Plan Review Details - Permit 00110398
Plan Review Stops For Permit 00110398
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-05-07 Cont ID  
Sent By lmartine Date 2001-05-07 Time 15:50 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-04-04 Cont ID  
Sent By lmartine Date 2001-04-04 Time 16:30 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-04-04 00:00:00OUTDOOR PATIO REVISION
  
 1]
 PROVIDE COPYS OF SIGNED RESOLUTIONS.
 2]
 SPECIFY ACCESSIBLE SEATING. CLARIFY
 ACCESSIBLE ROUTE, APPROVED PLANS CALL
 FOR RAMPS.
 3]
 SUBMIT ELECTRICAL INFORMATION FOR
 REVIEW.
 4]
 SUPPLY INFORMATION FOR NEW BI-FOLD DOORS
 AND AWNINGS.
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-01-23 Cont ID  
Sent By jwitmer Date 2001-01-23 Time 12:56 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-23 00:00:00PROVISO:
 1)- A SITE PLAN SHOWING A PROTECTED
 EGRESS FROM THE INTERIOR ENTRANCE.
 2)- SBC 1606.4.1 / 1707.4.1: GLAZED
 OPENINGS WILL REQUIRE LARGE MISSLE
 IMPACT RESISTANCE TESTING OR STORM
 SHUTTER PROTECTION, DADE COUNTY PRODUCT
 APPROVAL REPORT OR SBCCI REPORT ARE
 ACCEPTABLE, A SEPERATE SSUB-PERMIT WILL
 BE REQUIRED. 01/23/01 J. WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-19 Cont ID  
Sent By jwitmer Date 2001-01-19 Time 08:44 Rev Time 6.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-19 00:00:00BUILDING PLAN REVIEW:
 1). FL. ACC. CODE 4.3.2.2- PROVIDE AN
 ACCESSIBLE ROUTE THROUGHOUT TO ALL
 LEVELS. A) HORSESHOE BENCH RAISED SEAT-
 ING 6 INCHES.
 B) BAR AREA UP ONE STEP, NO RAMP
 C) BENCH SEATS, RAISED WOOD
 PLATFORM 1'-0".
 2) FL.ACC. CODE 4.3.2.2/SBC 1019.10.1.2
 44" ACCESS AILES IN FRONT OF HORSESHOE
 BENCH SEATING.
 3) DISCREPANCY- LS-1 VS A101- ENTRANCE
 TO MENS /LADIES RESTROOMS.
 4) FL.ACC. CODE 4.1.3.6 MENS RESTROOM
 ENTRY WILL REQUIRE 24" FOR SIDE EXIT.
 5) DOOR #2 IS LISTED AS USE AS A EXIT
 DOOR, THIS IS PROHIBITED BY SBC 1012.1.2
 EGRESS DOORS SHALL BE SIDE SWINGING DOOR
 DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS WHEN SERVING AN OCCUPANT LOAD OF
 50 OR MORE.
 6) PROVIDE SITE PLAN TO SHOW SECOND EXIT
 IS PROTECTED THROUGH TO THE EXTERIOR.
 7) SBC TABLE 705.1.2- EXIT ACCESS DOOR
 AT THE KITCHEN/ OFFICE AREA NEEDS TO
 BE A 20 MINUTE RATED DOOR,
 8).SBC 1606.4.1/1707.4.1- ALL EXTERIOR
 GLAZING TO HAVE LARGE MISSLE IMPACT TEST
 ING BY DADE COUNTY OR SBCCI, REPORTS AS
 WELL AS THE TECHNICAL DRAWINGS THAT
 SUPPORT THE REPORT WILL BE REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096
 9) THE THIRD SET OF PLANS DOES NOT HAVE
 THE LIFE SAFETY PLAN IN IT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-08 Cont ID  
Sent By lmartine Date 2001-01-08 Time 12:10 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
  
 1]
 PROVIDE ACCESSIBILITY AT ENTRY AND AN
 ACCESSIBLE ROUTE THOUGHOUT.
 2]
 BI-FOLD DOORS AT PATIO AREA CANNOT BE
 CONSIDERED AS AN APPROVED EGRESS TYPE
 DOOR.
 3]
 PROVIDE SITE PLAN TO SHOW SECOND EXIT
 ISPROTECTED THRU TO THE OUTSIDE.
 4]
 SUBMIT LIFE SAFETY,EGRESS PLAN.
 5]
 EXPLAIN CLOSET,DOOR SHALL NOT OPEN INTO
 PATH OF EGRESS.
 6]
 DOOR #4 AT SERVICE CORRIDOR SHALL BE
 RATED.
 7]
 SUBMIT PRODUCT TESTING FORALL EXTERIOR
 DOORS AND GLAZING.
 8]
 PROVIDE MANUVERING CLEARENCE AT WOMENS
 RESTROOM ENTRANCE,SEE SECT.4.13.6
 F.A.C.B.C.[FIG. 25B].
 9]
 LANDING AT BOTTOM OF RAMP LEADING TO BAR
 AREA,SHALL BE CLEAR 48"X48", SEE F.A.C.
 B.C. 4.8.4.
 10]
 PROVIDE HANDRAILS ON BOTH SIDES OF RAMP
 AT MAIN DINING ROOM, SEE F.A.C.B.C. 4.8.
 5.
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-05-14 Cont ID  
Sent By dpalmer Date 2001-05-14 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2001-05-14 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 20:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 20:39 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE; MISSING AIC RATING
 OF PANELBOARD"K". PLEASE SHOW.
  
