| Plan Review Stops For Permit 00110504 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-02-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-02-12 |
Time |
11:56 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-12 00:00:00 | PLUMB TO SUPPLY SEPERATE PLANS, PERMIT & | | | FEES. CONT. LETTER 02/12/01 JW | | | PROVISO: SHOP DRAWINGS REQUIRED FOR | | | FIRE ESCAPE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-01-09 |
Time |
18:14 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-10 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1] | | | DRAWINGS SHALL BE REVIEWED FOR COUNTY | | | IMPACT FEES. | | | 2] | | | SECOND MEANS OF EGRESS SHALL COMPLY WITH | | | 1004.1,SBC, FIRE ESCAPE EXIT IS NOT | | | CONSIDERED AS AN APPROVED EGRESS. | | | 3] | | | EXTERIOR STAIR SHALL COMPLY WITH 1007.3 | | | AND 1007.4,SBC,[TREADS AND RISERS | | | RATIO,LANDIGS]. | | | 4] | | | SUBMIT DETAILS AND CALCULATIONS FOR | | | FLOOR LOADING AND WALKING SURFACE AT | | | SECOND LEVEL DECK AREA. | | | EXSISTING LOW WALL/GUARDRAIL SHALL | | | COMPLY WITH 1015.2 AND 1608.2,SBC. | | | 5] | | | 704.3.1,SBC, SUBMIT DETAILS OF EXSISTING | | | PARTITIONS,1HR TENENT SEPERATION. | | | 704.2.4 ALLOWS 1/2HR. CORRIDOR WALLS | | | WITH 20 MIN. DOORS, SUBMIT DETAILS. | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 561-659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-09 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-01-09 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-09 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1] | | | SUBMIT DRAWINGS AND APPLICATION TO PALM | | | BEACH COUNTY IMPACT FEE OFFICE FOR | | | REVIEW. | | | 2] | | | THE FIRE ESCAPE STAIR CANNOT BE | | | CONSIDERED AS HE SECOND MEANS OF EGESS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-08 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-08 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
22:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
22:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE ENTIRE | | | STRUCTURE IS BEING RE-DONE. THE HEIGHT | | | OF ALL DEVICES NEED TO MEET THE REQ`D | | | HEIGHTS GIVEN IN CHAPTER 5 OF THE FAIR | | | HOUSING ACT,24 CFR 100.205 | | | | | | 2)NOTE: PLEASE NOTE PER 210-63 MISSING | | | ROOFTOP GFI`S FOR A/C EQUIPMENT. | | | | | | 3)NOTE:PLEASE NOTE THAT PLANS ARE SHOW- | | | -ING J-BOXES BEING SWITCHED. MEANS OF | | | EGRESS LIGHITNG IS REQUIRED ANDNEEDS | | | TO BE SHOWN PER 210-70 | | | | | | 4)NOTE: PLEASE SEE E3.1 FOR STORAGE ROOM | | | AS PER LOCAL CODE OUTLET SPACING TO MEET | | | 210-50. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-01-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-26 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-26 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2001-01-26 00:00:00 | 1) CODE ANALYSIS BOX INCORRECT. TRAVEL | | | DISTANCE FOR EXISTING APARTMENTS AND | | | MERCANTILE OCCUPANCIES WHEN SPRINKLERED | | | IS 150 FEET. | | | 2) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS. CUT SHEETS, | | | WIRING DIAGRAM AND BATTERY CALCULATIONS | | | ARE TO BE PROVIDED. THE FIRE ALARM NOTES | | | SECTION INDICATES CLASS B, STYLE C | | | CIRCUITS. ONLY CLASS A, STYLE D CIRCUITS | | | OR FULLY ADDRESSABLE WILL BE PERMITTED. | | | ALSO DUCT SMOKE DETECTORS MUST ACTIVATE | | | THE FIRE ALARM SYSTEM AND NOT JUST | | | A SUPERVISORY SIGNAL. SEPARATE PLANS | | | AND PERMITS REQUIRED. | | | 3) EXIT DOORS CANNOT SWING ONTO | | | SIDEWALKS. EXIT DOORS MUST BE RECESSED. | | | 4) FIRE SEPARATIONS BETWEEN MERCANTILE | | | AND RESIDENTIAL OCCUPANCIES TO COMPLY | | | WITH BUILDING CODE REGULATIONS. | | | 5) THE FIRE SPRINKLER DRAWINGS THAT | | | WERE ATTACHED MUST BE SUBMITTED UNDER | | | A SEPARATE PERMIT TO THE CONSTRUCTION | | | SERVICES DEPARTMENT. THE FIRE DEPARTMENT | | | CONNECTION MUST BE LOCATED NO FARTHER | | | THAN 150 FEET FROM A FIRE HYDRANT. | | | 6) ALL EXITS TO COMPLY WITH THE | | | REQUIREMENTS OF NFPA 101, THE LIFE | | | SAFETY CODE, 1985 EDITION. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-14 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-14 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | BE INSTALLED ON BUILDING AND COMPLY WITH | | | CITY CODE REQUIREMENTS. | | | 2) DOOR SWING IMPROPER ON MERCANTILE | | | SPACE THAT DISPLAYS A 77 FOOT MAXIMUM | | | TRAVEL DISTANCE. THE OCCUPANT LOAD | | | IS MORE THAN 50, SO EXIT DOORS SHALL | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | 3) FIRE SPRINKLER SYSTEM, FIRE | | | RESCUE CONNECTION SHOWN ON SPRINKLER | | | DRAWINGS TO BE NO MORE THAN 150 FEET | | | FROM A FIRE HYDRANT. ENTIRE BUILDING TO | | | BE COMPLETELY FIRE SPRINKLER PROTECTED. | | | THIS INCLUDES ALL ELECTRICAL, MECHANICAL | | | AND SERVICE ROOMS. ALSO VERTICAL SHAFTS. | | | 4) ELEVATION DRAWINGS DO NOT INCLUDE | | | HEIGHTS. | | | 5) FUTURE TENANT SPACES TO BE AT LEAST | | | ONE HOUR FIRE SEPARATED FROM ONE | | | ANOTHER. | | | 6) DOORS TO APARTMENTS TO BE AT LEAST | | | 20 MINUTE FIRE DOORS EQUIPPED WITH | | | SELF-CLOSING DEVICES. | | | 7) INTERIOR CORRIDOR WALLS TO BE AT | | | LEAST 1/2 HOUR FIRE RATED. | | | 8) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON THE DRAWINGS. CUT SHEETS, FLOOR | | | PLANS AND WIRING DIAGRAM REQUIRED. | | | 9) A KNOX-BOX WILL BE REQUIRED FOR | | | FIRE RESCUE ACCESS. | | | 10) NO FIRE EXTINGUISHERS SHOWN. | | | 11) NO OPENINGS ARE ALLOWED WITHIN 10 | | | FEET OF EXIT STAIRS. IF OPENINGS ARE | | | PRESENT, THEY ARE TO BE PROTECTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-02-08 |
Time |
13:02 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-02-08 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2001-02-08 00:00:00 | PROVISO: | | | PRIOR COMMENTS ACCEPTED BY REVISION AND | | | COMMENTS DATED 2/8/01 BY THIS OFFICE | | | WITH THE PROVISO THAT THE DRYER EXHAUST | | | DUCT PENETRATING RATED WALLS SHALL | | | COMPLY WITH ALL 4 PARTS OF 610.1.3. | | | 26 GA. METAL | | | 5 FOOT RUN ON BOTH SIDES OF THE RATED | | | WALL BEFORE ANY OPENING | | | UNDER 100 SQ. IN. | | | AND THE DUCT SHALL BE ABOVE A CEILING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-14 |
Time |
