| Plan Review Stops For Permit 00111091 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2001-12-19 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2001-12-19 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2001-12-10 |
Time |
11:51 |
Rev Time |
2.00 |
| Received By |
rbrown |
Date |
2001-12-10 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | THE FOLLOWING COMMENT IS NUMBERED AS PER | | | THE 11/26/01 BUILDING PLAN REVIEW: | | | | | | 3) STRUCTURAL CALCULATIONS.COMMENT NOT | | | ADDRESSED.SUBMIT CALCULATIONS FOR THE | | | REVISED LOAD PATHS DUE TO THE ROOF | | | RE-CONFIGURATION AND REVISED COLUMN | | | ARRANGEMENT. | | | ---------------------------------------- | | | | | | PROVISO: | | | | | | WINDOW PRODUCT APPROVAL.THE LARGE | | | ARCHED WINDOW ON THE WEST ELEVATION OF | | | THE VESTIBULE IS LARGER THAN THE PRODUCT | | | APPROVAL DIMENSIONS FOR LARGE MISSILE | | | IMPACT WINDOWS (SEE PGT INDUSTRIES | | | DRAWING NO.4231, SHEET 3).EITHER | | | SHUTTERS MUST BE PROVIDED OR A RELEVANT | | | PRODUCT APPROVAL SUBMITTED. | | | | | | | | | END OF REVIEW COMMENTS | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2001-11-26 |
Time |
11:17 |
Rev Time |
2.00 |
| Received By |
rbrown |
Date |
2001-11-26 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | ADDITIONAL NOTES | | | NOTES ON SUBMITTALS SINCE PLAN REVIEW | | | NUMBERED AS PER ORIGINAL COMMENTS: | | | | | | 7) PRODUCT APPROVALS.THE SUBMITTED | | | WINDOW/DOOR ASSEMBLY PRODUCT APPROVALS | | | STATE THAT THEY ARE FOR "SINGLE UNIT | | | APPLICATIONS ONLY".AS THEY DO NOT | | | CORRELATE TO THE PROPOSED ARCHED | | | WINDOWS, FURTHER PRODUCT APPROVALS ARE | | | REQUIRED TO COVER THE GLAZED OVER-PANELS | | | AND ASSOCIATED MULLIONS. | | 2001-11-26 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE | | | SBC* = STANDARD BUILDING CODE AMENDMENTS | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | FL ENERGY = FLORIDA ENERGY EFFICIENCY | | | CODE FOR BUILDING COSTRUCTION | | | | | | | | | 1) CONFIRM THAT SITE PLAN IS UNCHANGED | | | TO VERIFY ADEQUATE HORIZONTAL SEPARATION | | | | | | 2) FL ENERGY 103.3 - SUBMIT ENERGY CODE | | | COMPLIANCE CALCULATIONS. | | | | | | 3) ROOF RE-CONFIGURED AND COLUMNS | | | REVISED.SUBMIT STRUCTURAL | | | CALCULATIONS FOR REVISED LOAD PATHS. | | | | | | 4) COLUMN ON FOOTING F-3 IS SHOWN AS | | | 4"X4"X1/2" ON FOUNDATION PLAN, | | | 5"X5"X1/4" ON COLUMN SCHEDULE AND | | | 6"X6"X1/2" ON ROOF FRAMING PLAN. | | | CLARIFICATION REQUIRED. | | | | | | 5) FOUNDATION PLAN, SLAB SECTION A-A: | | | EXPANSION JOINT REQUIRED. | | | | | | 6) FL ACC CODE 4.13.6 - MINIMUM | | | MANEUVERING CLEARANCES HAVE NOT | | | BEEN PROVIDED AT THE DOORS TO MALE | | | TOILET, FEMALE TOILET OR SUPPLY ROOM | | | (ROOM 06). REVISION REQUIRED. | | | | | | 7) WINDOWS HAVE BEEN CHANGED TO ARCHED | | | WINDOWS.SUBMIT PRODUCT APPROVALS TO | | | INCLUDE THE GLAZED OVER-PANELS AND | | | ADDITIONAL MULLIONS | | | | | | 8) SBC 2405.2 - THE GLAZING IN THE | | | WINDOW ADJACENT THE EXIT DOOR FROM THE | | | STAFF LOUNGE REQUIRES TEMPERED GLASS. | | | SHUTTERS ARE REQUIRED FOR LARGE MISSILE | | | IMPACT PROTECTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-12 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-27 |
Time |
