Plan Review Details - Permit 00110799
Plan Review Stops For Permit 00110799
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 11:59 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 20:49 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 20:49 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE AVAILABLE
 FAULT IS SHOWN BUT PLEASE LIST THE RAT-
 -ING OF THE PANEL. ALSO PLEASE LIST THE
 AIC RATING OF MAIN DISCONNECT. PLEASE
 SUBMIT CLARIFICATIONOF RISER DIAGRAM
 AND PLANS. PLAN SHOWS MAIN DISCONNECT
 NEXT TO METER? AND RISER SHOWS PANEL
 BEING NEMA-1 INSIDE.??? PLEASE CORRELATE
  
  
 2)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING REQ`MENTS. 2`,6` RULE.
  
 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210-8-A-6.
  
 4)NOTE: PLEASE SEE MECH CODE 300.9 FOR
 'WP GFI REQ`D FOR A/C COND UNITS.
  
 5)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3 AND
 210-52D. MUST BE #12 AND 20A.
  
 6)NOTE: PLEASE NOTE THAT THE GAS WATER
 HEATER MAY NOT BE PERMITTED IN UNDER
 SEC 504 OF THE GAS CODE, 504.1
  
 7)NOTE: PLEASE SEE THE REQ`MENTS FOR
 GARAGE OUTLET, 210-52G AND MUST BE GFI
 PER 210-8.
  
 8)NOTE: PLEASE NOTE THAT THE SAME
 NOTE PERTAINS TO GARAGE FOR CLARIFICAT-
 -ION OF SERVICE/PANEL/DISCONNECT.
 AIC RATINGS ETC.215-5
  
 9)NOTE: SMOKE DETECTOR ON EACH LEVEL
 FOR APT.
  
 10)NOTE: PLEASE NOTE BATH(S) CIRCUIT
 FOR APT ALSO. PER 210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-01-25 Cont ID  
Sent By fknapp Date 2001-01-25 Time 14:30 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-25 00:00:00OK PER D.LAUDERMILK NO PROVISO NEEDED
 CITY FIRE HYDRANT TO BE HANDLE BY CITY.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2001-01-25 Cont ID  
Sent By fknapp Date 2001-01-25 Time 14:33 Rev Time 0.00
Received By fknapp Date 2001-01-16 Time 13:44 Sent To  
Notes
2001-01-16 00:00:00DISREGARD FIRST REVIEW.
 PASSED WITH PROVISOS:
 THE DRIVEWAY CAN NOT BE INSTALLED WHERE
 SHOWN ON THE PLANS, UNLESS THE HOME
 OWNER MOVES THE HYDRANT AT HIS COST.
 THE HYDRANT MUST BE RELOCATED (AT A
 MINIMUM OF FIVE FOOT FROM THE EDGE OF
 OF THE NEW DRIVEWAY.
 SIDEWALK AND DRIVEWAY REQUIREMENTS:
 ALL BROKEN SIDEWALKS, CURBSAND DRIVE-
 WAYS MUST BE REPLACED.
 ALL DRIVEWAY APPROACHES THAT ARE NOT TO
 BE USED MUST BE REMOVED AND REPLACED
 WITH NEW CURBS (AND GUTTERS).
 ALL DRIVEWAY APPROACHES MUST BE TO THE
 CITY STANDARD INDEX (SEE ATTACHED).
 ALL GRADES FOR CITY SIDEWALKS AND DRIVES
 MUST BE SET UP BY THE CITY SURVEY CREW.
 CALL ED RYAN AT 659-8040 TO SET UP AN
 APPOINTMENT.
 ALL WORK IN THE ROAD RIGHT OF WAY MUST
 BE PERMITTED THROUGH THE PUBLIC
 ENGINEERING OFFICE AT 1000-45TH STREET.
 A CLEAN-OUT IS REQUIRED AT THE PROPERTY
 LINE ON THE SANITARY SEWER LATERAL.
 CALL 659-8079 TO HAVE A CREW COME OUT
 AND LOCATE THE EXISTING SEWER LATERAL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-01-16 Cont ID  
Sent By dlauderm Date 2001-01-16 Time 13:28 Rev Time 1.00
Received By dlauderm Date 2001-01-16 Time 12:33 Sent To  
Notes
2001-01-16 00:00:00PASSED WITH PROVISOS:
 THE DRIVEWAY CAN NOT BE INSTALLED WHERE
 SHOWN ON THE PLAN.THERE MUST BE FIVE
 FOOT OF CLEARANCE FROM THE EDGE OF THE
 DRIVE TO THE HYDRANT. IF THE DRIVEWAY
 HAS TO BE INSTALLED AT THIS LOCATION THE
 N THE PROPERTY OWNER MUST RELOCATED THE
 FIRE HYDRANT AT THEIR COST.THE NEW
 FIRE HYDRANT LOCATION MUST BE FIVE FOOT
 FROM THE NEW DRIVEWAY. THIS FIRE HYDRANT
 WAS INSTALLED IN JUNE OF 2000.
 SIDEWALK AND DRIVEWAY REQUIREMENTS:
 ALL BROKEN SIDEWALKS ALONG THE FRONT OF
 THE PROPERTY MUST BE REPLACED.
 ALL DRIVEWAY APPROACHES THAT ARE NOT TO
 BE USED MUST BE REMOVED AND REPLACED
 WITH NEW CURBS (AND GUTTERS).
 ALL DRIVEWAYS MUST BE TO THE ATTACHED
 CITY STANDARD DRIVEWAY INDEX.
 ALL GRADES FOR CITY SIDEWALKS AND DRIVES
 MUST BE SET UP BY THE CITY SURVEY CREW.
 CALL ED RYAN AT 659-8040 TO SET UP AN
 APPOINTMENT.
 ALL RIGHT OF WAY PERMIT MUST BE APPLIED
 FOR TO INSTALL THE DRIVEWAY APPROACH AND
 SIDEWALKS.APPLY FOR THE PERMIT AT THE
 ENGINEERING DEPARTMENT AT 1000-45TH ST.
 WATER AND SEWER:
 A RPZA BACKFLOW PREVENTER MUST BE
 INSTALLED AT THE PROPERTY LINE.
 A CLEAN-OUT IS REQUIRED ON THE SEWER
 LINE AT THE PROPERETY LINE.
 NO TREES CAN BE PLANTED WITHIN FIVE FOOT
 OF ANY WATER, SANITARY OR STORM LINE OR
 APPURTANANCES OWNED BY THE CITY.THIS
 INCLUDES HYDRANTS AND WATER SERVICES
 AND SANITARY SEWER LATERALS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-25 Cont ID  
Sent By pkrauss Date 2002-01-25 Time 08:27 Rev Time 0.40
Received By pkrauss Date 2002-01-25 Time 08:27 Sent To  
Notes
2002-01-25 00:00:00MECH REV 01011080