 2)NOTE: PLEASE SEE LOADING OF BRANCH
 BREAKERS. ALL CONTINUOUS LOADS ARE TO BE
 SHOWN AT 125%. (LIGHTING ETC) PLEASE
 SEE LOADS SHOWN, IF 125% IS ADDED THEN
 LOAD EXCEEDS 80% OF BREAKER PER 384-16D
 PLEASE SHOW ALL CONTINOUS LOADS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-04-05 Cont ID  
Sent By mcarsill Date 2001-04-05 Time 08:41 Rev Time 0.00
Received By mcarsill Date 2001-04-05 Time 08:40 Sent To  
Notes
2001-04-05 00:00:001) AWNINGS ARE TO BE FIRE RETARDANT
 IF PERSONS WILL BE UNDERNEATH IT.
 2) SEATING IS NOT TO INTERFERE WITH
 EXITING FROM INSIDE THE ASSEMBLY
 OCCUPANCY.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-01-25 Cont ID  
Sent By mcarsill Date 2001-01-25 Time 16:34 Rev Time 0.00
Received By mcarsill Date 2001-01-25 Time 16:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-01-11 Cont ID  
Sent By mcarsill Date 2001-01-11 Time 10:35 Rev Time 0.00
Received By mcarsill Date 2001-01-11 Time 10:35 Sent To  
Notes
2001-01-11 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 2) ALL SUNBRELLA AWNINGS TO BE FIRE
 RETARDANT. PLEASE PROVIDE FLAME
 CERTIFICATIONS TO THIS OFFICE UNDER
 SEPARATE COVER WITH LETTER.
 3) NO COMBUSTIBLES PERMITTED IN MAKE-UP
 AIR PLENUM AREA.
 4) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS, CEILINGS AND
 SEATING CONTAINED WITHIN THE SPACE.
 5) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS. ON JANUARY 11,2001, WRITER
 CALLED AND SPOKE TO TERRY MARCUM OF DK
 ARCHITECTS. HE WAS ADVISED THAT FIRE
 ALARM EQUIPMENT WOULD BE REQUIRED IN THE
 SPACE BUT A SEPARATE FIRE ALARM CONTROL
 PANEL WOULD NOT BE NECESSARY. SEPARATE
 PLANS AND PERMITS WOULD BE REQUIRED.
 6) THERE IS AN AREA NEAR BAR 116 THAT
 HAS ONLY ONE STEP AND IT APPEARS THAT
 AN EXIT SIGN DIRECTS PERSONS TO EXIT
 BY USING THE ONE STEP. CHANGES IN
 ELEVATION IN THE MEANS OF EGRESS LESS
 THAN 21 INCHES SHALL BE BY RAMPS. STAIRS
 WHEN USED TO BE A MINIMUM OF THREE AT
 SEVEN INCHES. IT ALSO APPEARS THAT THIS
 AREA IS NOT WIDE ENOUGH TO SUPPORT
 EXITING THROUGH IT. ON JANUARY 18,2001,
 WRITER ALSO SPOKE TO TERRY MARCUM ABOUT
 THIS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-14 Cont ID  
Sent By mcarsill Date 2000-11-13 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2000-11-13 Time 11:19 Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.THE
 ENTIRE SPACE IS TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THIS INCLUDES ALL
 COOLERS, FREEZERS, MECHANICAL AND
 STORAGE ROOMS.
 2) PROVISIONS ARE TO BE MADE FOR THE
 SEATING OF AT LEAST TWO HANDICAPPED
 PERSONS.
 3) IT APPEARS THAT THE WAITING AND HOST
 STATION SIT DIRECTLY IN FRONT OF MAIN
 ENTRY/EXIT DOORS.
 4) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS. STEPS WHEN
 USED ARE TO EQUAL AT LEAST THREE AT 7
 INCHES EACH.
 5) PLATFORMS TO COMPLY WITH FIRE AND
 BUILDING CODE REGULATIONS.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-05-22 Cont ID  
Sent By pkrauss Date 2001-05-22 Time 11:24 Rev Time 0.35
Received By pkrauss Date 2001-05-22 Time 11:24 Sent To  
Notes
2001-05-22 00:00:00AS BUILTS - MECH PERMIT 01030736

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-02-26 Cont ID  
Sent By pkrauss Date 2001-02-26 Time 09:27 Rev Time 0.45
Received By pkrauss Date 2001-02-26 Time 09:27 Sent To  
Notes
2001-02-26 00:00:00RELOCATED AHU, SERVICE PLATFORM AND
 LADDER.
  