15:46 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW | | | 1): FRONT ENTRY / VESTIBULE 6" CHANGE IN | | | GRADE. FL. ACCESSIBILITY CODE 4.3.2 | | | THERE WILL BE AT LEAST ONE ACCESSIBLE | | | ROUTEPROVIDED FROM PUBLIC TRANSPORTA- | | | TION STOPS, ACCESSIBLE PARKING, LOADING | | | ZONES AND TO THE ACCESSIBLE BUILDING | | | ENTRRANCE THEY SERVE. | | | 2).W P B ADMIN.CODE 104.2.2/1606SBC | | | SPECIFIC WINDOW AND DOOR BUCK DETAILS. | | | 3).S.B.C. 1606.2.6.2 COMPONENTS & CLADD- | | | ING.PRODUCT APPROVAL REPORTS FOR WINDOWS | | | EXT DOORS,GLASS BLOCK & ROOFING MATERIAL | | | 4).SBC 1606.4.1/ 1707.4.1 STORM SHUTTERS | | | REQUIRED FOR GLAZED OPENINGS NOT PASSING | | | LARGE MISSLE IMPACT TESTING, A SBCCI OR | | | DADE COUNTY REPORT REQUIRED. A SCHEDULE | | | AND KEY INSTALLATION PLAN WILL BE | | | REQUIRED, SEE ATTACHED POLICY. | | | 5). 104.2.2 ADD INFO REQUIRED ON THE | | | STRUCTURAL MEMBER THAT WILL BE BETWEEN | | | THE ARCHED WINDOWS AND WITHER WINDOWS | | | BELOW. ATTACHMENT OF WINDOWS AND ATTACH- | | | MENT TO THE BLOCK OR COLUMNS. | | | 6). 104.22 ADD INFO REQUIRED, WINDOWS | | | WITH RADIUS HEADS HOW WILL THE INFILL | | | OCCUR WHEN USING DETAIL WINDOW A-A? | | | 7).ENERGY CALCULATIONS | | | 8).SOILS TEST REPORT 1804.2 GIVING | | | BEARING VALUE. | | | 9). F102.2.4 (FIRE ZONE) FIRE RESISTANT | | | ROOF COVERINGS CLASS A OR B AS DEFINED | | | IN 1503.2. | | | 10).ARCH DETAILS PAGE A-6 (FIRE ZONE) | | | ARCH TRIM-APPROVED NON COMBUSTIBLE | | | MATERIAL OR FIRE RESISTANT TREATED WOOD. | | | 11). THESE SAME DETAILS WILL REQUIRE ADD | | | INFO, THE BOTTOM DETAIL DOESN'T GIVE ANY | | | FASTENING TO THE TOP PLATE OR LEDGER. | | | THE UPPER DETAIL ALSO DOESN,T GIVE HOW | | | TO ATTACH THE TOP LEDGER OR HOW THE LOOK | | | OUTS ARE TO FASTENED TO THE LEDGERS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 | | | | | | PLEASE RETURN THE REVIEWED PAGES AFTER | | | THE CORRECTIONS ARE COMPLETED, THIS WILL | | | EXPEDITE THE REVIEW PROCESS,IF YOU HAVE | | | ANY QUESTIONS PLEASE CALL, THANK YOU. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2002-09-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-13 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-07-01 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-11 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-11 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2002-06-11 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT "EQUIPMENT | | | GROUNDING" CONDUCTORS ARE STILL BEING | | | SHOWN BETWEEN METER AND GUTTER AND | | | BETWEEN GUTTER AND MAIN DISC`S. THIS WAS | | | REDLINED A YEAR AGO. PLEASE NOTE THAT | | | THIS PARALELLING THE NEUTRAL. PLEASE SEE | | | 250-24 | | | | | | 2)NOTE: PLEASE NOTE THAT THERE ARE NO | | | REVISIONS INDICATED BY EITHER CLOUDS OR | | | TRIANLGES? NO DATES FO ANY REVISIONS | | | ARE SHOWN IN THE UPPER RIGHT HAND CORNER | | | ?? PLEASE SHOW BY CLOUDS OR TRIANGLES. | | | NO INDICATIONS IF PLANS WERE COMPLETELY | | | REDRAWN. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW, IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-06 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-13 |
Time |
21:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-03-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-06 |
Time |
20:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-06 |
Time |
20:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-25 |
Time |
23:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-25 |
Time |
23:01 |
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLANS ARE SIGNED AND SEALED, | | | ALL CHANGES SUBMITTED ARE REQ`D TO BE | | | SIGNED AND SEALED ALSO. PER F.A.C. SEC | | | 481.221. | | | PLEASE MAKE NOTES ON PLANS ALREADY DONE | | | AND HAVE ARCH/ENGINEER INITIALED AT | | | LOCATION OF NOTES AND/OR CHANGES. | | | | | | PLEASE SUBMIT THE SUBMITTED AND ABOVE | | | INFORMATION FOR REVIEW. IF THIS IS DONE | | | WHEN SUBMITTD FOR PERMIT THEN ELECTRICAL | | | REVIEW WILL BE SIGNED OFF. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-14 |
Time |
19:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-14 |
Time |
19:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM. AN | | | EQUIPMENT GROUNDING CONDUCTOR IS SHOWN | | | IN RISER AND FROM METERCAN TO FIRST | | | MEANS OF DISCONNECT. PLEASE NOTE PER 250 | | | OF THE NEC ONLY AFTER FIRST MEANS. | | | | | | 2)NOTE: PLEASE SEE E-4. THIS SHOWS AIC | | | RATINGS FOR ALL PANELS BUT NOTHING FOR | | | MAINS? PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT. PER 110-9 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2002-09-16 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-09-16 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2002-09-16 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2002-09-13 00:00:00 | PASSED WITH PROVISOS: | | | 1. UPON COMPLETION OF THE CIVIL/SITE | | | WORKS AND INSTALLTION OF THE ALTERNATE | | | DRAINAGE SYSTEMS, A CERTIFICATION BY THE | | | CIVIL ENGINEER OF RECORD MUST BE | | | SUBMITTED TO THE CONSTRUCTION SERVICES | | | DEPARTMENT ATT: MOHAMMAD R. AMINI. | | | THE CERTIFICATION MUST STATE THAT THE | | | DRAINAGE SYSTEM IS CONSTRUCTED PER | | | PROPOSED ALTERNATE PLAN AND IS OPERATING | | | AS DESIGNED AND COMPLY WITH THE CITY | | | REQUIREMENTS. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-02-12 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-02-12 |
Time |
14:06 |
Rev Time |
1.50 |
| Received By |
mamini |
Date |
2001-02-12 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2001-02-12 00:00:00 | PASSED WITH PROVISOS: | | | 1. PLEASE REFER TO PREVIOUSE ENGINEERING | | | REVIEW COMMENTS AND COMPLY. | | | 2. BACKFLOW PREVENTTES ARE REQUIRED AT | | | CONNECTIONS TO WATER MAIN. | | | IF ANY QUESTION PLEASE CONTACT 659 80 | | | 96 EXT. 8492 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-01-04 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2001-01-04 |
Time |
15:43 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FAILED | | | MUST COMPLY WITH THE FOLLOWING DEMANDS | | | 1. PLEASE SHOW EXISTING WM ALONG 3' | | | UTILITY EASEMENT AND SHOW NEW IRRIGATION | | | METER SERVICE CONNECTION. | | | 2. IT IS RECOMENDED THAT NEW IRRIGATION | | | SERVICE BE MADE ON THE WATERMAIN OFF SUN | | | SET ROADAND DIXIE. | | | 3. DRIVEWAY ENTRANCES DO NOT COMPLY WITH | | | CITY DRIVEWAY APPROACH STANDARDS | | | EMAIL [email protected] | | | FOR STANDARD DETAIL. | | | 4. CALL OUT SIZE OF METER AND SIZE OF SE | | | RVICE. WE ALLOW ONLY 1" OR 2" TYPE K | | | COPPER. | | | 5. PROVIDE CITY OF WPB | | | PUBLIC UTILITY DEPT. WITH A MINIMUM OF 2 | | | SETS OF PLANS FOR THEIR FILES. | | | 6. DRAINAGE CALCULATIONS SHALL BE SUBMIT | | | TED TO JOSE DEL RIOS OF THE STORM WATER | | | DIVISION FORAPPROVAL. | | | 7. NO LARGE STREES SHALL BE PLANTED IN | | | UTILITY EASEMENT | | | 8. PROVIDE OR CALL OUT HANDICAP RAMP FOR | | | PARKING | | | TOTAL SITE SF IS 19175OK | | | TOTAL IMPERVIOUS SF IS 16154OK | | | TOTAL PERVIOUS SF IS 3021OK | | | 9. PROVIDE STANDARD UTILITY DETAILS | | | THAT APPLY. YOU MAY REQUEST THESE VIA | | | EMAIL TO THE SAME EMAIL AS ABOVE | | | 10. A DESIGNATED PLAN SHOULD BE TITLED | | | POLLUTION CONTROL PLAN AND SHALL SHOW | | | A SILT FENCE ALONG THE PROPERTY LINE | | | OF THE SITE. PLEASE PROVIDE A SILT | | | FENCE DETAIL OR CUT SECTION. | | | 11. ALL LARGE TREES MUST BE ATLEAST 5' | | | AWAY FROM EXISTING WM'S | | | 12. TO LOCATE EXISTING WM YOU MAY CONTAC | | | T OUR UTILITY LOCATING DEPT. AT | | | 659 8079. | | | | | | IF ANY QUESTION PLEASE FEEL | | | FREE TO CONTACT ME AT | | | 561 659 8040 | | | PUBLIC UTILITIES ENGINEERING SERVICES | | | 1000 45TH STREET SUITE 15 | | | WPB, FL 33407 | | | FAX 561 659 8039 | | | | | | HAVE A GREAT DAY!! |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-14 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-14 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-01-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-23 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-23 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-30 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-30 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT NOTED ON | | | ELEVATION DRAWINGS. ADDRESS TO BE | | | INSTALLED ON BUILDING IN ACCORDANCE WITH | | | CITY CODE REQUIREMENTS. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION. SINCE THERE ARE NO FIRE | | | SPRINKLERS ARE PLANNED, INTERIOR FINISH | | | IN EXITS SHALL BE CLASS A OR B. OFFICE | | | AREAS CAN BE CLASS A, B, OR C. | | | 3) PLEASE INDICATE ON THE PLANS WHERE | | | THE FIRE EXTINGUISHERS WILL BE | | | LOCATED. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-06 |
Time |
13:08 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-06 |
Time |
12:06 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-02 |
Time |
15:18 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-01-02 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-12-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-26 |
Time |
08:12 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
2000-12-26 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.MOP SINK CLOSET TO HAVE EXHAUST FAN | | | PER 1997 SMC 501.4 | | | 2. DUCT DETECTOR TO BE TIED TO BLDG FIRE | | | ALARM OR HORN AND STROBE FOR NOTIFICATIO | | | PER 1996 NFPA 90A | | | 3. MEDICAL GAS SYSTEMS REQUIRE SEPARATE | | | PERMIT. SUBMIT PLANS AT TIME OF MECHANI- | | | CAL PERMIT APPLICATION FOR THIS WORK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-02 |
Time |
13:39 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-01-02 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | PASSED/PROVISO | | | | | | 1) SHUT OFF VALVE TO BE WITH-IN 3' OF | | | W/HEATER, AND RELIEF LINE SHALL NOT BE | | | TRAPPED. | | | | | | 2) SEPARATE PERMIT REQUIRED FOR MED-GAS. | | | COPY OF CERTIFICATION FOR INSTALLATION | | | REQUIRED AT TIME OF PERMITTING. | | | KSTEVENS - FOR P.E.S. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2001-12-09 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-12-09 |
