Plan Review Details - Permit 00111341
| Plan Review Stops For Permit 00111341 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-03 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2001-01-03 |
Time |
10:50 |
Rev Time |
4.00 |
| Received By |
fknapp |
Date |
2001-01-03 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | *************BUILDING UNSAT************* | | | | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVALS | | | FOR ALL EXTERIOR SWING DOORS TO BE USED | | | WITH APPROVED DRAWINGS. | | | | | | 2)PROVIDE SAFETY GLASS AS REQ PER 1997 | | | SBC 2405.2.1 (3) | | | | | | 3)PROVIDE TRUSS ENGINEERING SHEETS WITH | | | LAYOUT PLAN APPROVED BY DESIGNER OF | | | RECORD. | | | | | | 4)PROVIDE ENGINEERING FOR ALL BUTT GLASS | | | OPENINGS. | | | | | | 5)PROVIDE DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE. | | | | | | 6)NOTES ON SHEET A-1 REFERENCE ASCE 7-93 | | | (NOT CURRENT) AND UPLIFT CALCULATIONS | | | REFERENCES SBC SEC. 1606.2., MIXING | | | PROVISIONS FROM ASCE 7 AND 1606.2 SHALL | | | NOT BE PERMITTED 1997 SBC 1606.1.2.1. | | | | | | 7)PROVIDE DESIGN PRESSURES ON PLANS FOR | | | ALL EXTERIOR OPENINGS. | | | | | | ANY QUESTIONS,PLEASE CALL | | | FRANK KNAPP | | | BUILDING PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-04-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-09 |
Time |
20:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-09 |
Time |
20:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-02-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-27 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-27 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2001-02-27 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | WERE ADDRESSED FROM FIRST AND SECOND | | | REVIEWS???? | | | | | | PLEASE SUBMIT REVISED/CORRECTED PLANS | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-17 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-17 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | ******************UNSAT **************** | | | | | | 1)NOTE: NOTES FROM FIRST REVIEW WERE NOT | | | ADDRESSED. PLEASE REVIEW NOTES AND CALL | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-13 |
Time |
20:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-13 |
Time |
20:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM. MAIN | | | SHOWS 2P250A FEEDING PANEL INSIDE WITH | | | 1/0 CONDUCTORS. PLEASE ADJUST TO NEC. | | | | | | 2)NOTE: PLEASE NOTE AS PER 309.1 A WP | | | GFI RECEPT IS REQ`D FOR A/C COND UNITS. | | | | | | 3)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN DISC TO | | | PANEL. SIZE PER 250-122 | | | | | | 4)NOTE: PLEASE SEE PLANS. PLANS DON'T | | | SHOW MAIN NEXT TO METERCAN?? PLEASE | | | SHOW LOCATION ON PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-05 |
Time |
18:34 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-12-05 |
Time |
18:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-05 |
Time |
18:34 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-12-05 |
Time |
18:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-01-03 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2001-01-03 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLAN REVIEW ONLY |
|
|
|