Plan Review Details - Permit 00110543
Plan Review Stops For Permit 00110543
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-27 Cont ID  
Sent By jwitmer Date 2001-03-27 Time 14:23 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By lmartine Date 2001-01-17 Time 16:51 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-30 Cont ID  
Sent By drunnels Date 2000-11-30 Time 11:11 Rev Time 1.00
Received By drunnels Date 2000-11-30 Time 11:11 Sent To  
Notes
2001-01-08 00:00:001]SUBMIT PRODUCT APPROVALS FOR IMPACT
 RESISTANCT GLAZING FOR STOREFRONT
 WINDOWS AND DOORS
 2]SUBMIT LETTER FROM SPECIAL INSPECTOR
 3]SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.
 4]GENERAL CONTRACTOR NEEDS TO MAKE
 APPLICATION FOR PERMIT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-03-26 Cont ID  
Sent By dpalmer Date 2001-03-26 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2001-03-26 Time 14:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 18:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-11-17 Cont ID  
Sent By mcarsill Date 2000-11-17 Time 15:15 Rev Time 0.00
Received By mcarsill Date 2000-11-17 Time 15:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 11:05 Rev Time 0.50
Received By ndenmark Date 2000-12-14 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 SEPARATE PERMITS REQUIRED FOR HOODS AND
 GREASE DUCTS AND WALK IN COOLER/FREEZERS
 SUBMIT PLANS AT TIME OF PERMIT APPLICA-
 TION

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By jleech Date 2001-01-17 Time 07:16 Rev Time 0.33
Received By jleech Date 2001-01-17 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-14 Cont ID  
Sent By pschmitz Date 2000-12-03 Time 07:50 Rev Time 1.00
Received By jleech Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW DENIED
 (1) SHT MP-1 H/C REST RM'S TO BE ACCESS-
 IBLE TO THE PUBLIC,FACBC SEC.4.1.3(1)(11
 (16)(A).
 (2) SHT MP-1 AIR CHAMBERS SPC 94 607.8.3
 CALCULATED AIR CHAMBERS TO BE ACCESSIBLE
 & RECHARGEABLE.
 END OF COMMENTS PAUL SCHMITZ