Plan Review Details - Permit 00111365
Plan Review Stops For Permit 00111365
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-07-10 Cont ID  
Sent By hpiskura Date 2001-07-10 Time 12:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-06-19 Cont ID  
Sent By hpiskura Date 2001-06-19 Time 16:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-06-19 00:00:00SHOW SPECIFIC CONNECTION DETAILS OR LOAD
 TO BE RESISTED FOR THE CEILING FRAMING
 ON SHEET 3.1
  
 IS THE LOBBY SHOWN ON SHEET 1.4 ON THE
 FIRST FLOOR?
  
 SHOW THE FIRE SPRINKLER DESIGN
 INFORMATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-29 Cont ID  
Sent By hpiskura Date 2001-01-29 Time 15:21 Rev Time 0.00
Received By hpiskura Date 2001-01-29 Time 14:20 Sent To  
Notes
2001-01-29 00:00:00WHEN STRUCTURAL DESIGN IS DELEGATED,
 SUCH AS THAT FOR THE SUSPENDED GYP
 BOARD CEILING ON SHEET 4/A3, THEN THE
 DESIGNER OF RECORD SHOULD NOTE THE
 LOCATION, DIRECTION, MAGNITUDE AND
 NATURE OF THE FORCES TO BE RESISTED.
 SEE CHAPTER 61G15-32 OF THE FLORIDA
 ADMINISTRATIVE CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-20 Cont ID  
Sent By hpiskura Date 2000-12-20 Time 11:26 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 LETTER W/APPLICATION

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-11-14 Cont ID  
Sent By dpalmer Date 2001-11-14 Time 17:56 Rev Time 0.00
Received By dpalmer Date 2001-11-14 Time 17:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-10-22 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 21:24 Rev Time 0.00
Received By dpalmer Date 2001-10-22 Time 21:24 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-09-14 Cont ID  
Sent By dpalmer Date 2001-09-14 Time 10:19 Rev Time 0.00
Received By dpalmer Date 2001-09-14 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-06-13 Cont ID  
Sent By dpalmer Date 2001-06-13 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2001-06-13 Time 20:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-02 Cont ID  
Sent By dpalmer Date 2001-02-02 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2001-02-02 Time 15:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 22:04 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 22:04 Sent To  
Notes
2001-01-08 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR BUS AMPS SHOWN AS ???FOR "GCH"
  
 2)NOTE: PLEASE SEE COLOR CODING OF LOCAL
 AMNEDMENTS OF 277/480 ART215
  
 3)NOTE: PLEASE SEE 450-13B AND SUBMIT
 CLARIFICATION ON TRANSFORMER INSTALL-
 ATION. NOT ALLOWED ABOVE CEILING OVER
 50KVA.
  
 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE FIGURED AT 125% LIGHTING
 AND LARGEST MOTOR. 215-2
  
 5)NOTE: PLEASE NOTE THAT NO BRANCH
 CIRCUIT CONDUCTOR SIZES ARE SHOWN ON
 PANEL SCHEDULES? PLEASE ADJUST.
  
