Plan Review Details - Permit 00111288
Plan Review Stops For Permit 00111288
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By mcarsill Date 2001-01-17 Time 11:39 Rev Time 0.00
Received By mcarsill Date 2001-01-17 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By mcarsill Date 2000-11-30 Time 12:47 Rev Time 0.00
Received By mcarsill Date 2000-11-30 Time 12:47 Sent To  
Notes
2001-01-08 00:00:001) FIRE HYDRANT LOCATIONS NOT SHOWN IN
 RELATIONSHIP TO FIRE DEPARTMENT
 CONNECTION. A FIRE HYDRANT IS TO BE NO
 FARTHER THAN 150 FEET FROM THE
 DEPARTMENT CONNECTION.
 2) NO CUT SHEETS PROVIDED ON FIRE
 SPRINKLER HEADS OR PIPING PLANNED FOR
 USE.
 3) PROVIDE MORE DETAILS ON FIRE HOSE
 CABINETS LOCATED IN WAREHOUSE AREA.
 4) ENTIRE BUILDING TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL MECHANICAL, ELECTRICAL AND STORAGE
 ROOMS. ALL VERTICAL SHAFTS ARE ALSO
 REQUIRED TO BE FIRE SPRINKLER PROTECTED.
 5) PLEASE PROVIDE DETAILS ON STORAGE
 RACKS PLANNED FOR USE. WHAT MATERIALS
 ARE THEY MADE OF.
 6) PLEASE PROVIDE FIRE HYDRANT
 INFORMATION ON BUILDING KEY PLAN.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910
  
 CALLED WIGINTON FIRE SPRINKLER TO PICK
 UP PLANS ON 11-30-00