2 SBC 1997.
 7-STORM PANELS:
 -PROVIDE A KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE (AS PER CITY
 SAMPLE ATTACHED).
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 8-SOIL TEST REPORT NEEDS TO HAVE ENG'R
 ORIGINAL SIGNATURE AS PER CHAPTER 471
 OF FLORIDA STATUTES.
 -PROVIDE COMPLETE SOIL TEST REPORT WITH
 DEMUCKING AND FOOTINGS RECOMMENDATIONS
 9-PROVIDE COMPLETE DETAILS AND SPECS FOR
 SCREEN ENCLOSURE IF PART OF THIS
 PERMIT OR A SEPARATE PERMIT WILL BE
 REQUIRED.
 10-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT SECOND FLOOR FRAMING PLAN.
 SECTION 2305.2 SBC 1997.
 11-SEE COMMENTS ON PLANS. INCLUDING
 COMMENTS BY THE OTHER TRADES.
 12-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS AND SPECIFICATIONS FOR THE
 "ROYAL WALL" SYSTEM TO BE USED.
 -INCLUDE ALL ENGINEER'S INFORMATION AS
 REQUESTED BY CHAPTER 471 OF F. S.
 13-ENGINEER OF RECORD FOR THIS HOUSE TO
 PROVIDE ALL HIS INFORMATION REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES.
  
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-03-06 Cont ID  
Sent By sgraham Date 2001-03-06 Time 08:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***