 DUCT SMOKE DETECTOR TIED TO BUILDING
 FIRE ALARM SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-01-26 Cont ID  
Sent By ndenmark Date 2001-01-26 Time 08:03 Rev Time 0.50
Received By ndenmark Date 2001-01-26 Time 08:03 Sent To  
Notes
2001-01-26 00:00:00PRIOR COMMENTS ADDRESSED BY REVISIONS
 CHANGES WRITTEN IN BY ENGINEER.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-01-24 Cont ID  
Sent By ndenmark Date 2001-01-24 Time 12:56 Rev Time 0.50
Received By ndenmark Date 2001-01-24 Time 12:56 Sent To  
Notes
2001-01-24 00:00:00***************DENIED*******************
 1. PROVIDE DETAILS ON PLATFORM AREA FOR
 AHU -1 SHOWING CONSTRUCTION AND
 CLEARANCE DETAILS. SHOW COMPLIANCE WITH
 1997 SMC 304.2.1 ACCESSIBLILITY FOR
 SERVICE AND 304.4.1 MINIMUM CLEARANCE
 FOR ACCESS AND REMOVAL OF EQUIPMENT.
 MINIMUM SIZES FOR PASSAGEWAYS AND
 PLATFORM DIMENSIONS TO BE SHOWN ON PLAN.
  
 2. NOTE: SEPARATE PERMITS REQUIRED FOR
 HOOD, SUPPRESSION SYSTEM,AND
 COOLER/ FREEZERS
  
 3.SUBMIT TWO COMPLETE SETS OF SIGNED AND
 SEALED DRAWINGS FOR REVIEW AND
 PROCESSING. ONE SET FOR FIELD AND ONE
 SET FOR THE JOB. THIS SUBMITTAL
 INCLUDED TWO OLD REVISIONS AND ONLY ONE
 NEW SET OF REVISIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-12-07 Cont ID  
Sent By ndenmark Date 2000-12-07 Time 14:10 Rev Time 2.00
Received By ndenmark Date 2000-12-07 Time 14:09 Sent To  
Notes
2001-01-08 00:00:00***************DENIED*******************
  
 1. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
 3. 1997 SMC 610 REQUIRES LOCATION OF ALL
 FIRE DAMPERS ETC. TO BE CLEARLY SHOWN
 ON PLAN ALONG WITH THE INSTALLATION
 DETAILS BY DESIGNER. NO FIRE DAMPERS
 SHOWN ESP. AT SHAFT WALL PENETRATION.
 4. CLEAR UP CONFLICT BETWEEN EQUIPMENT
 SCHEDULE AND REFRIGERANT PIPE SCHEMATIC
 ON AC-3.
 5. SHOW CFM VALUE OF DROP IN FRONT OF
 BEER COOLER.
 6. INDICATE LOCATIONS OF RETURN AIR
 GRILLS INTO CEILING PLENUM.
 7. NOTE: NO COMBUSTIBLES ALLOWED IN
 RETURN AIR PLENUM ABOVE CEILING AREA.
 PER 1997 SMC 609.1.1 (INCLUDING NO PVC)
 8. DUCT SMOKE DETECTOR TO BE TIED TO
 BUILDING FIRE ALARM SYSTEM.
 9. PROVIDE ELEVATION SHOWING HOOD
 EXHAUST DUCT PITCH REQUIRED 1" PER FOOT
 SLOPE BACK TO HOOD.(BOTH HOODS).
 10. REQUIRED ENCLOSURE FOR GREASE
 EXHAUST DUCT TO BE FOR A SINGLE EXHAUST
 DUCT AND FOR NO OTHER PURPOSE PER 1997
 SMC 505.9. PLAN SHOWS OTHER DUCTS AND
 PIPING IN SHAFT. CLEARANCE FROM DUCT TO
 INSIDE OF ENCLOSURE TO BE MIN. 6" PER
 1997 SMC 505.9.1.
 11. ACCESS TO AHU TO BE PROVIDED FOR
 SERVICE AND CLEANING PER 304.3. PROVIDE
 MANUFACTURES REQUIRED CLEARANCE AREA
 TO BE DEDICATED FOR SERVICE AND CLEANING
 12. NOTE: SEPARATE PERMITS ARE REQUIRED
 FOR WALK IN COOLERS/FREEZERS AND HOOD
 SYSTEMS INCLUDED ASSOCIATED DUCT WORK.
 COMPLETE PLANS ARE REQUIRED AT TIME OF
 MECHANICAL PERMIT APPLICATION FOR THESE
 SYSTEMS PRIOR TO ANY WORK BEING DONE ON
 THEM.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-03-01 Cont ID  
Sent By jleech Date 2001-03-01 Time 07:33 Rev Time 1.00
Received By pschmitz Date 2001-03-01 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-01-25 Cont ID  
Sent By jleech Date 2001-01-25 Time 15:47 Rev Time 1.50
Received By jleech Date 2001-01-25 Time 15:47 Sent To  
Notes
2001-01-25 00:00:00PROVISO;
 REVISED DRAWINGS REQUIRED SHOWING
 HAND WRITTEN CHANGES MADE BY
 ARCHITECT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-01-25 Cont ID  
Sent By jleech Date 2001-01-25 Time 09:30 Rev Time 2.50
Received By jleech Date 2001-01-25 Time 09:30 Sent To  
Notes
2001-01-25 00:00:00FOLLOW UP OF PAUL SCHMITZ REVIEW ON
 12/3/2000.
  
