Plan Review Details - Permit 00110504
Plan Review Stops For Permit 00110504
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-12 Cont ID  
Sent By jwitmer Date 2001-02-12 Time 11:56 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-12 00:00:00PLUMB TO SUPPLY SEPERATE PLANS, PERMIT &
 FEES. CONT. LETTER 02/12/01 JW
 PROVISO: SHOP DRAWINGS REQUIRED FOR
 FIRE ESCAPE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-09 Cont ID  
Sent By lmartine Date 2001-01-09 Time 18:14 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-10 00:00:00BUILDING COMMENTS
 -------------------
  
 1]
 DRAWINGS SHALL BE REVIEWED FOR COUNTY
 IMPACT FEES.
 2]
 SECOND MEANS OF EGRESS SHALL COMPLY WITH
 1004.1,SBC, FIRE ESCAPE EXIT IS NOT
 CONSIDERED AS AN APPROVED EGRESS.
 3]
 EXTERIOR STAIR SHALL COMPLY WITH 1007.3
 AND 1007.4,SBC,[TREADS AND RISERS
 RATIO,LANDIGS].
 4]
 SUBMIT DETAILS AND CALCULATIONS FOR
 FLOOR LOADING AND WALKING SURFACE AT
 SECOND LEVEL DECK AREA.
 EXSISTING LOW WALL/GUARDRAIL SHALL
 COMPLY WITH 1015.2 AND 1608.2,SBC.
 5]
 704.3.1,SBC, SUBMIT DETAILS OF EXSISTING
 PARTITIONS,1HR TENENT SEPERATION.
 704.2.4 ALLOWS 1/2HR. CORRIDOR WALLS
 WITH 20 MIN. DOORS, SUBMIT DETAILS.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-09 Cont ID  
Sent By lmartine Date 2001-01-09 Time 06:49 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-09 00:00:00BUILDING COMMENTS
 -------------------
  
 1]
 SUBMIT DRAWINGS AND APPLICATION TO PALM
 BEACH COUNTY IMPACT FEE OFFICE FOR
 REVIEW.
 2]
 THE FIRE ESCAPE STAIR CANNOT BE
 CONSIDERED AS HE SECOND MEANS OF EGESS

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-08 Cont ID  
Sent By dpalmer Date 2001-02-08 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2001-02-08 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 22:04 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 22:04 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THE ENTIRE
 STRUCTURE IS BEING RE-DONE. THE HEIGHT
 OF ALL DEVICES NEED TO MEET THE REQ`D
 HEIGHTS GIVEN IN CHAPTER 5 OF THE FAIR
 HOUSING ACT,24 CFR 100.205
  
 2)NOTE: PLEASE NOTE PER 210-63 MISSING
 ROOFTOP GFI`S FOR A/C EQUIPMENT.
  
 3)NOTE:PLEASE NOTE THAT PLANS ARE SHOW-
 -ING J-BOXES BEING SWITCHED. MEANS OF
 EGRESS LIGHITNG IS REQUIRED ANDNEEDS
 TO BE SHOWN PER 210-70
  
