| Plan Review Stops For Permit 00111365 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-10 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-06-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-06-19 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-19 00:00:00 | SHOW SPECIFIC CONNECTION DETAILS OR LOAD | | | TO BE RESISTED FOR THE CEILING FRAMING | | | ON SHEET 3.1 | | | | | | IS THE LOBBY SHOWN ON SHEET 1.4 ON THE | | | FIRST FLOOR? | | | | | | SHOW THE FIRE SPRINKLER DESIGN | | | INFORMATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-29 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-01-29 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2001-01-29 00:00:00 | WHEN STRUCTURAL DESIGN IS DELEGATED, | | | SUCH AS THAT FOR THE SUSPENDED GYP | | | BOARD CEILING ON SHEET 4/A3, THEN THE | | | DESIGNER OF RECORD SHOULD NOTE THE | | | LOCATION, DIRECTION, MAGNITUDE AND | | | NATURE OF THE FORCES TO BE RESISTED. | | | SEE CHAPTER 61G15-32 OF THE FLORIDA | | | ADMINISTRATIVE CODE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-12-20 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | LETTER W/APPLICATION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-14 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-14 |
Time |
17:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-22 |
Time |
21:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-22 |
Time |
21:24 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-14 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-14 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-13 |
Time |
20:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-13 |
Time |
20:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-02 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-02 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-13 |
Time |
22:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-13 |
Time |
22:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE PROVIDE CLARIFICATION | | | FOR BUS AMPS SHOWN AS ???FOR "GCH" | | | | | | 2)NOTE: PLEASE SEE COLOR CODING OF LOCAL | | | AMNEDMENTS OF 277/480 ART215 | | | | | | 3)NOTE: PLEASE SEE 450-13B AND SUBMIT | | | CLARIFICATION ON TRANSFORMER INSTALL- | | | ATION. NOT ALLOWED ABOVE CEILING OVER | | | 50KVA. | | | | | | 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE FIGURED AT 125% LIGHTING | | | AND LARGEST MOTOR. 215-2 | | | | | | 5)NOTE: PLEASE NOTE THAT NO BRANCH | | | CIRCUIT CONDUCTOR SIZES ARE SHOWN ON | | | PANEL SCHEDULES? PLEASE ADJUST. | | | | | | 6)NOTE:PLEASE SEE RISER DIAGRAM NO COND- | | | -UCTOR SIZES AND CONDUIT SIZES FROM | | | PANEL"GCH" TO TRANSFORMER AND TO "GCL" | | | PLEASE SHOW. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-06-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-19 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-22 |
Time |
21:24 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-06-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-21 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-21 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2001-06-21 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) PLEASE INDICATE WHAT OXY NOTED ON | | | PAGE P-2 REFERS TO. | | | 3) PLEASE EXPLAIN NOTES ON THE DRAWINGS | | | "EMERGENCY EXIT SIGN. EMPLOYEES ONLY". | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-25 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-25 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | ON JANUARY 25, 2001, WRITER CALLED THE | | | OFFICE OF DAVID LAWRENCE. MR. LAWRENCE | | | WAS ADVISED THAT NO FIRE SPRINKLER | | | DRAWINGS WERE INCLUDED WITH PLANS. HE | | | ADVISED HE WOULD HAVE THEM BROUGHT OVER | | | TO THE CONSTRUCTION SERVICES OFFICE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-11 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-11 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE INDICATE HOW EXITING IS | | | ACCOMPLISHED FROM THE TENANT SPACE | | | DOORS. WHERE ARE THE STAIRS LOCATED | | | FROM THE SECOND FLOOR. | | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 3) PROVIDE SEPARATE PLANS AND PERMIT | | | FOR FIRE ALARM EQUIPMENT SHOWN ON | | | PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-26 |
Time |
15:12 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-09-20 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | ******************PROVISO*************** | | | | | | | | | CONTAMINANTS FROM STATIONARY LOCAL | | | SOURCES WITHIN THE SPACE SHALL BE | | | CONTROLLED BY COLLECTION AND REMOVAL AS | | | CLOSE TO THE SOURCE AS PRACTICABLE. | | | THIS PERTAINS TO THE "NAIL" OR MANICURE | | | AREA. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-06-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-09 |
Time |
