Plan Review Details - Permit 00111091
Plan Review Stops For Permit 00111091
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-12-19 Cont ID  
Sent By rbrown Date 2001-12-19 Time 14:35 Rev Time 0.00
Received By rbrown Date 2001-12-19 Time 14:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-12-10 Cont ID  
Sent By rbrown Date 2001-12-10 Time 11:51 Rev Time 2.00
Received By rbrown Date 2001-12-10 Time 11:50 Sent To  
Notes
2001-12-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 THE FOLLOWING COMMENT IS NUMBERED AS PER
 THE 11/26/01 BUILDING PLAN REVIEW:
  
 3) STRUCTURAL CALCULATIONS.COMMENT NOT
 ADDRESSED.SUBMIT CALCULATIONS FOR THE
 REVISED LOAD PATHS DUE TO THE ROOF
 RE-CONFIGURATION AND REVISED COLUMN
 ARRANGEMENT.
 ----------------------------------------
  
 PROVISO:
  
 WINDOW PRODUCT APPROVAL.THE LARGE
 ARCHED WINDOW ON THE WEST ELEVATION OF
 THE VESTIBULE IS LARGER THAN THE PRODUCT
 APPROVAL DIMENSIONS FOR LARGE MISSILE
 IMPACT WINDOWS (SEE PGT INDUSTRIES
 DRAWING NO.4231, SHEET 3).EITHER
 SHUTTERS MUST BE PROVIDED OR A RELEVANT
 PRODUCT APPROVAL SUBMITTED.
  
  
 END OF REVIEW COMMENTS
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-11-26 Cont ID  
Sent By rbrown Date 2001-11-26 Time 11:17 Rev Time 2.00
Received By rbrown Date 2001-11-26 Time 11:12 Sent To  
Notes
2001-12-05 00:00:00ADDITIONAL NOTES
 NOTES ON SUBMITTALS SINCE PLAN REVIEW
 NUMBERED AS PER ORIGINAL COMMENTS:
  
 7) PRODUCT APPROVALS.THE SUBMITTED
 WINDOW/DOOR ASSEMBLY PRODUCT APPROVALS
 STATE THAT THEY ARE FOR "SINGLE UNIT
 APPLICATIONS ONLY".AS THEY DO NOT
 CORRELATE TO THE PROPOSED ARCHED
 WINDOWS, FURTHER PRODUCT APPROVALS ARE
 REQUIRED TO COVER THE GLAZED OVER-PANELS
 AND ASSOCIATED MULLIONS.
2001-11-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC* = STANDARD BUILDING CODE AMENDMENTS
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY = FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING COSTRUCTION
  
  
 1) CONFIRM THAT SITE PLAN IS UNCHANGED
 TO VERIFY ADEQUATE HORIZONTAL SEPARATION
  
 2) FL ENERGY 103.3 - SUBMIT ENERGY CODE
 COMPLIANCE CALCULATIONS.
  
 3) ROOF RE-CONFIGURED AND COLUMNS
 REVISED.SUBMIT STRUCTURAL
 CALCULATIONS FOR REVISED LOAD PATHS.
  
 4) COLUMN ON FOOTING F-3 IS SHOWN AS
 4"X4"X1/2" ON FOUNDATION PLAN,
 5"X5"X1/4" ON COLUMN SCHEDULE AND
 6"X6"X1/2" ON ROOF FRAMING PLAN.
 CLARIFICATION REQUIRED.
  
 5) FOUNDATION PLAN, SLAB SECTION A-A:
 EXPANSION JOINT REQUIRED.
  
 6) FL ACC CODE 4.13.6 - MINIMUM
 MANEUVERING CLEARANCES HAVE NOT
 BEEN PROVIDED AT THE DOORS TO MALE
 TOILET, FEMALE TOILET OR SUPPLY ROOM
 (ROOM 06). REVISION REQUIRED.
  