 4)NOTE: PLEASE SEE E3.1 FOR STORAGE ROOM
 AS PER LOCAL CODE OUTLET SPACING TO MEET
 210-50.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-01-26 Cont ID  
Sent By mcarsill Date 2001-01-26 Time 14:28 Rev Time 0.00
Received By mcarsill Date 2001-01-26 Time 14:28 Sent To  
Notes
2001-01-26 00:00:001) CODE ANALYSIS BOX INCORRECT. TRAVEL
 DISTANCE FOR EXISTING APARTMENTS AND
 MERCANTILE OCCUPANCIES WHEN SPRINKLERED
 IS 150 FEET.
 2) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS. CUT SHEETS,
 WIRING DIAGRAM AND BATTERY CALCULATIONS
 ARE TO BE PROVIDED. THE FIRE ALARM NOTES
 SECTION INDICATES CLASS B, STYLE C
 CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS
 OR FULLY ADDRESSABLE WILL BE PERMITTED.
 ALSO DUCT SMOKE DETECTORS MUST ACTIVATE
 THE FIRE ALARM SYSTEM AND NOT JUST
 A SUPERVISORY SIGNAL. SEPARATE PLANS
 AND PERMITS REQUIRED.
 3) EXIT DOORS CANNOT SWING ONTO
 SIDEWALKS. EXIT DOORS MUST BE RECESSED.
 4) FIRE SEPARATIONS BETWEEN MERCANTILE
 AND RESIDENTIAL OCCUPANCIES TO COMPLY
 WITH BUILDING CODE REGULATIONS.
 5) THE FIRE SPRINKLER DRAWINGS THAT
 WERE ATTACHED MUST BE SUBMITTED UNDER
 A SEPARATE PERMIT TO THE CONSTRUCTION
 SERVICES DEPARTMENT. THE FIRE DEPARTMENT
 CONNECTION MUST BE LOCATED NO FARTHER
 THAN 150 FEET FROM A FIRE HYDRANT.
 6) ALL EXITS TO COMPLY WITH THE
 REQUIREMENTS OF NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-14 Cont ID  
Sent By mcarsill Date 2000-11-14 Time 10:22 Rev Time 0.00
Received By mcarsill Date 2000-11-14 Time 09:01 Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 BE INSTALLED ON BUILDING AND COMPLY WITH
 CITY CODE REQUIREMENTS.
 2) DOOR SWING IMPROPER ON MERCANTILE
 SPACE THAT DISPLAYS A 77 FOOT MAXIMUM
 TRAVEL DISTANCE. THE OCCUPANT LOAD
 IS MORE THAN 50, SO EXIT DOORS SHALL
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 3) FIRE SPRINKLER SYSTEM, FIRE
 RESCUE CONNECTION SHOWN ON SPRINKLER
 DRAWINGS TO BE NO MORE THAN 150 FEET
 FROM A FIRE HYDRANT. ENTIRE BUILDING TO
 BE COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL ELECTRICAL, MECHANICAL
 AND SERVICE ROOMS. ALSO VERTICAL SHAFTS.
 4) ELEVATION DRAWINGS DO NOT INCLUDE
 HEIGHTS.
 5) FUTURE TENANT SPACES TO BE AT LEAST
 ONE HOUR FIRE SEPARATED FROM ONE
 ANOTHER.
 6) DOORS TO APARTMENTS TO BE AT LEAST
 20 MINUTE FIRE DOORS EQUIPPED WITH
 SELF-CLOSING DEVICES.
 7) INTERIOR CORRIDOR WALLS TO BE AT
 LEAST 1/2 HOUR FIRE RATED.
 8) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON THE DRAWINGS. CUT SHEETS, FLOOR
 PLANS AND WIRING DIAGRAM REQUIRED.
 9) A KNOX-BOX WILL BE REQUIRED FOR
 FIRE RESCUE ACCESS.
 10) NO FIRE EXTINGUISHERS SHOWN.
 11) NO OPENINGS ARE ALLOWED WITHIN 10
 FEET OF EXIT STAIRS. IF OPENINGS ARE
 PRESENT, THEY ARE TO BE PROTECTED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-08 Cont ID  
Sent By ndenmark Date 2001-02-08 Time 13:02 Rev Time 0.33
Received By ndenmark Date 2001-02-08 Time 13:02 Sent To  
Notes
2001-02-08 00:00:00PROVISO:
 PRIOR COMMENTS ACCEPTED BY REVISION AND
 COMMENTS DATED 2/8/01 BY THIS OFFICE
 WITH THE PROVISO THAT THE DRYER EXHAUST
 DUCT PENETRATING RATED WALLS SHALL
 COMPLY WITH ALL 4 PARTS OF 610.1.3.
 26 GA. METAL
 5 FOOT RUN ON BOTH SIDES OF THE RATED
 WALL BEFORE ANY OPENING
 UNDER 100 SQ. IN.
 AND THE DUCT SHALL BE ABOVE A CEILING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 11:21 Rev Time 0.50
Received By ndenmark Date 2000-12-14 Time 11:21 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1.EXHAUST DUCT PENETRATING RATED WALLS
 TO HAVE FIRE DAMPERS PER 610.1.2 OR
 COMPLY WITH ALL 4 PARTS OF 610.1.3 (3)
 EXCEPTIONS.
 2. DRYER VENTS DO NOT COMPLY WITH 1997
 SMC 613.4 OR 509.
 EACH DRYER VENT DUCT SHALL BE RUN TO
 THE OUTSIDE OF THE BUILDING IN A DIRECT
 AS POSSIBLE MANNER.
 FIRE DAMPERS SHALL BE SPECIFICALLY
 LISTED FOR USE IN THE DRYER EXHAUST
 SYSTEM.
 DETAILS ON CONNECTION OF TWO OR MORE
 DRYER VENTS NEED TO BE PROVIDED FOR
 REVIEW.
 ACCESS FOR CLEANING THE ENTIRE DUCT
 SYSTEM SHALL BE PROVIDED. SHOW DETAILS
 ON PLANS.
 NO DUCTS ARE SHOWN FOR THE THIRD
 FLOOR LAUNDRY.
 MULTIPLE FAMILY USE OF THIS EQUIPMENT
 REQUIRES COMMERCIAL DESIGN OF THE DUCT
 SYSTEM. SHOW DUCT TYPE AND CLEARANCE
 FROM COMBUSTIBLE DETAIL SHOWING COMPLI-
 ANCE WITH 1997 SMC 509.4.
 3. PROVIDE OUTSIDE AIR CALCULATIONS
 SHOWING COMPLIANCE W/ ASHRAE 62-89.