Time |
09:17 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-09 00:00:00 | PLUMBING PLAN REVIEW,MEDICAL GAS DENIED | | | 2ND TIME,PREVIOUS COMMENTS NOT ADDRESS. | | | PROVIDE A RESPONSE SHEET ADDRESSING EACH | | | COMMENT. SPC94,SEC 104.3 PLANS & SPECS. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2001-12-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-08 |
Time |
07:06 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-12-08 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2001-12-08 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P-5 WATER HEATER DETAIL. WATER | | | HEATER CAN NOT INTERFERE WITH NORMAL | | | USE OF MOP SINK. | | | 2) SHT P-3 INTERGAL BACKFLOW PREVENTER | | | ARE NOT APPROVED. PLEASE PROVIDE BACK- | | | FLOW FOR ALL DENTAL EQUIPMENT AND PRO- | | | CESSOR. | | | 3) SHT'S P-1, P-2, & P-3, NO DETAIL FOR | | | WATER FEATURE SHOWN AS REQUESTED IN PRE- | | | VIOUS REVIEWS. | | | 4) SHT P-3, IF AIR CHAMBERS ARE TO BE | | | USED, SHOW DETAIL AS PER WH-PDI 201. | | | SEE ATTACHED SHEET FOR REFERENCE. | | | 5) SHT P-5, AS REQUESTED IN PREVIOUS RE- | | | VIEW, AIR GAP FOR PROCESSOR DRAIN NOT | | | APPROVED. PLEASE SEE ATTACHED SHEET FOR | | | APPROVED AIR GAP FITTING FOR THIS APPLI- | | | CATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-11-21 |
Time |
09:29 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | PLUMBING PLAN REVIEW,MEDICAL GAS DENIED. | | | SHT P-2,4 COMPLY WITH NFPA-99C LEVEL 3 | | | DENTAL OFFICE,SEC 4-5.1.1.3, COMPRESSED | | | AIR, SEE FIG 4-5.1.1.3 | | | PIPED VACUM SYSTEMS, LEVEL 3,SEC 4-5.2, | | | SEE FIG 4-5.2.1 | | | DESIGN SYSTEM PER ABOVE. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-13 |
Time |
08:55 |
Rev Time |
3.00 |
| Received By |
kstevens |
Date |
2001-11-13 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) WATER HEATER TO HAVE PERMINATE SHIPS | | | LADDER AND A WORKING PLATFORM MINIMUM | | | DEMENSIONS 30"X30" TO MAKE WATER HEATER | | | READILY ACCESSIBLE PER SPC SEC 501.7. | | | 2) BACKFLOW REQUIRED FOR PROCESSOR | | | 3) PAGE P1, PLEASE SUBMIT DETAILS FOR | | | WATER FEATURE. AND SHOW HOW POTABLE | | | WATER WILL BE PROTECTED. | | | 4) PAGE P1, PAGE P5, VACUUMN DETAIL. VAC | | | PUMP TO BE DIRECTLY CONNECTED TO SANT. | | | SYSTEM. SEC 4-5.2.1.3 & 4-5.2.1.4 | | | 5) PAGE P1, NO WATER SUPPLY SHOWN TO | | | DRINKING FOUNTAIN. | | | 6) PAGES P1, P3 & P5, WATER FILTER SHALL | | | COMPLY WITH NSF STANDARDS. PLEASE SUBMIT | | | MANUFACTURE INFORMATION TO SHOW FILTER | | | COMPLIES WITH STANDARD. | | | 7) PAGES P1 & P3, BACKFLOW REQUIRED ON | | | WATER SERVICE AND ALL DENTAL EQUIPMENT. | | | 8)PAGE P3, NOTES #1, & #2 TO READ SPC- | | | 94 NOT SPC-97. | | | 9)PAGE P3, AIR CHAMBERS ARE A "QUICK | | | FIX" AND REQUIRE ACCESS PANELS. THEY | | | ALSO SHALL BE RECHARGEABLE PER SPC-94 | | | SEC 607.8.3. WATER HAMMER ARRESTORS | | | SHOULD BE USED AND SIZED AND LOCATED PER | | | MANUFACTURE INSTRUCTION AND PDI-WH 201, | | | CLOSE TO FIXTURES NOT AT TOP OF DROP AS | | | SHOWN ON RISER DIAGRAM. | | | 10) PAGE