 7) WINDOWS HAVE BEEN CHANGED TO ARCHED
 WINDOWS.SUBMIT PRODUCT APPROVALS TO
 INCLUDE THE GLAZED OVER-PANELS AND
 ADDITIONAL MULLIONS
  
 8) SBC 2405.2 - THE GLAZING IN THE
 WINDOW ADJACENT THE EXIT DOOR FROM THE
 STAFF LOUNGE REQUIRES TEMPERED GLASS.
 SHUTTERS ARE REQUIRED FOR LARGE MISSILE
 IMPACT PROTECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-02-12 Cont ID  
Sent By jwitmer Date 2001-02-12 Time 10:24 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-27 Cont ID  
Sent By jwitmer Date 2000-12-27 Time 15:46 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW
 1): FRONT ENTRY / VESTIBULE 6" CHANGE IN
 GRADE. FL. ACCESSIBILITY CODE 4.3.2
 THERE WILL BE AT LEAST ONE ACCESSIBLE
 ROUTEPROVIDED FROM PUBLIC TRANSPORTA-
 TION STOPS, ACCESSIBLE PARKING, LOADING
 ZONES AND TO THE ACCESSIBLE BUILDING
 ENTRRANCE THEY SERVE.
 2).W P B ADMIN.CODE 104.2.2/1606SBC
 SPECIFIC WINDOW AND DOOR BUCK DETAILS.
 3).S.B.C. 1606.2.6.2 COMPONENTS & CLADD-
 ING.PRODUCT APPROVAL REPORTS FOR WINDOWS
 EXT DOORS,GLASS BLOCK & ROOFING MATERIAL
 4).SBC 1606.4.1/ 1707.4.1 STORM SHUTTERS
 REQUIRED FOR GLAZED OPENINGS NOT PASSING
 LARGE MISSLE IMPACT TESTING, A SBCCI OR
 DADE COUNTY REPORT REQUIRED. A SCHEDULE
 AND KEY INSTALLATION PLAN WILL BE
 REQUIRED, SEE ATTACHED POLICY.
 5). 104.2.2 ADD INFO REQUIRED ON THE
 STRUCTURAL MEMBER THAT WILL BE BETWEEN
 THE ARCHED WINDOWS AND WITHER WINDOWS
 BELOW. ATTACHMENT OF WINDOWS AND ATTACH-
 MENT TO THE BLOCK OR COLUMNS.
 6). 104.22 ADD INFO REQUIRED, WINDOWS
 WITH RADIUS HEADS HOW WILL THE INFILL
 OCCUR WHEN USING DETAIL WINDOW A-A?
 7).ENERGY CALCULATIONS
 8).SOILS TEST REPORT 1804.2 GIVING
 BEARING VALUE.
 9). F102.2.4 (FIRE ZONE) FIRE RESISTANT
 ROOF COVERINGS CLASS A OR B AS DEFINED
 IN 1503.2.
 10).ARCH DETAILS PAGE A-6 (FIRE ZONE)
 ARCH TRIM-APPROVED NON COMBUSTIBLE
 MATERIAL OR FIRE RESISTANT TREATED WOOD.
 11). THESE SAME DETAILS WILL REQUIRE ADD
 INFO, THE BOTTOM DETAIL DOESN'T GIVE ANY
 FASTENING TO THE TOP PLATE OR LEDGER.
 THE UPPER DETAIL ALSO DOESN,T GIVE HOW
 TO ATTACH THE TOP LEDGER OR HOW THE LOOK
 OUTS ARE TO FASTENED TO THE LEDGERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412
  
 PLEASE RETURN THE REVIEWED PAGES AFTER
 THE CORRECTIONS ARE COMPLETED, THIS WILL
 EXPEDITE THE REVIEW PROCESS,IF YOU HAVE
 ANY QUESTIONS PLEASE CALL, THANK YOU.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-09-13 Cont ID  
Sent By btrobaug Date 2002-09-13 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2002-07-01 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 13:27 Rev Time 0.00
Received By dpalmer Date 2002-06-11 Time 06:49 Sent To  
Notes
2002-06-11 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT "EQUIPMENT
 GROUNDING" CONDUCTORS ARE STILL BEING
 SHOWN BETWEEN METER AND GUTTER AND
 BETWEEN GUTTER AND MAIN DISC`S. THIS WAS
 REDLINED A YEAR AGO. PLEASE NOTE THAT
 THIS PARALELLING THE NEUTRAL. PLEASE SEE
 250-24
  
