| Plan Review Stops For Permit 00110544 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-27 |
Time |
14:56 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
N |
Date |
2001-03-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-03-27 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-15 00:00:00 | SHOP DRAWINGS FOR FRONT ELEVATIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-17 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-17 |
Time |
11:32 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-17 00:00:00 | ENERGY CALS NEED THE ARCHETECT OWNER OR | | | HIS AGENT TO SIGN THE SECOND SIGNATURE | | | BLOCK, BEFORE WE CAN ISSUE THE PERMIT. | | | JIMWITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-01-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-16 |
Time |
09:13 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-16 00:00:00 | 1). FL ENERGY CODE 400.3ABCD.2 THE | | | ENERGY CODE SHEETS TO BE SIGNED BY THE | | | OWNER OR AGENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-05 |
Time |
11:01 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: | | | 1). FL ENERGY CODE 400.3.ABCD.2 THE | | | BUILDINGS OWNER,THE OWNERS ARCHITECT, OR | | | OTHER AUTHORIZED AGENT LEGALLY | | | DESIGNATED BY THE OWNER SHALL CERTIFY TO | | | THE BUILDING OFFICIAL THAT HTE BUILDING | | | IS IN COMPLIANCE.SIGN ENERGY SHEETS. | | | 2). NOTE: TWO SETS OF CURRENT PRODUCT | | | APPROVAL REPORTS ARE REQUIRED FOR EACH | | | SET OF PLANS. | | | 3).NOTE: ALUMINIUNM WINDOW WALL SYSTEM | | | REPORT 94-1110.02 EXPIRED, THE TECHNICAL | | | DRAWINGS ARE NOT FOR THIS REPORT.THE | | | 98-1216.06 ARE CURRENT AND DO HAVE LARGE | | | MISSLE TESTING. WE WOULD NEED THE REPORT | | | THAT BACKS UP THE TECHNICAL DRAAWINGS. | | | | | | BUILDING PLAN REVIEW: | | | JIM WITMER | | | (561) 659-8096 EX 8412. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-11-20 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-20 |
Time |
12:40 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-11-20 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1]SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. | | | 2]SUBMIT PRODUCT APPROVALS FOR IMPACT | | | RESISTANT GLAZING FOR STOREFRONT AND | | | DOORS. METRO DADE COUNTY OR SBCCI | | | 3]SUBMIT LETTER FROM SPECIAL INSPECTOR. | | | 4]SUBMIT FLORIDA ENERGY SHEETS SIGNED | | | AND SEALED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-12-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-26 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-26 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-30 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-30 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE THE REQ`MENTS OF THE | | | F.A.C SEC. 553-79-6A. PLANS ARE TO SIGN- | | | -ED AND SEALED BY AN P.E. UNDER 471.025 | | | | | | 2)NOTE" PLEASE SUBMIT AND SHOW AIC RAT- | | | -INGS FOR ALL NEW EQUIPMENT AND BRKRS | | | BEING INSTALLED. ALL MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9 | | | | | | 3)NOTE: PLEASE NOTE THAT A MAIN DISC/ | | | MCB IS REQ`D ON THE LOAD SIDE OF THE | | | TANSFORMER. | | | | | | 4)NOTE: PLEASE PROVIDE MORE DETAIL FOR | | | WIRES/CONDUIT SIZES FROM DISC TO TRANS. | | | | | | 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% AND ALL TRACK LIGHTING PER NEC | | | ART; 220-12B | | | | | | 6)NOTE:PLEASE SHOW TRANSFORMER SIZE?? | | | | | | 7)NOTE: PLEASE SHOW GROUNDING FOR THE | | | TRANSFORMER FOR SEP DERIVED SYSTEM. | | | | | | 8)NOTE: PLEASE SHOW LOCATIONS FOR ALL | | | EQUIPMENT BEING INSTALLED. PER 215-5 | | | | | | 9)NOTE:PLEASE SHOW ON PLAN THE COLOR | | | CODING FOR WIRING PER LOCAL CODE/AMEND. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFOMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELETRICALPLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-20 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-20 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-21 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-21 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE ALARM EQUIPMENT SHOWN ON | | | PLANS. | | | 2) SOFFITS ARE NOT TO INTERFERE WITH | | | ANY FIRE SPRINKLER HEAD DISCHARGE | | | PATTERNS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-11-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-30 |
Time |
10:45 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-11-30 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | LOCATE AHU WITH RESPECT TO BUILDING | | | CONSTRUCTION TO ALLOW FOR SERVICE AND | | | REMOVAL OF EQUIPMENT AND COMPONENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-17 |
Time |
09:40 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-17 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-01-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-03 |
Time |
15:04 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-01-03 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DRINKING FOUNTAIN MUST BE ACCESSIBLE. | | | NOT ACCESSIBLE TO PUBLIC IF INSTALLED | | | IN STOCK ROOM. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-12-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-03 |
Time |
11:31 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1)SHT 3/3 SPC 94 SEC 407.2.2 DRINKING | | | FOUNTAIN REQ.TO BE H/C AND ACCESSIBLE TO | | | THE PUBLIC.FACBC 4.1.3 (10)(A) | | | FOR PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. | | | (2) SHT 3/3 AIR CHAMBERS TO BE | | | ACCESSIBLE & RECHARGEABLE,SPC 94 | | | SEC 607.8.3 | | | END OF COMMENTSPAUL SCHMITZ | | | 561-659-8096X 8233 |
|
|