| Plan Review Stops For Permit 00111179 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-08-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-31 |
Time |
07:28 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-08-31 |
Time |
07:27 |
Sent To |
|
|
| Notes |
| 2001-08-31 00:00:00 | REVISION SUBMITTED8/7/01 OK JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-30 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-08-20 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2001-07-30 00:00:00 | BUILDING PLAN REVIEW | | | 00111179 | | | 2308 N DIXIE | | | | | | 1)- FL AESSIBILITY CODE 4.4.3.8 | | | CHANGE IN GRADE, FRONT AND SIDE ENTRY SH | | | OW A STOOP, A RAMP OR OTHER OF VERTICAL | | | ACCESSIBILITY WILL BE REQUIRED. | | | | | | JIM WITMER | | | (561) 659-8096X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-03-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-20 |
Time |
11:35 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-03-20 00:00:00 | BUILDING: | | | 1)- FL ACCESSIBLITY CODE 4.4.3.8 CHANGE | | | IN GRADE, FRONT AND SIDE ENTRY SHOWS A | | | STOOP, A RAMP OR OTHER FORM OF VERTICAL | | | ACCESSIBILITY WILL BE REQUIRED. | | | | | | 2)- BACKING BEHIND THE WATER CLOSETS | | | WHERE THERE IS NO SIDE WALL FOR GRAB | | | RAIL SUPPORT, SEE DETAIL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-06 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-11-29 |
Time |
07:22 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEED PRODUCT APPROVALS: DOORS ON PLANS | | | NOT ON PERMIT APP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
tjonseck |
Date |
2001-10-25 |
Time |
15:40 |
Rev Time |
0.25 |
| Received By |
tjonseck |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | SEPERATE PERMIT FOR ELECTRICAL SEE | | | PERMIT # 01070172 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-03-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-12 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-12 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2001-03-12 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE ELECTRICAL PLANS | | | NEED TO BE SUBMITTED WITH AN ELECTRICAL | | | PERMIT APPLICATION. PLEASE NOTE PLANS | | | AHVE NEVER HAD AN ELECTRICAL REVIEW. | | | PERMIT IS A MISC PERMIT. VALUE OF WORK | | | NEEDS TO BE INCREASED. ORIG VALUE AT | | | $6500?? | | | | | | 2)NOTE: PLEASE NOTE THAT YOU ARE SHOWING | | | PANELS FEEDING MORETHAN ONE TENANT | | | SPACE?. | | | THIS IS NOT PERMITTED. PLEASE CLARIFY. | | | | | | NEEDS TO REVIEW BY ZONING FOR USE SHOWN. | | | | | | PLEASE SUBMIT ALL THE INFORMATION NEEDED | | | AND SUBMIT FOR APPROPIATE PERMITS AND | | | UP VALUE OF EXISTING . | | | | | | PLEASE SUBMIT THE ABOVE. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-20 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-20 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | 1) EXIT SIGNS AND EMERGENCY LIGHTING | | | REQUIRED. | | | 2) ELECTRIC POWERED SMOKE DETECTORS | | | REQUIRED IN EACH SLEEPING ROOM. WHEN | | | ACTIVATED, THESE DEVICES ARE TO BE | | | AUDIBLE IN THE SLEEPING ROOMS OF THAT | | | UNIT. | | | 3) TENANT SEPARATIONS TO COMPLY WITH | | | BUILDING CODE REQUIREMENTS. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-25 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-25 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2001-07-25 00:00:00 | 1) ELECTRIC POWERED SMOKE DETECTORS | | | REQUIRED IN EACH APARTMENT. WHEN | | | ACTIVATED THESE DETECTORS ARE TO BE | | | AUDIBLE THROUGHOUT THE UNIT. | | | 2) WALLS ARE TO BE 1/2 HOUR FIRE | | | RESISTIVE AND HAVE AT LEAST 20 MINUTE | | | FIRE DOORS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-03-13 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-03-13 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) PLANS INDICATE ONE HOUR RATED FIRE | | | DOORS. DOOR CLOSERS AND FRAMES HAVE | | | NOT BEEN MENTIONED ON THE PLANS. | | | 3) HOW ARE THE DRYERS VENTED. | | | 4) WHAT FLOOR OF THE BUILDING IS THE | | | WORK TAKING PLACE ONE. | | | 5) ARE THERE ANY FIRE ALARM DEVICES | | | IN THE AREA. | | | 6) NO INTERIOR FINISH INFORMATION WITH | | | PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
tjonseck |
Date |
2001-10-25 |
Time |
15:42 |
Rev Time |
0.25 |
| Received By |
tjonseck |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | SEPERATE PLUMB PERMIT SEE PERMIT | | | #01070017 DR |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-03-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-14 |
Time |
16:58 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-03-14 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2001-03-14 00:00:00 | DENIED; | | | | | | NOT ENOUGH INFORMATION. WHAT IS THE | | | EXTENT OF PLUMBING WORK? WHAT FLOOR IS | | | BEING REMODELED? IF ANY PLUMBING DEMO | | | WORK IS TO BE DONE PLUMBING PERMITS ARE | | | REQUIRED. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|