 2)NOTE: PLEASE NOTE THAT THERE ARE NO
 REVISIONS INDICATED BY EITHER CLOUDS OR
 TRIANLGES? NO DATES FO ANY REVISIONS
 ARE SHOWN IN THE UPPER RIGHT HAND CORNER
 ?? PLEASE SHOW BY CLOUDS OR TRIANGLES.
 NO INDICATIONS IF PLANS WERE COMPLETELY
 REDRAWN.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW, IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-14 Cont ID  
Sent By pkrauss Date 2002-06-06 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 21:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-03-06 Cont ID  
Sent By dpalmer Date 2001-03-06 Time 20:52 Rev Time 0.00
Received By dpalmer Date 2001-03-06 Time 20:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-01-25 Cont ID  
Sent By dpalmer Date 2001-01-25 Time 23:01 Rev Time 0.00
Received By dpalmer Date 2001-01-25 Time 23:01 Sent To  
Notes
2001-01-25 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLANS ARE SIGNED AND SEALED,
 ALL CHANGES SUBMITTED ARE REQ`D TO BE
 SIGNED AND SEALED ALSO. PER F.A.C. SEC
 481.221.
 PLEASE MAKE NOTES ON PLANS ALREADY DONE
 AND HAVE ARCH/ENGINEER INITIALED AT
 LOCATION OF NOTES AND/OR CHANGES.
  
 PLEASE SUBMIT THE SUBMITTED AND ABOVE
 INFORMATION FOR REVIEW. IF THIS IS DONE
 WHEN SUBMITTD FOR PERMIT THEN ELECTRICAL
 REVIEW WILL BE SIGNED OFF.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-14 Cont ID  
Sent By dpalmer Date 2000-12-14 Time 19:29 Rev Time 0.00
Received By dpalmer Date 2000-12-14 Time 19:29 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM. AN
 EQUIPMENT GROUNDING CONDUCTOR IS SHOWN
 IN RISER AND FROM METERCAN TO FIRST
 MEANS OF DISCONNECT. PLEASE NOTE PER 250
 OF THE NEC ONLY AFTER FIRST MEANS.
  
 2)NOTE: PLEASE SEE E-4. THIS SHOWS AIC
 RATINGS FOR ALL PANELS BUT NOTHING FOR
 MAINS? PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. PER 110-9
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2002-09-16 Cont ID  
Sent By mamini Date 2002-09-16 Time 08:25 Rev Time 0.00
Received By mamini Date 2002-09-16 Time 08:00 Sent To  
Notes
2002-09-13 00:00:00PASSED WITH PROVISOS:
 1. UPON COMPLETION OF THE CIVIL/SITE
 WORKS AND INSTALLTION OF THE ALTERNATE
 DRAINAGE SYSTEMS, A CERTIFICATION BY THE
 CIVIL ENGINEER OF RECORD MUST BE
 SUBMITTED TO THE CONSTRUCTION SERVICES
 DEPARTMENT ATT: MOHAMMAD R. AMINI.
 THE CERTIFICATION MUST STATE THAT THE
 DRAINAGE SYSTEM IS CONSTRUCTED PER
 PROPOSED ALTERNATE PLAN AND IS OPERATING
 AS DESIGNED AND COMPLY WITH THE CITY
 REQUIREMENTS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-02-12 Cont ID  
Sent By mamini Date 2001-02-12 Time 14:06 Rev Time 1.50
Received By mamini Date 2001-02-12 Time 13:06 Sent To  
Notes
2001-02-12 00:00:00PASSED WITH PROVISOS:
 1. PLEASE REFER TO PREVIOUSE ENGINEERING
 REVIEW COMMENTS AND COMPLY.
 2. BACKFLOW PREVENTTES ARE REQUIRED AT
 CONNECTIONS TO WATER MAIN.
 IF ANY QUESTION PLEASE CONTACT 659 80
 96 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-01-04 Cont ID  
Sent By mgonzale Date 2001-01-04 Time 15:43 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED
 MUST COMPLY WITH THE FOLLOWING DEMANDS
 1. PLEASE SHOW EXISTING WM ALONG 3'
 UTILITY EASEMENT AND SHOW NEW IRRIGATION
 METER SERVICE CONNECTION.
 2. IT IS RECOMENDED THAT NEW IRRIGATION
 SERVICE BE MADE ON THE WATERMAIN OFF SUN
 SET ROADAND DIXIE.
 3. DRIVEWAY ENTRANCES DO NOT COMPLY WITH
 CITY DRIVEWAY APPROACH STANDARDS
 EMAIL [email protected]
 FOR STANDARD DETAIL.
 4. CALL OUT SIZE OF METER AND SIZE OF SE
 RVICE. WE ALLOW ONLY 1" OR 2" TYPE K
 COPPER.
 5. PROVIDE CITY OF WPB
 PUBLIC UTILITY DEPT. WITH A MINIMUM OF 2
 SETS OF PLANS FOR THEIR FILES.
 6. DRAINAGE CALCULATIONS SHALL BE SUBMIT
 TED TO JOSE DEL RIOS OF THE STORM WATER
 DIVISION FORAPPROVAL.
 7. NO LARGE STREES SHALL BE PLANTED IN
 UTILITY EASEMENT
 8. PROVIDE OR CALL OUT HANDICAP RAMP FOR
 PARKING
 TOTAL SITE SF IS 19175OK
 TOTAL IMPERVIOUS SF IS 16154OK
 TOTAL PERVIOUS SF IS 3021OK
 9. PROVIDE STANDARD UTILITY DETAILS
 THAT APPLY. YOU MAY REQUEST THESE VIA
 EMAIL TO THE SAME EMAIL AS ABOVE
 10. A DESIGNATED PLAN SHOULD BE TITLED
 POLLUTION CONTROL PLAN AND SHALL SHOW
 A SILT FENCE ALONG THE PROPERTY LINE
 OF THE SITE. PLEASE PROVIDE A SILT
 FENCE DETAIL OR CUT SECTION.
 11. ALL LARGE TREES MUST BE ATLEAST 5'
 AWAY FROM EXISTING WM'S
 12. TO LOCATE EXISTING WM YOU MAY CONTAC
 T OUR UTILITY LOCATING DEPT. AT
 659 8079.
  