Review Stop P PLUMBING
Rev No 2 Status N Date 2001-02-12 Cont ID  
Sent By pschmitz Date 2001-02-11 Time 07:04 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-12 00:00:002/12/01 GENERAL CONT. DELETE PLUMB TO
 COME IN WITH SEPERATE PLANS PERMIT &
 FEES. 02/12/01 JW
2001-02-11 00:00:00PLUMBING PLAN REVIEW 2ND TIME DENIED
 REFERENCES STD PLBG CODE 94
 RE: COMMENTS FROM KAMM CONSULTING INC
 DATED 01-17-01
 (1)SHT.P0.1 WTR HTR DETAIL CONFLICTS
 WITH NOTE # 1, COMMENTS.T/P,P/D TO BE
 READLY OBSERVIBLE. SEC 507.8.4 PAN DRAIN
 1", T/P 3/4" ALL INDIRECT WASTE TO FLOOR
 SINKS, THIS LOCATION IS NOT READLY
 OBSERVIBLE SEC 507.8.4
 (2) WATER HEATER IN CORNER KITCHEN
 CABNET IS NOT READLY ACCESSIBLE.SEC501.7
 T/P,PAN DRAIN,SHALL BE READLY OBSERVED,
 SEC 507.8.4
 (3)SHT.P-5.1DWV ISOMETRIC,IS NOT
 COMPLETE, SHOW ENTIRE SYSTEM SEC 104.3
 (4) SHT P2.2 NEW COMMENT SEC 409.4.5
 ROOMS CONTANING LAUNDARY MACHINES SHALL
 BE PROVIDED WITH A FLOOR DRAIN.
 END OF COMMENTS QUESTIONS PAUL SCHMITZ
 561-659-8096

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-02-12 Cont ID  
Sent By jleech Date 2000-11-28 Time 10:53 Rev Time 3.00
Received By jwitmer Date 2000-11-28 Time 10:53 Sent To  
Notes
2001-01-08 00:00:001.WATER HEATER PAN DRAINS AND RELIOF
 LINES MUST RUN TO THE OUTSIDE. 94 SPC.
 507.8.4 AND 807.3.
  
 2.WATER HEATERS MUST BE READILY ACCESS-
 IBLE. CABINET MUST HAVE A DOOR THAT
 OPENS WITHOUT USING TOOLS AND OPENING
 MUST BE LARGER THAN WATER HEATER.
 PLEASE SHOW DETAIL.
  
 3.P6.1,EACH APARTMENT MUST HAVE AN
 ACCESSIBLE SHUTOFF VALVE AHEAD OF THE
 FIRST BRANCH CONNECTION. 610.1.
  
 4.SHUTOFF VALVES REQUIRED FOR LAUNDRY
 FACILITIES.
  
 5.SHOW SHUTOFF VALVES AT THE BASE OF
 EACH RISER ON WATER RISER DIAGRAM AS
 SHOWN ON PAGE P3.1.
  
 6.SANITARY RISER DIAGRAM REQUIRED.
 PAGE P5.1 NOT WITH PLANS.
  
 7.PAGE P0.1 NOTE #10 WATER DISTRIBUTION
 PIPING BELOW GROUND MUST BE MINIMUM
 "L" COPPER PIPE. CITY AMENDMENTS 611.3
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377