P3, NO WATER SHOWN TO WATER | | | FEATURE ON RISER DIAGRAM. | | | 11) PAGE P5, AIR GAP FOR PROCESSOR DRAIN | | | NOT APPROVED. PLEASE SEE ATTACHED SHEET | | | FOR APPROVED AIR GAP FITTING FOR THIS | | | APPLICATION. | | | 12) PAGES P1 & P2, DRINKING FOUTAIN. | | | PLEASE PROVIDE PROVISIONS FOR THOSE WHO | | | HAVE DIFFICULTY BENDING OR STOOPING. | | | SHOW HOW D.F. WILL COMPLY WITH FACBC SEC | | | 4.15 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-03-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-12 |
Time |
14:49 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-03-12 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2001-03-12 00:00:00 | PROVISO; | | | | | | 1.DR.BATHROOM TO BE WOMANS RESTROOM WITH | | | DOOR TO HALLWAY FOR PUBLIC USE. | | | | | | 2.P-4 NOTE 3,2" AIR SUPPLY FOR | | | COMPRESSOR SHALL BE INSTALLED IN MAKE | | | UP AIR VENT NOT SUPPLY AIR DUCT. | | | | | | 3.ADDITIONAL PERMIT REQUIRED FOR MED. | | | GAS. SUBMIT PLANS WITH APPLICATION. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-02-07 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-02-07 |
Time |
15:56 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-07 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | REFERENCES: SPC 94, FACBC 97,NFPA 99-C | | | (1) SHT A-3 DR'S REST RM TO BE H/C | | | ADAPTABLE SEC 4.1.3(11) | | | (2) SHT A-9 SEC 1109 SEPERATE DRAINAGE | | | SYSTEM FROM THE SECONDARY SYSTEM SHALL | | | BE REQUIRED, PROVIDE ISOMETRIC WITH PIPE | | | SIZES, CALCULATIONS, TYPE OF MATEREIAL. | | | (3) SHT A-3 MINIMUM FACILITIES BASED ON | | | TAB 407 ON NUMBER OF FIXTURES FOR MEN | | | WOMEN REST ROOMS REQUIRED. | | | (4) SHT P-5 WATER HEATER ON SHELF,2ND X | | | SHOW A DETAIL OF THE WORKING PLATFORM | | | WITH A FIXED SHIPS LADDER FIXED IN | | | PLACE. SEC 501.7 | | | (5) SHT A-11 SHOW A DETAIL OF THE BREAK | | | RM SINK, ELV.34",CLEAR FLR SPACE 30"X48" | | | KNEE CLEARANCE 19". | | | (6) SHT P-3 AIR CHAMBERS TO BE READLY | | | ACCESSIBLE AND RECHARGEABLESEC.607.8.3 | | | (7) SHT P-3 BACK FLOW PREVENTER REQUIRED | | | ON WATER SERVICE, ALL DENTAL EQUIPMENT. | | | SEC. 601.1 | | | (8) SHT P-4 SEC 104.3 EXAMINATION OF | | | DOCUMENTS. SUBMIT DATA ON ALL DENTAL | | | EQUIPMENT,INCLUDING X RAY PROCESSOR. | | | (9) SHT P-4 VACUM PUMP DRAIN TO BE | | | DIRECTLY CONNECTED TO SANITARY SYSTEM. | | | VENT VACUM PUMP SEPERATLY OUTSIDE. | | | SEC 4-5.2.1.3 & 4-5.2.1.4 | | | (10) SHT P-4 VACUM DISTRIBUTION SYSTEM, | | | SHOW ACCESSIBLE CO'S ON MAINS, BRANCHES | | | 4-5.2.2 | | | END OF COMMENTS, QUESTIONS CONTACT | | | PAUL SCHMITZ 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-12-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-08 |
Time |
11:37 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2000-12-08 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED; | | | 1.DRINKING FOUNTAIN TO MEET FACBC | | | 4.1.3.10 STANDARDS,HIGH LOW FOUNTAIN | | | FOR HANDICAP AND PEOPLE WHO HAVE | | | TROUBLE BENDING AND STOOPING. | | | | | | 2.WATER HEATER TO BE READILY ACCESSIBLE | | | WATER HEATER MUST BE INSTALLED ON THE | | | FLOOR OR A FIXED SHIP LADDER MUST BE | | | INSTALLED.CHANGE DETAIL ON P-5 TO | | | SHOW W/H ON FLOOR. | | | | | | 3.LOUNGE SINK MUST COMPLY WITH FACBC | | | 4.24 THRU 4.24.7. |
|
|