 IF ANY QUESTION PLEASE FEEL
 FREE TO CONTACT ME AT
 561 659 8040
 PUBLIC UTILITIES ENGINEERING SERVICES
 1000 45TH STREET SUITE 15
 WPB, FL 33407
 FAX 561 659 8039
  
 HAVE A GREAT DAY!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 14:44 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-23 Cont ID  
Sent By mcarsill Date 2001-01-23 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2001-01-23 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By mcarsill Date 2000-11-30 Time 09:53 Rev Time 0.00
Received By mcarsill Date 2000-11-30 Time 09:53 Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS NOT NOTED ON
 ELEVATION DRAWINGS. ADDRESS TO BE
 INSTALLED ON BUILDING IN ACCORDANCE WITH
 CITY CODE REQUIREMENTS.
 2) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION. SINCE THERE ARE NO FIRE
 SPRINKLERS ARE PLANNED, INTERIOR FINISH
 IN EXITS SHALL BE CLASS A OR B. OFFICE
 AREAS CAN BE CLASS A, B, OR C.
 3) PLEASE INDICATE ON THE PLANS WHERE
 THE FIRE EXTINGUISHERS WILL BE
 LOCATED.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-06 Time 13:08 Rev Time 0.45
Received By pkrauss Date 2002-06-06 Time 12:06 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-02 Cont ID  
Sent By pkrauss Date 2002-01-02 Time 15:18 Rev Time 0.40
Received By pkrauss Date 2002-01-02 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-26 Cont ID  
Sent By ndenmark Date 2000-12-26 Time 08:12 Rev Time 0.50
Received By pschmitz Date 2000-12-26 Time 08:12 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.MOP SINK CLOSET TO HAVE EXHAUST FAN
 PER 1997 SMC 501.4
 2. DUCT DETECTOR TO BE TIED TO BLDG FIRE
 ALARM OR HORN AND STROBE FOR NOTIFICATIO
 PER 1996 NFPA 90A
 3. MEDICAL GAS SYSTEMS REQUIRE SEPARATE
 PERMIT. SUBMIT PLANS AT TIME OF MECHANI-
 CAL PERMIT APPLICATION FOR THIS WORK.

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-01-02 Cont ID  
Sent By kstevens Date 2002-01-02 Time 13:39 Rev Time 1.50
Received By kstevens Date 2002-01-02 Time 13:39 Sent To  
Notes
2002-01-02 00:00:00PASSED/PROVISO
  
 1) SHUT OFF VALVE TO BE WITH-IN 3' OF
 W/HEATER, AND RELIEF LINE SHALL NOT BE
 TRAPPED.
  
 2) SEPARATE PERMIT REQUIRED FOR MED-GAS.
 COPY OF CERTIFICATION FOR INSTALLATION
 REQUIRED AT TIME OF PERMITTING.
 KSTEVENS - FOR P.E.S.

