Plan Review Details - Permit 00110627
Plan Review Stops For Permit 00110627
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-19 Cont ID  
Sent By dpalmer Date 2000-12-19 Time 16:17 Rev Time 0.00
Received By dpalmer Date 2000-12-19 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 19:59 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 AND SIZE OF EXISTING SERVICE. PER
 220-3-C-1
  
  
 2)NOTE: PLEASE SHOW RISER DIAGRAM WITH
 NEW EQUIPMENT BEING INSTALLED. PLEASE
 SHOW ALL GROUNDING FOR NEW EQUIPMENT AND
 BONDING OF NEW BLDG STEEL. PER 250-50
  
 3)NOTE: PLEASE SUBMIT PANEL SHEDULES FOR
 NEW PANEL SHOWN. PLEASE INCLUDE THE
 REQ`D BATH(S) CIRCUIT(S) PER 210-11-C-3
 MUST BE #12 AND 20A.
  
 4)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS OR ROOMS
 THAT CAN BE CONVERTED TO SLEEPING ROOMS.
 THESE ROOMS ARE ANY ROMMS WITH ADJACENT
 CLOSETS OR BATHROOMS. THE ABOVE IS PER
 NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 OUTSIDE AREAS AS GFI/GFI PROTECTED.
 PER 210-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-05-21 Cont ID  
Sent By pkrauss Date 2001-05-21 Time 08:21 Rev Time 0.30
Received By pkrauss Date 2001-05-21 Time 08:21 Sent To  
Notes
2001-05-21 00:00:00LETTER FROM ARCHITECT DETAILING TIE
 DOWN FOR A/C PAD AND STATING APPLICATION
 WILL WITHSTAND 1500 LBS. OF UPLIFT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-16 Cont ID  
Sent By jleech Date 2000-12-16 Time 11:34 Rev Time 0.33
Received By jleech Date 2000-12-16 Time 11:33 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 CONDENSOR TO BE 12 SEER TO MATCH ENERGY
 CAULKS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-02 Cont ID  
Sent By jleech Date 2000-12-02 Time 13:39 Rev Time 0.25
Received By jleech Date 2000-12-02 Time 13:38 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-19 Cont ID  
Sent By kstevens Date 2001-05-19 Time 07:14 Rev Time 0.25
Received By kstevens Date 2001-05-19 Time 07:14 Sent To  
Notes
2001-05-19 00:00:00REVIEW NOTES. PASSED
  
 LETTER FROM ARCHITECT DELETING BAR SINK
 FOR FUTURE.DATED MAY 17,2001 S.J.BRUH
  
 KSTEVENS

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-03-08 Cont ID  
Sent By jleech Date 2001-03-08 Time 12:19 Rev Time 0.25
Received By jleech Date 2001-03-08 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-12-02 Cont ID  
Sent By jleech Date 2000-12-02 Time 13:39 Rev Time 0.25
Received By jleech Date 2000-12-02 Time 13:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2001-03-07 Cont ID  
Sent By jgomez Date 2001-03-07 Time 08:42 Rev Time 0.25
Received By jgomez Date 2001-03-07 Time 08:42 Sent To  
Notes
2001-03-07 00:00:00TRUSS DRAWINGS APPROVED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-02-27 Cont ID  
Sent By jgomez Date 2001-02-27 Time 18:22 Rev Time 0.50
Received By jgomez Date 2001-02-27 Time 18:22 Sent To  
Notes
2001-02-27 00:00:00TRUSS DRAWINGS 2ND CHECKLIST:
  
 1-THE FOLLOWING COMMENTS FROM PREVIOUS
 CHECKLIST WERE NOT ADDRESSED:
 A)ALLTRUSS DRAWINGS TO HAVE ORIGINAL
 SEAL, SIGNATURE AND DATE AS REQUIRED
 BY CHAPTER 471 OF FLORIDA STATUTES
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORD.
 B)UPDATE ALL GENERAL TRUSS DETAILS AS
 REQUIRED AND SEAL, SIGN AND DATE THEM
 AS REQUIRED BY CHAPTER 471 FL STATUTES
  
