Plan Review Details - Permit 00110788
Plan Review Stops For Permit 00110788
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 18:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By dpalmer Date 2000-11-30 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2000-11-30 Time 19:10 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS OF NEW AND ON EACH LEVEL.ALSO
 FOR EXISTING BEDROOM(S) PER NFPA-72 2-2.
 .1.1.1.
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 REQ`D BY 220-3-C-1
 PLEASE SHOW EXISTING SERVICE SIZE/FEEDER
 -S,/ PANEL SCHEDULES,,,,,, 215-5
  
 3)NOTE: A/C LOADS??
  
 4)NOTE: PLEASE SHOW ANY CATV AND TELE-
 -PHONES AND LOCATIONS ON PLANS.
  
 5)NOTE: PLEASE SHOW OUTLETS IN BATHS AS
 GFI REQ`D PER 210-8.
  
 6)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3
  
 7)NOTE: PLEASE SEE CLOSET CLEARENCES PER
 410-8. PLEASE SHOW TYPE OF FIXTURE.
  
 8)NOTE: PLEASE SEE 210-52E FOR WP GFI
 OUTLET FRONT OF DWELLING.
  
 9)NOTE: PLAN SHOWS MORE THAN 50% OF THE
 WIRING IN HOUSE AS BEING NEW. ALL ELEC-
 -TRICAL IN HOUSE MAY NEED TO BE BROUGHT
 UP TO CODE AS REQ`D AND SUBJECT TO
 ELECTRICAL INSPECTION.
  
 10NOTE: PLEASE SHOW OUTLET ON BACK PORCH
 AS GFI PER 210-8
  
  
 PLEASE SUBMIT AND SHOW ALL OF THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-12-01 Cont ID  
Sent By jleech Date 2000-12-01 Time 07:18 Rev Time 0.25
Received By jleech Date 2000-12-01 Time 07:15 Sent To  
Notes
2001-01-08 00:00:00A/C PLAN TO BE SUBMITED WITH APPLICATION
 BY LICENSED A/C CONTRACTOR.
 A/C PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-12 Cont ID  
Sent By pschmitz Date 2001-02-12 Time 18:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-01 Cont ID  
Sent By jleech Date 2000-12-01 Time 07:31 Rev Time 0.25
Received By jleech Date 2000-12-01 Time 07:30 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.SHOW PLUMBING SANITARY AND WATER RISER
 DIAGRAMS.
  
 2.WHAT SIZE IS EXISTING BUILDING DRAIN
 AND BUILDING SEWER?
  
 3.HOW WILL NEW PLUMBING TIE INTO OLD
 PLUMBING?
  
 4.HOW WILL FIRST FLOOR BATHROOM AND
 KITCHEN VENT STACK VENTED?
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-02-21 Cont ID  
Sent By rmcdouga Date 2001-02-21 Time 10:44 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-02-21 00:00:00PROVISO
  
 1) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS PRIOR TO
 INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-05 Cont ID  
Sent By rmcdouga Date 2000-12-05 Time 10:07 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)RECORDED COPY OF NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITED TO CITY BUILDING DEPT. BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED.
  
 3)PROVIDE SPECIFIC DETAILS FOR INTERIOR
 AND EXTERIOR STAIRS INCLUDING DIMENSIONS
 FOR ALL COMPONENTS. 97 SBC 104.2
  
 4)PROVIDE FLOOR AND ROOF TRUSS PLANS
 INDICATING THE CALCULATED UPLIFTS AND
 THE SPECIFIC CONNECTORS TO BE USED.
  
 5)PROVIDE FOUNDATION PLAN INDICATING
 LOCATIONS OF PADS FOR STEEL COLUMNS,
 ADDED FOOTINGS AT FRONT PORCH,AT BEARING
 WALLS OF STAIRWELL,FOOTINGS FOR COVERED
 DECK. PROVIDE COLUMN SPACING,ETC.
  
 6)PROVIDE SPECIFIC DETAILS FOR GUARDRAIL
 AT COVERED DECK. SPECIFY MATERIAL,SPAC-
 ING OF INTERMEDIATE RAILS,SPACING OF
 SUPPORTS,METHOD OF ATTACHMENT,ETC.
  
 7)PROVIDE ATTIC VENTILATION.97SBC 2309.7
  
 8)PROVIDE CRAWL VENTILATION. SPECIFY
 SIZE,LOCATION AND NUMBER OF VENTS.97SBC
 1804.6.2 NOTE:ACCESS IS REQUIRED TO
 USABLE CRAWL SPACE.
  
 9)PROVIDE 2 COPIES OF FL ENERGY CODE
 COMPLIANCE FORMS AND MANUAL "J" CALCS.
  
 10)SAFETY GLASS IS REQUIRED IN BATHROOMS
 97SBC 2405.2
  
 11)PROVIDE FLOOR AND CEILING ELEVATIONS
 FROM FINISH GRADE. INDICATE MEAN ROOF
 HEIGHT.
  
 12)PROVIDE VIEWS OF ALL FOUR ELEVATIONS
 ON PLANS.
  
 13)PLANS APPEAR TO INDICATE RELOCATION
 OF EXISTING ENTRY DOOR ON 1ST FLOOR.
 PLANS DO NOT INDICATE PORCH OR STEPS AT
 RELOCATED DOOR. PLEASE CLARIFY.
  
 14)TRUSS LAYOUTS AND TRUSS DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD AND TO BE SO
 NOTED AND SIGNED BY THE DESIGNER OF THE
 STRUCTURE.NOTE: PLEASE CHECK THE DIMEN-
 SIONS,THE TRUSS LAYOUT AND AND PLANS DO
 NOT CONCUR.
  
 15)PROVIDE FASTENING DETAILS FOR ATTACH-
 ING THE 3 PLIES OF LVL TOGETHER.
  
 16)PROVIDE DETAILS ON LOAD BEARING WALLS
 AT STAIR OPENING SUPPORTING FLOOR TRUSS-
 ES F2 AND GIRDER TRUSS G2, INCLUDING
 FOUNDATION.
  
 17)PROVIDE 2 COPIES OF KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
 ALSO PROVIDE AN ADDITIONAL COPY OF THE
 PRODUCT APPROVAL, ONLY 1 COPY WAS
 RECIEVED.
  
 18)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR ROOF COVERING. THE ONES
 SUBMITTED HAD EXPIRED PRIOR TO APPLICAT-
 ION DATE.
  
 19)PRODUCT APPROVALS FOR FRENCH DOORS
 WERE SUBMITTED.PLEASE INDICATE WHERE
 THEY WILL BE LOCATED ON THE PLANS.
  
 20)PROVIDE PRODUCT APPROVALS FOR SLIDING
 GLASS DOORS SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-22 Cont ID  
Sent By sgraham Date 2000-11-22 Time 10:34 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***