Plan Review Details - Permit 00111283
Plan Review Stops For Permit 00111283
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-12-08 Cont ID  
Sent By lmartine Date 2000-12-08 Time 17:07 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-12-05 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2001-12-05 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-27 Cont ID  
Sent By dpalmer Date 2001-11-27 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2001-11-27 Time 12:05 Sent To  
Notes
2001-11-27 00:00:00******************* UNSAT **************
  
 PLEASE NOTE, AS PER CONVERSATION WITH
 THE COMPANIES ENGINEER. THE FOLLOWING
 ITMES ARE TO BE CORRECTED.
  
 1)NOTE: PLEASE NOTE THAT EXISTING HSA
 MAIN 1OF2 IS SHOWN AS 1000A`S.
 THIS IS 400A PER CONVERSATION.
 THIS IS SHOWN AT MORETHAN ONE LOCATION
 ON PLAN.
  
 2)NOTE: PLEASE ALSO NOTE THAT PLANS SHOW
 3-SETS OF 4" CONDUITS WITH 4-400MCM`S
 IN EACH. PLEASE CLARIFY FOR ONLY 400A
 SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-31 Cont ID  
Sent By dpalmer Date 2001-01-31 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2001-01-31 Time 18:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 15:32 Sent To  
Notes
2001-01-09 00:00:00***************** UNSAT ****************
  
  
 1)NOTE: PLEASE PROVIDE MEANS OD
 DISCONNECT FOR SERVICE INLINE TO ATS.
  
 2)NOTE: PLEASE CLARIFY # OF CONDUCTORS.
  
 3)NOTE: PLEASE PROVIDE NOC AND CORRECT
 JOB VALUE FOR ENTIRE SCOPE OF WORK.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-02 Cont ID  
Sent By mcarsill Date 2001-02-02 Time 14:23 Rev Time 0.00
Received By mcarsill Date 2001-02-02 Time 14:23 Sent To  
Notes
2001-02-02 00:00:001) PLEASE PROVIDE BARRIER PROTECTION
 FROM VEHICULAR TRAFFIC IN PAVED
 PARKING AREA.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-12-14 Cont ID  
Sent By mcarsill Date 2000-12-14 Time 15:17 Rev Time 0.00
Received By mcarsill Date 2000-12-14 Time 15:17 Sent To  
Notes
2001-01-08 00:00:001) PLEASE INDICATE LOCATION OF PROPERTY
 LINES, STORM DRAINS, RIGHT OF WAYS, ETC.
 2) PLEASE INDICATE DISTANCE BETWEEN
 GENERATOR AND SUB BASE TANK TO
 COMMUNITY DRIVE.
 3) THE PLAN INDICATES A 750 GALLON
 SUB-BASE FUEL TANK BUT THE LITERATURE
 INDICATES THAT 2000 GALLON CAPACITIES
 ARE AVAILABLE. CLEARLY SPECIFY THE
 AMOUNT PLANNED FOR USE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop Z ZONING
Rev No 1 Status N Date 2001-02-05 Cont ID  
Sent By lsmith Date 2001-02-05 Time 07:28 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***