11:21 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-12-14 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1.EXHAUST DUCT PENETRATING RATED WALLS | | | TO HAVE FIRE DAMPERS PER 610.1.2 OR | | | COMPLY WITH ALL 4 PARTS OF 610.1.3 (3) | | | EXCEPTIONS. | | | 2. DRYER VENTS DO NOT COMPLY WITH 1997 | | | SMC 613.4 OR 509. | | | EACH DRYER VENT DUCT SHALL BE RUN TO | | | THE OUTSIDE OF THE BUILDING IN A DIRECT | | | AS POSSIBLE MANNER. | | | FIRE DAMPERS SHALL BE SPECIFICALLY | | | LISTED FOR USE IN THE DRYER EXHAUST | | | SYSTEM. | | | DETAILS ON CONNECTION OF TWO OR MORE | | | DRYER VENTS NEED TO BE PROVIDED FOR | | | REVIEW. | | | ACCESS FOR CLEANING THE ENTIRE DUCT | | | SYSTEM SHALL BE PROVIDED. SHOW DETAILS | | | ON PLANS. | | | NO DUCTS ARE SHOWN FOR THE THIRD | | | FLOOR LAUNDRY. | | | MULTIPLE FAMILY USE OF THIS EQUIPMENT | | | REQUIRES COMMERCIAL DESIGN OF THE DUCT | | | SYSTEM. SHOW DUCT TYPE AND CLEARANCE | | | FROM COMBUSTIBLE DETAIL SHOWING COMPLI- | | | ANCE WITH 1997 SMC 509.4. | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS | | | SHOWING COMPLIANCE W/ ASHRAE 62-89. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2001-02-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-02-11 |
Time |
07:04 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-12 00:00:00 | 2/12/01 GENERAL CONT. DELETE PLUMB TO | | | COME IN WITH SEPERATE PLANS PERMIT & | | | FEES. 02/12/01 JW | | 2001-02-11 00:00:00 | PLUMBING PLAN REVIEW 2ND TIME DENIED | | | REFERENCES STD PLBG CODE 94 | | | RE: COMMENTS FROM KAMM CONSULTING INC | | | DATED 01-17-01 | | | (1)SHT.P0.1 WTR HTR DETAIL CONFLICTS | | | WITH NOTE # 1, COMMENTS.T/P,P/D TO BE | | | READLY OBSERVIBLE. SEC 507.8.4 PAN DRAIN | | | 1", T/P 3/4" ALL INDIRECT WASTE TO FLOOR | | | SINKS, THIS LOCATION IS NOT READLY | | | OBSERVIBLE SEC 507.8.4 | | | (2) WATER HEATER IN CORNER KITCHEN | | | CABNET IS NOT READLY ACCESSIBLE.SEC501.7 | | | T/P,PAN DRAIN,SHALL BE READLY OBSERVED, | | | SEC 507.8.4 | | | (3)SHT.P-5.1DWV ISOMETRIC,IS NOT | | | COMPLETE, SHOW ENTIRE SYSTEM SEC 104.3 | | | (4) SHT P2.2 NEW COMMENT SEC 409.4.5 | | | ROOMS CONTANING LAUNDARY MACHINES SHALL | | | BE PROVIDED WITH A FLOOR DRAIN. | | | END OF COMMENTS QUESTIONS PAUL SCHMITZ | | | 561-659-8096 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-02-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-28 |
Time |
10:53 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2000-11-28 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.WATER HEATER PAN DRAINS AND RELIOF | | | LINES MUST RUN TO THE OUTSIDE. 94 SPC. | | | 507.8.4 AND 807.3. | | | | | | 2.WATER HEATERS MUST BE READILY ACCESS- | | | IBLE. CABINET MUST HAVE A DOOR THAT | | | OPENS WITHOUT USING TOOLS AND OPENING | | | MUST BE LARGER THAN WATER HEATER. | | | PLEASE SHOW DETAIL. | | | | | | 3.P6.1,EACH APARTMENT MUST HAVE AN | | | ACCESSIBLE SHUTOFF VALVE AHEAD OF THE | | | FIRST BRANCH CONNECTION. 610.1. | | | | | | 4.SHUTOFF VALVES REQUIRED FOR LAUNDRY | | | FACILITIES. | | | | | | 5.SHOW SHUTOFF VALVES AT THE BASE OF | | | EACH RISER ON WATER RISER DIAGRAM AS | | | SHOWN ON PAGE P3.1. | | | | | | 6.SANITARY RISER DIAGRAM REQUIRED. | | | PAGE P5.1 NOT WITH PLANS. | | | | | | 7.PAGE P0.1 NOTE #10 WATER DISTRIBUTION | | | PIPING BELOW GROUND MUST BE MINIMUM | | | "L" COPPER PIPE. CITY AMENDMENTS 611.3 | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|