 6)NOTE:PLEASE SEE RISER DIAGRAM NO COND-
 -UCTOR SIZES AND CONDUIT SIZES FROM
 PANEL"GCH" TO TRANSFORMER AND TO "GCL"
 PLEASE SHOW.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-06-19 Cont ID  
Sent By lsmith Date 2001-06-19 Time 14:47 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-07-24 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 21:24 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-06-21 Cont ID  
Sent By mcarsill Date 2001-06-21 Time 10:25 Rev Time 0.00
Received By mcarsill Date 2001-06-21 Time 10:25 Sent To  
Notes
2001-06-21 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) PLEASE INDICATE WHAT OXY NOTED ON
 PAGE P-2 REFERS TO.
 3) PLEASE EXPLAIN NOTES ON THE DRAWINGS
 "EMERGENCY EXIT SIGN. EMPLOYEES ONLY".
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-02-08 Cont ID  
Sent By mcarsill Date 2001-01-25 Time 13:51 Rev Time 0.00
Received By mcarsill Date 2001-01-25 Time 13:51 Sent To  
Notes
2001-01-25 00:00:00ON JANUARY 25, 2001, WRITER CALLED THE
 OFFICE OF DAVID LAWRENCE. MR. LAWRENCE
 WAS ADVISED THAT NO FIRE SPRINKLER
 DRAWINGS WERE INCLUDED WITH PLANS. HE
 ADVISED HE WOULD HAVE THEM BROUGHT OVER
 TO THE CONSTRUCTION SERVICES OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By mcarsill Date 2000-12-11 Time 09:57 Rev Time 0.00
Received By mcarsill Date 2000-12-11 Time 09:57 Sent To  
Notes
2001-01-08 00:00:001) PLEASE INDICATE HOW EXITING IS
 ACCOMPLISHED FROM THE TENANT SPACE
 DOORS. WHERE ARE THE STAIRS LOCATED
 FROM THE SECOND FLOOR.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 3) PROVIDE SEPARATE PLANS AND PERMIT
 FOR FIRE ALARM EQUIPMENT SHOWN ON
 PLANS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-09-26 Cont ID  
Sent By pkrauss Date 2001-09-26 Time 15:12 Rev Time 1.00
Received By pkrauss Date 2001-09-20 Time 13:01 Sent To  
Notes
2001-09-26 00:00:00******************PROVISO***************
  
  
 CONTAMINANTS FROM STATIONARY LOCAL
 SOURCES WITHIN THE SPACE SHALL BE
 CONTROLLED BY COLLECTION AND REMOVAL AS
 CLOSE TO THE SOURCE AS PRACTICABLE.
 THIS PERTAINS TO THE "NAIL" OR MANICURE
 AREA.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-06-09 Cont ID  
Sent By pkrauss Date 2001-06-09 Time 10:55 Rev Time 0.35
Received By pkrauss Date 2001-06-09 Time 10:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-06 Cont ID  
Sent By ndenmark Date 2001-02-06 Time 15:14 Rev Time 1.00
Received By ndenmark Date 2001-02-06 Time 15:14 Sent To  
Notes
2001-02-06 00:00:00PER CONVERSATION W/ ENGINEER OF RECORD
 28 PEOPLE IS MAX OCCUPANCY AND REQUIRED
 QUANTITIY OF OUTSIDE AIR IS SUPPLIED TO
 3 OF 5 FAN COIL UNITS AND WILL MIX
 THROUGH TOTAL SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-21 Cont ID  
Sent By ndenmark Date 2000-12-21 Time 11:00 Rev Time 0.33
Received By ndenmark Date 2000-12-21 Time 11:00 Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89, DEFINE SPACES CLEARLY AS
 TO USE, (BEAUTY SALONS REQUIRE MORE O/A
 THAN SOME OTHER OCCUPANCIES.)
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2
 3. NOTE TABLE 1205 1997 SMC REQUIRES ALL
 CHILLED WATER PIPE IN COPPER TO BE
 BRAZED, NOT SOLDERED.
 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR ALL UNITS SERVING AREAS W/
 COMBINED AIR TOTALING 2000 CFM OR MORE
 OR UNITS W/ LESS THAN 2000 CFM BUT SERV-
 ING AREAS USED FOR EGRESS.