10:55 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-09 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-02-06 |
Time |
15:14 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2001-02-06 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2001-02-06 00:00:00 | PER CONVERSATION W/ ENGINEER OF RECORD | | | 28 PEOPLE IS MAX OCCUPANCY AND REQUIRED | | | QUANTITIY OF OUTSIDE AIR IS SUPPLIED TO | | | 3 OF 5 FAN COIL UNITS AND WILL MIX | | | THROUGH TOTAL SPACE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-21 |
Time |
11:00 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-21 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************DENIED******************* | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89, DEFINE SPACES CLEARLY AS | | | TO USE, (BEAUTY SALONS REQUIRE MORE O/A | | | THAN SOME OTHER OCCUPANCIES.) | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2 | | | 3. NOTE TABLE 1205 1997 SMC REQUIRES ALL | | | CHILLED WATER PIPE IN COPPER TO BE | | | BRAZED, NOT SOLDERED. | | | 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR ALL UNITS SERVING AREAS W/ | | | COMBINED AIR TOTALING 2000 CFM OR MORE | | | OR UNITS W/ LESS THAN 2000 CFM BUT SERV- | | | ING AREAS USED FOR EGRESS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-21 |
Time |
16:28 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-21 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-21 |
Time |
16:27 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-11-21 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-31 |
Time |
12:57 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-31 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2001-10-31 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | MORE INFORMATION REQUIRED. SHOW DETAILS | | | OF HOW CARLISLE CCW-501 WILL BE APPLIED. | | | GIVE DETAILS OF COMPONETS AND HOW THEY | | | ARE MIXED AND WHAT PERCENTAGE OF EACH | | | COMPONENT. | | | PLEASE SUBMIT PRODUCT APPROVAL FOR PLAN | | | REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-10-25 |
Time |
19:22 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-10-25 |
Time |
19:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-09-22 |
Time |
10:13 |
Rev Time |
1.25 |
| Received By |
jleech |
Date |
2001-09-22 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | REVISION DENIED; | | | 1.SANITARY RISER DIAGRAM S-2 NOT SIZED | | | PROPERLY. AT 1/4" PER FOOT MAX. | | | FIXTURE UNITS IS 27. YOU SHOW 31 FU'S. | | | 2.PAGE P-2 URINAL MISS MARKED SHOULD BE | | | P-4 NOT P-7. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 | | | 3.PAGE P-2 DOOR FROM MENS BATHROOM TO | | | MENS LOUNGE MUST SWING OUT NOT IN, | | | MARKED IN RED ON APPROVED DRAWINGS. | | | DRAWINGS APPROVED ON JULY 25,2001. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-07-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-07 |
Time |
06:42 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-07-07 |
Time |
06:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-06-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-06-10 |
Time |
08:09 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-06-10 00:00:00 | PLUMBING PLAN REVIEW"DENIED" | | | (1) SHT 1.2, MEN'S LOCKER RM, ENTERANCE | | | DOOR,SWINGS INTO STALL DOOR,SEC 4.22 | | | (2) SHT 3.4, DETAIL 9,12 RE: GRAB BAR | | | LENGTH,CONFLICTS WITH DETAIL ON SHT 3.8 | | | COMPLY W/FACBC 97 FIG.30 PG.108 | | | (3) SHT P-1, WATER SERVICE, BACK FLOW | | | PREVENTER REQ.SPC 94 SEC 606. | | | (4) SHT P-5 DOMESTIC WATER RISER,PIPE | | | SIZES, NO MORE THAN 2 FIXTURES ON 1/2" | | | COLD WATER, NO MORE THAN 4 FIXTURES ON | | | 1/2' HOT WATER.SPC 94 CNTY. W/AMENDMENTS | | | (5) SHT P-5, PLUMBING SPECIFICATIONS | | | MATRIALS, NOTE (F) AIR CHAMBERS TO BE | | | RECHARGEABLE & ACCESSIBLE. | | | SPC 94 SEC 607.8.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-02-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-02-04 |
Time |
06:55 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-04 00:00:00 | PLUMBING PLAN REVIEWPROVISO | | | (1) SHT P-3 BACK FLOW PREVENTER ON | | | WATER SERVICE. | | | END OF COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-12-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-03 |
Time |
06:13 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1)SHT A4 EMPLOYEE LOUNGE SINK, COMPLY | | | WITH FACBC SEC 4.24.2 MAX HGTH 34" | | | CLEAR FLR SPACE SEC.4.24.530"X 48". | | | (2) SHT A6 SHOWER STALLS MEN/WOMEN, | | | COMPLY W/FACBC 4.21.7 NO CURBS. | | | (3) SHT P3 BACK FLOW PREVENTER ON WATER | | | SERVICE, LOCAL ORDINANCE # 2853-95. | | | END OF COMMENTS CONTACT PAUL SCHMITZ | | | 561-659- 8096 X 8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-06-19 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-06-19 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|