 1.COVER SHEET, GOVERNING CODES, CHANGE
 TO; 94 STANDARD PLUMBING CODE AND 97
 STANDARD GAS CODE.
  
 2.OK
  
 3.CHANGE SHT. A-401 FROM HUB DRAIN TO
 FLOOR SINK.
  
 4.SHT. P1 LOCATION AND SIZE OF GREASE
 TRAP ( FOUR GREASE TRAPS ON PROPERTY
 SHOW LOCATION AND SIZE OF G.T. TO BE
 USED.)
  
 5.OK
  
 6.OK
 7.AIR CHAMBERS (ADD NOTE TO P-3 THAT AIR
 CHAMBERS TO BE READLY ACCESSIBLE AND
 RECHARGEABLE)
  
 8.97 SGC TABLE 305.4A SHOULD BE USED TO
 SIZE GAS PIPE. PIPE SIZE TO GRILL
 SHOULD 3". ADD TOTAL BTU'S 1,913,400.
  
 9.OK
  
 10.P-2 (IN FLOOR GAS LINE) CHANGE NOTE
 TO READ LIGHT WEIGHT CONCRETE.
  
 11.CHANGE (P-2 "PLUMBING FIXTURE
 SCHEDULE") WATER HEATER FROM L.P. TO
 NATERAL.
  
 SECOND REVIEW BY; JOHN LEECH
 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-12-03 Cont ID  
Sent By pschmitz Date 2000-12-03 Time 10:24 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWDENIED
 GOVERNING CODE:STD PLBG 94,STD GAS 97
 (1) COVER SHT STD. PLBG CODE 94.
 (2) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW & COMMENTS BEFORE PLBG APPR.
 CONTACT /954-958-5520 PLAN REVIEW.
 (3) SHT A-401 SQUARE BUFFET, HUB DRAINS,
 PROHIBITED, SEC 802 ALL INDIRECT TO
 FLOOR SINKS.
 (4) SHT P-1 LOCATION & SIZE OF EXISTING
 GREASE TRAP.
 (5) SHT P-1 DISHWASHER TO SANITARY
 SEWER, LOCAL ORD. # 2938-96
 (6) SHT P-1 BAR #116 HAND SINK, NO DRAIN
 SEC 701.2 ALL INDIRECT WASTE,6" OFF FLR.
 (7) SHT P-3 AIR CHAMBERS TO BE ACCESSIBL
 & RECHARGEABLE,SEC 607.8.3
 (8) SHT P-3 GAS DIAGRAM, SHOW TOT.BTU'S
 TOT.DEVELOPED LENGTH TO FARTHEST POINT.
 GAS PSI & TABEL USED TO SIZE PIPE.
 AUTO SOV TO BE BELOW CEILING WITH A
 UNION DOWN STREAM OF SOV, NFPA-54,5.5.4
 TYPE OF JOINTS WELDED OR SCREWED? 306.4
 SEDEMENT TRAPS ON DROPS,NFPA-54, 5.5.6
 (9) SHT AC-1 GAS WTR.HTR. RM #108 SHOW
 CALCULATIONS FOR COMBUSTION AIR.
 (10)SHT P-1 BURIED BUILDING PIPING,(GAS)
 308.3.2 NOT APPR.& NOT READLY ACCESSIBLE
 END OF COMMENTS
 CONTACT PAUL SCHMITZ 561-659- 8096X8233