Plan Review Details - Permit 00110721
Plan Review Stops For Permit 00110721
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-28 Cont ID  
Sent By lmartine Date 2001-03-28 Time 16:10 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-28 00:00:00OK, TO INCLUDE STAIR WITH THIS PERMIT
 L. MARTINEZ3/28

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-03-08 Cont ID  
Sent By lmartine Date 2001-03-08 Time 12:23 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-08 00:00:00BUILDING COMMENTS
 -----------------
  
 PROVIDE PERMIT # FOR THE TENANT
 BUILDOUTFOR VARIFICATION OF COMPLIANCE
 WITH EXCEPTION ALLOWED BY SECT.
 705.2.2,#2,SBC.
 [SHAFT ENCLOSURES]. SEE ATTAHED.
  
 SEPERATE PERMIT IS REQUIRED FOR SCOPE OF
 WORK INDICATED, THIS PERMIT IS FOR THE
 CUTTING OF FLOOR ONLY.
  
 SEE COMMENTS FROM FIRE REVIEW.
  
  
 LUIS MARTINEZ
 BLDG.PLAN REVIEW
 (561) 659-8096EXT. 8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By lmartine Date 2001-01-19 Time 13:02 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-19 00:00:00PERMIT IS BEING ISSUED FOR CUTTING OF
 FLOOR ONLY.
 STAIRS ARE NOT CODE COMPLIANT, AND SHALL
 BE REVISED.
  
  
 L.MARTINEZ

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-03-08 Cont ID  
Sent By mcarsill Date 2001-03-08 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2001-03-08 Time 09:42 Sent To  
Notes
2001-03-08 00:00:001) A DRAFT STOP AND FIRE SPRINKLER HEADS
 SPACED NO FARTHER SIX FEET APART ARE
 TO BE PROVIDED FOR THE OPEN STAIR.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910