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 07:19 Rev Time 0.33
Received By jleech Date 2001-01-20 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-02 Cont ID  
Sent By jleech Date 2000-12-02 Time 08:44 Rev Time 0.75
Received By jleech Date 2000-12-02 Time 08:44 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.IS WATER HEATER GAS OR ELECTRIC?
 ENERGY CAULKS CALL FOR ELECTRIC, PLANS
 SHOW GAS. IF GAS SHOW VENTING AND
 COMBUSTION AIR CALKULATIONS.
  
 2.M-1 IN LIBRARY A 12X12 DROP WITH 210
 CFM'S IS SHOWN, WHAT SIZE DUCT AND
 WHERE IS DUCT RUN FROM?
  
 3.M-1 SECOND FLOOR, LEFT SIDE OF A/H#1
 6" DUCT AND DROP HAVE NO SIZE OR CFM'S
  
 4.BATHROOM EXHAUST FANS MUST VENT TO
 OUTSIDE.
  
 5.ATTIC ACCESS MUST BE NO LESS THAN
 22X36 INCHES. THE ATTIC OPENING SHALL
 NOT BE MORE THAN 20 FEET FROM
 EQUIPMENT AND HAVE A PASSAGE WAY ALSO
 WORKING CLEARANCE MUST BE MET. PER
 97 SMC 304.4.1.
  
 6.GUEST HOUSE. A/C FOR FIRST FLOOR?
 NONE SHOWN.
  
 7.WHAT SIZE IS R/A DUCT SECOND FLOOR.
  
 8.WATER HEATER [SAME AS NOTE 1]
  
 9.ATTIC ACCESS [SAME AS NOTE 5]
  
 MECHANICAL PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-20 Cont ID  
Sent By jleech Date 2001-01-20 Time 07:20 Rev Time 0.33
Received By jleech Date 2001-01-20 Time 07:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-02 Cont ID  
Sent By jleech Date 2000-12-02 Time 09:09 Rev Time 0.75
Received By jleech Date 2000-12-02 Time 09:09 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.PLUMBING RISER DIAGRAM NOT TO CODE.
 SHOW PROPER VENTING.
  
 2.IF ICE MACHINES DRAIN FLOOR DRAINS
 MUST BE INSTALLED TO ALLOW I.M. TO
 DRAIN INDURECTLY TO THE DRAINAGE
 SYSTEM.
  
 3.A-3 BEDROOM 2 SHOWER MUST BE AT LEAST
 30" WIDE AND HAVE 1024 SQ. IN.
 INTERIOR ROOM.
  
 4.BACKFLOW PREVENTOR MUST BE INSTALLED
 IF ONE WATER METER IS USED FOR BOTH
 DWELLINGS. SHOW WATER RISER.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT.8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-01-25 Cont ID  
Sent By fknapp Date 2001-01-25 Time 14:29 Rev Time 2.00
Received By fknapp Date 2001-01-25 Time 14:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-13 Cont ID  
Sent By fknapp Date 2000-12-13 Time 15:19 Rev Time 4.00
Received By fknapp Date 2000-12-13 Time 15:19 Sent To  
Notes
2001-01-08 00:00:00 
 ************BUILDING UNSAT**************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 MULLIONS
 GARAGE DOOR
 ARCH TRANSOMS
 FLAT ROOF COVERING
 STORM PANELS WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED.
  
 2)PROVIDE OWNER/AGENT SIGNATURE ON BOTH
 COPIES OF ENERGY CALCULATIONS.
  
 3)PROVIDE ATTIC ACCESS 22"X 36" MIN.
 PER 1997 SBC 2309.6.
  
 4)PROVIDE COMPLETE STRUCTUAL DETAILS FOR
 BALCONIES AND RAILINGS.
  
 5)POOL AND DECK UNDER SEPARATE PERMIT.
  
 PLEASE MAKE CORRECTIONS TO ORIGINAL PLAN
 SUBMITTED AND RETURN.
  
 ANY QUESTIONS PLEASE CALL:
 FRANK KNAPP
 CITY OF WEST PALM BEACH
 BUILDING PLAN REVIEW
 561-659-8096 EXT 8392

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-27 Cont ID  
Sent By sgraham Date 2000-11-27 Time 16:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***