Plan Review Details - Permit 00110647
Plan Review Stops For Permit 00110647
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-05-03 Cont ID  
Sent By dpalmer Date 2001-05-03 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2001-05-03 Time 15:18 Sent To  
Notes
2001-05-03 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM ORIG PROVISO WERE NOT ADDRESSED.
  
 PLEASE SEE NOTES ATTACHED FROM FIRST REV
 IEW. #`S 4,6,8.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-11-15 Cont ID  
Sent By dpalmer Date 2000-11-15 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2000-11-15 Time 18:50 Sent To  
Notes
2001-01-08 00:00:00********PLEASE REVISE **************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH MORE
 ELECTRICAL DETAIL SHOWN.
  
 2)NOTE: PLEASE SHOW A/C UNITS. SHOW
 DISCONNECTS PER 440-11 AND RECEPT PER
 LOCAL MECH CODE.
  
 3)NOTE: NO HWH SHOWN?? IS THIS CORRECT?
 IF THERE IS ONE PLEASE SHOW ON PANEL
 AND PLAN. INCLUDE ON LOAD CALCS.
  
 4)NOTE: PLEASE NOTE THAT SD`S ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 PER NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE LABEL/SHOW ALL OUTLETS
 THAT MEET THE REQ`MENTS FOR 210-8 AS
 GFI/GFI PROTECTED.
  
 6)NOTE:PLEASE INCLUDE BLDG STEEL AND CWP
 AS PART OF THE GROUNDING BOND AT CABANA.
 PER 250-50
  
 7)NOTE: PLEASE NOTE THAT IF THERE IS
 GOING TO BE ANY LOW VOLTAGE IN THE
 CABANA THEN PLEASE SHOW ON PLAN. THIS
 MIGHT INCLUDE CATV,TELEPHONE,SPEAKERS
 ETC. PLEASE NOTE SEPARATE LV PERMIT
 IS REQ`D OR INCLUDE ON THIS PERMIT.
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED. MAINS
 /PANELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT. PER 110-9
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ROUGH INSPECTION.
 IF THERE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372