Review Stop P PLUMBING
Rev No 9 Status P Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 16:28 Rev Time 0.50
Received By kstevens Date 2001-11-21 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 8 Status P Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 16:27 Rev Time 1.00
Received By kstevens Date 2001-11-21 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2001-10-31 Cont ID  
Sent By kstevens Date 2001-10-31 Time 12:57 Rev Time 0.50
Received By kstevens Date 2001-10-31 Time 12:49 Sent To  
Notes
2001-10-31 00:00:00DENIED
 REFERENCE: SPC-94
  
 MORE INFORMATION REQUIRED. SHOW DETAILS
 OF HOW CARLISLE CCW-501 WILL BE APPLIED.
 GIVE DETAILS OF COMPONETS AND HOW THEY
 ARE MIXED AND WHAT PERCENTAGE OF EACH
 COMPONENT.
 PLEASE SUBMIT PRODUCT APPROVAL FOR PLAN
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-10-25 Cont ID  
Sent By jleech Date 2001-10-25 Time 19:22 Rev Time 1.00
Received By jleech Date 2001-10-25 Time 19:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-09-22 Cont ID  
Sent By jleech Date 2001-09-22 Time 10:13 Rev Time 1.25
Received By jleech Date 2001-09-22 Time 10:13 Sent To  
Notes
2001-09-22 00:00:00REVISION DENIED;
 1.SANITARY RISER DIAGRAM S-2 NOT SIZED
 PROPERLY. AT 1/4" PER FOOT MAX.
 FIXTURE UNITS IS 27. YOU SHOW 31 FU'S.
 2.PAGE P-2 URINAL MISS MARKED SHOULD BE
 P-4 NOT P-7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369
 3.PAGE P-2 DOOR FROM MENS BATHROOM TO
 MENS LOUNGE MUST SWING OUT NOT IN,
 MARKED IN RED ON APPROVED DRAWINGS.
 DRAWINGS APPROVED ON JULY 25,2001.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 06:42 Rev Time 1.50
Received By jleech Date 2001-07-07 Time 06:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-06-10 Cont ID  
Sent By pschmitz Date 2001-06-10 Time 08:09 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-10 00:00:00PLUMBING PLAN REVIEW"DENIED"
 (1) SHT 1.2, MEN'S LOCKER RM, ENTERANCE
 DOOR,SWINGS INTO STALL DOOR,SEC 4.22
 (2) SHT 3.4, DETAIL 9,12 RE: GRAB BAR
 LENGTH,CONFLICTS WITH DETAIL ON SHT 3.8
 COMPLY W/FACBC 97 FIG.30 PG.108
 (3) SHT P-1, WATER SERVICE, BACK FLOW
 PREVENTER REQ.SPC 94 SEC 606.
 (4) SHT P-5 DOMESTIC WATER RISER,PIPE
 SIZES, NO MORE THAN 2 FIXTURES ON 1/2"
 COLD WATER, NO MORE THAN 4 FIXTURES ON
 1/2' HOT WATER.SPC 94 CNTY. W/AMENDMENTS
 (5) SHT P-5, PLUMBING SPECIFICATIONS
 MATRIALS, NOTE (F) AIR CHAMBERS TO BE
 RECHARGEABLE & ACCESSIBLE.
 SPC 94 SEC 607.8.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-04 Cont ID  
Sent By pschmitz Date 2001-02-04 Time 06:55 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-04 00:00:00PLUMBING PLAN REVIEWPROVISO
 (1) SHT P-3 BACK FLOW PREVENTER ON
 WATER SERVICE.
 END OF COMMENTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-03 Cont ID  
Sent By pschmitz Date 2000-12-03 Time 06:13 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWDENIED
 (1)SHT A4 EMPLOYEE LOUNGE SINK, COMPLY
 WITH FACBC SEC 4.24.2 MAX HGTH 34"
 CLEAR FLR SPACE SEC.4.24.530"X 48".
 (2) SHT A6 SHOWER STALLS MEN/WOMEN,
 COMPLY W/FACBC 4.21.7 NO CURBS.
 (3) SHT P3 BACK FLOW PREVENTER ON WATER
 SERVICE, LOCAL ORDINANCE # 2853-95.
 END OF COMMENTS CONTACT PAUL SCHMITZ
 561-659- 8096 X 8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-19 Cont ID  
Sent By lsmith Date 2001-06-19 Time 14:47 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***