Review Stop P PLUMBING
Rev No 7 Status F Date 2001-12-09 Cont ID  
Sent By pschmitz Date 2001-12-09 Time 09:17 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-09 00:00:00PLUMBING PLAN REVIEW,MEDICAL GAS DENIED
 2ND TIME,PREVIOUS COMMENTS NOT ADDRESS.
 PROVIDE A RESPONSE SHEET ADDRESSING EACH
 COMMENT. SPC94,SEC 104.3 PLANS & SPECS.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 6 Status F Date 2001-12-08 Cont ID  
Sent By kstevens Date 2001-12-08 Time 07:06 Rev Time 1.25
Received By kstevens Date 2001-12-08 Time 07:05 Sent To  
Notes
2001-12-08 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT P-5 WATER HEATER DETAIL. WATER
 HEATER CAN NOT INTERFERE WITH NORMAL
 USE OF MOP SINK.
 2) SHT P-3 INTERGAL BACKFLOW PREVENTER
 ARE NOT APPROVED. PLEASE PROVIDE BACK-
 FLOW FOR ALL DENTAL EQUIPMENT AND PRO-
 CESSOR.
 3) SHT'S P-1, P-2, & P-3, NO DETAIL FOR
 WATER FEATURE SHOWN AS REQUESTED IN PRE-
 VIOUS REVIEWS.
 4) SHT P-3, IF AIR CHAMBERS ARE TO BE
 USED, SHOW DETAIL AS PER WH-PDI 201.
 SEE ATTACHED SHEET FOR REFERENCE.
 5) SHT P-5, AS REQUESTED IN PREVIOUS RE-
 VIEW, AIR GAP FOR PROCESSOR DRAIN NOT
 APPROVED. PLEASE SEE ATTACHED SHEET FOR
 APPROVED AIR GAP FITTING FOR THIS APPLI-
 CATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-11-21 Cont ID  
Sent By pschmitz Date 2001-11-21 Time 09:29 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-21 00:00:00PLUMBING PLAN REVIEW,MEDICAL GAS DENIED.
 SHT P-2,4 COMPLY WITH NFPA-99C LEVEL 3
 DENTAL OFFICE,SEC 4-5.1.1.3, COMPRESSED
 AIR, SEE FIG 4-5.1.1.3
 PIPED VACUM SYSTEMS, LEVEL 3,SEC 4-5.2,
 SEE FIG 4-5.2.1
 DESIGN SYSTEM PER ABOVE.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-11-13 Cont ID  
Sent By kstevens Date 2001-11-13 Time 08:55 Rev Time 3.00
Received By kstevens Date 2001-11-13 Time 08:54 Sent To  
Notes
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) WATER HEATER TO HAVE PERMINATE SHIPS
 LADDER AND A WORKING PLATFORM MINIMUM
 DEMENSIONS 30"X30" TO MAKE WATER HEATER
 READILY ACCESSIBLE PER SPC SEC 501.7.
 2) BACKFLOW REQUIRED FOR PROCESSOR
 3) PAGE P1, PLEASE SUBMIT DETAILS FOR
 WATER FEATURE. AND SHOW HOW POTABLE
 WATER WILL BE PROTECTED.
 4) PAGE P1, PAGE P5, VACUUMN DETAIL. VAC
 PUMP TO BE DIRECTLY CONNECTED TO SANT.
 SYSTEM. SEC 4-5.2.1.3 & 4-5.2.1.4
 5) PAGE P1, NO WATER SUPPLY SHOWN TO
 DRINKING FOUNTAIN.
 6) PAGES P1, P3 & P5, WATER FILTER SHALL
 COMPLY WITH NSF STANDARDS. PLEASE SUBMIT
 MANUFACTURE INFORMATION TO SHOW FILTER
 COMPLIES WITH STANDARD.
 7) PAGES P1 & P3, BACKFLOW REQUIRED ON
 WATER SERVICE AND ALL DENTAL EQUIPMENT.
 8)PAGE P3, NOTES #1, & #2 TO READ SPC-
 94 NOT SPC-97.
 9)PAGE P3, AIR CHAMBERS ARE A "QUICK
 FIX" AND REQUIRE ACCESS PANELS. THEY
 ALSO SHALL BE RECHARGEABLE PER SPC-94
 SEC 607.8.3. WATER HAMMER ARRESTORS
 SHOULD BE USED AND SIZED AND LOCATED PER
 MANUFACTURE INSTRUCTION AND PDI-WH 201,
 CLOSE TO FIXTURES NOT AT TOP OF DROP AS
 SHOWN ON RISER DIAGRAM.
 10) PAGE P3, NO WATER SHOWN TO WATER
 FEATURE ON RISER DIAGRAM.
 11) PAGE P5, AIR GAP FOR PROCESSOR DRAIN
 NOT APPROVED. PLEASE SEE ATTACHED SHEET
 FOR APPROVED AIR GAP FITTING FOR THIS
 APPLICATION.
 12) PAGES P1 & P2, DRINKING FOUTAIN.
 PLEASE PROVIDE PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 SHOW HOW D.F. WILL COMPLY WITH FACBC SEC
 4.15
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-03-12 Cont ID  
Sent By jleech Date 2001-03-12 Time 14:49 Rev Time 2.00
Received By jleech Date 2001-03-12 Time 14:48 Sent To  
Notes
2001-03-12 00:00:00PROVISO;
  