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-02-12 Cont ID  
Sent By jgomez Date 2001-02-12 Time 10:37 Rev Time 1.00
Received By jgomez Date 2001-02-12 Time 10:36 Sent To  
Notes
2001-02-12 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE. PROVIDE STAMP FROM DESIGNER OF
 RECORD FIRM FOR REVIEW OF TRUSS DWGS.
 2-ALL ENGINEERED TRUSS DRAWINGS TO HAVE
 ORIGINAL SEAL, SIGNATURE AND DATE AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 3-UPDATE ALL GENERAL TRUSS DETAILS AND
 SIGN, SEAL AND DATE THEM AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES.
 4-ATTIC WITH STORAGE TRUSSES TO BE
 DESIGN FOR 60# PSF AS REQUIRED ON
 ARCHITECT'S ROOF FRAMING PLAN.
 5-MEAN ROOF HEIGHT CONSIDERED BY
 ARCHITECT IS 18'-0". REVISE ENGINEERED
 TRUSS DRAWINGS AS REQUIRED.
  
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-12-27 Cont ID  
Sent By jgomez Date 2000-12-27 Time 16:57 Rev Time 2.00
Received By jgomez Date 2000-12-27 Time 16:57 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
  
 1-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS THAT MATCH ASSEMBLY SHOWN
 ON ARCHITECTURAL PLANS: THREE PANELS.
 -PRODUCT APPROVAL SUBMITTED IS FOR FOUR
 PANELS AS SHOWN ON APPROVED DRAWINGS.
 SEE SECTION 3, LIMITATIONS, OF PRODUCT
 APPROVAL REPORT.
 -SUBMIT IT PRIOR TO SGD INSTALLATION.
 2-GAS GRILLE TO HAVE UL LISTING AND
 INSTALLATION SPECIFICATIONS FOR
 INSPECTOR INSPECTION.
  
  
  
  
  
 NOTE:
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-12-09 Cont ID  
Sent By jgomez Date 2000-12-09 Time 14:41 Rev Time 2.50
Received By jgomez Date 2000-12-09 Time 14:41 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY
 AND BRING STAMPED DRAWINGS AND RECEIPT
 2-ARCHITECT TO DATE DRAWINGS WHEN
 SUBMITTING FOR PUBLIC RECORDS. CHAPTER
 481 FLORIDA STATUTES.
 3-PROVIDE PRODUCT APPROVAL FOR:
 -ROOF TILE
 -SLIDING GLASS DOORS (PRODUCT APPROVAL
 SUBMITTED IS FOR 2 PANELS ONLY)
 -UL LISTING AND SPECS FOR BBQ.
 -SINGLE HUNG WINDOWS PRODUCT APPROVAL
 IS MISSING DRAWINGS. ALSO, MAKE SURE
 DRAWINGS ARE LEGIBLE WHEN RESUBMITTING
 4-SPECIFY HOW IS VENTILATION PROVIDED TO
 STORAGE ROOM. PROVIDE HVAC DRAWINGS.
 SECTION 1203.1.4 SBC 1997.
 5-PROVIDE SOIL TEST REPORT.
 6-SEE ADDITIONAL COMMENTS ON PLANS AND
 REVISE ORIGINAL DRAWINGS AS REQUIRED.
 INCLUDING COMMENTS BY THE OTHER TRADES
 7-ROOF FRAMING PLAN: SPECIFY UPLIFT
 CALCULATIONS AND PROVIDE TRUSS ANCHOR
 SCHEDULE.
 8-REVISE DESIGN CERTIFICATION FOR WIND
 LOAD COMPLIANCE FORM (USE ATTACHED
 UPDATED FORM):
 -VELOCITY PRESSURE IS INCORRECT. SEE
 TABLE 1606.2A SBC 1997.
 -SBC DOESN'T USE THE COASTAL EXPOSURE.
 SEE CHAPTER 16 SBC 1997.
 -NEED ORIGINAL SIGNATURE AND DATE.
 CHAPTER 481 OF FLORIDA STATUTES.
 9-PROVIDE LINTEL SCHEDULE.
 SECTION 104.2.2 CITY AMENDMENTS TO SBC
 10-PROVIDE SURVEY WITH PROPOSED LAYOUT.
 SECTION 104.2.2 CITY AMENDMENTS.
 11-OWNER TO SIGN AND DATE THE ENERGY
 CALCULATIONS.
  
  
  
  
  
  
 NOTES:
 - PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.
 - IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 - A/C DRAWINGS WERE SUBMITTED AFTER ALL
 REVIEWS WERE DONE. PLEASE RESUBMIT
 A/C DRAWINGS WHEN RESUBMITTING ALL
 PACKAGE.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-29 Cont ID  
Sent By sgraham Date 2000-11-29 Time 15:07 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***