 1.DR.BATHROOM TO BE WOMANS RESTROOM WITH
 DOOR TO HALLWAY FOR PUBLIC USE.
  
 2.P-4 NOTE 3,2" AIR SUPPLY FOR
 COMPRESSOR SHALL BE INSTALLED IN MAKE
 UP AIR VENT NOT SUPPLY AIR DUCT.
  
 3.ADDITIONAL PERMIT REQUIRED FOR MED.
 GAS. SUBMIT PLANS WITH APPLICATION.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-02-07 Cont ID  
Sent By pschmitz Date 2001-02-07 Time 15:56 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-07 00:00:00PLUMBING PLAN REVIEWDENIED
 REFERENCES: SPC 94, FACBC 97,NFPA 99-C
 (1) SHT A-3 DR'S REST RM TO BE H/C
 ADAPTABLE SEC 4.1.3(11)
 (2) SHT A-9 SEC 1109 SEPERATE DRAINAGE
 SYSTEM FROM THE SECONDARY SYSTEM SHALL
 BE REQUIRED, PROVIDE ISOMETRIC WITH PIPE
 SIZES, CALCULATIONS, TYPE OF MATEREIAL.
 (3) SHT A-3 MINIMUM FACILITIES BASED ON
 TAB 407 ON NUMBER OF FIXTURES FOR MEN
 WOMEN REST ROOMS REQUIRED.
 (4) SHT P-5 WATER HEATER ON SHELF,2ND X
 SHOW A DETAIL OF THE WORKING PLATFORM
 WITH A FIXED SHIPS LADDER FIXED IN
 PLACE. SEC 501.7
 (5) SHT A-11 SHOW A DETAIL OF THE BREAK
 RM SINK, ELV.34",CLEAR FLR SPACE 30"X48"
 KNEE CLEARANCE 19".
 (6) SHT P-3 AIR CHAMBERS TO BE READLY
 ACCESSIBLE AND RECHARGEABLESEC.607.8.3
 (7) SHT P-3 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVICE, ALL DENTAL EQUIPMENT.
 SEC. 601.1
 (8) SHT P-4 SEC 104.3 EXAMINATION OF
 DOCUMENTS. SUBMIT DATA ON ALL DENTAL
 EQUIPMENT,INCLUDING X RAY PROCESSOR.
 (9) SHT P-4 VACUM PUMP DRAIN TO BE
 DIRECTLY CONNECTED TO SANITARY SYSTEM.
 VENT VACUM PUMP SEPERATLY OUTSIDE.
 SEC 4-5.2.1.3 & 4-5.2.1.4
 (10) SHT P-4 VACUM DISTRIBUTION SYSTEM,
 SHOW ACCESSIBLE CO'S ON MAINS, BRANCHES
 4-5.2.2
 END OF COMMENTS, QUESTIONS CONTACT
 PAUL SCHMITZ 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-08 Cont ID  
Sent By jleech Date 2000-12-08 Time 11:37 Rev Time 1.00
Received By pschmitz Date 2000-12-08 Time 11:37 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.DRINKING FOUNTAIN TO MEET FACBC
 4.1.3.10 STANDARDS,HIGH LOW FOUNTAIN
 FOR HANDICAP AND PEOPLE WHO HAVE
 TROUBLE BENDING AND STOOPING.
  
 2.WATER HEATER TO BE READILY ACCESSIBLE
 WATER HEATER MUST BE INSTALLED ON THE
 FLOOR OR A FIXED SHIP LADDER MUST BE
 INSTALLED.CHANGE DETAIL ON P-5 TO
 SHOW W/H ON FLOOR.
  
 3.LOUNGE SINK MUST COMPLY WITH FACBC
 4.24 THRU 4.24.7.


Account Summary | Usage Policy | Privacy Policy