| Plan Review Stops For Permit 00110398 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-05-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-05-07 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-04-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-04-04 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-04-04 00:00:00 | OUTDOOR PATIO REVISION | | | | | | 1] | | | PROVIDE COPYS OF SIGNED RESOLUTIONS. | | | 2] | | | SPECIFY ACCESSIBLE SEATING. CLARIFY | | | ACCESSIBLE ROUTE, APPROVED PLANS CALL | | | FOR RAMPS. | | | 3] | | | SUBMIT ELECTRICAL INFORMATION FOR | | | REVIEW. | | | 4] | | | SUPPLY INFORMATION FOR NEW BI-FOLD DOORS | | | AND AWNINGS. | | | | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 561-659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-01-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-23 |
Time |
12:56 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-23 00:00:00 | PROVISO: | | | 1)- A SITE PLAN SHOWING A PROTECTED | | | EGRESS FROM THE INTERIOR ENTRANCE. | | | 2)- SBC 1606.4.1 / 1707.4.1: GLAZED | | | OPENINGS WILL REQUIRE LARGE MISSLE | | | IMPACT RESISTANCE TESTING OR STORM | | | SHUTTER PROTECTION, DADE COUNTY PRODUCT | | | APPROVAL REPORT OR SBCCI REPORT ARE | | | ACCEPTABLE, A SEPERATE SSUB-PERMIT WILL | | | BE REQUIRED. 01/23/01 J. WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-01-19 |
Time |
08:44 |
Rev Time |
6.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-19 00:00:00 | BUILDING PLAN REVIEW: | | | 1). FL. ACC. CODE 4.3.2.2- PROVIDE AN | | | ACCESSIBLE ROUTE THROUGHOUT TO ALL | | | LEVELS. A) HORSESHOE BENCH RAISED SEAT- | | | ING 6 INCHES. | | | B) BAR AREA UP ONE STEP, NO RAMP | | | C) BENCH SEATS, RAISED WOOD | | | PLATFORM 1'-0". | | | 2) FL.ACC. CODE 4.3.2.2/SBC 1019.10.1.2 | | | 44" ACCESS AILES IN FRONT OF HORSESHOE | | | BENCH SEATING. | | | 3) DISCREPANCY- LS-1 VS A101- ENTRANCE | | | TO MENS /LADIES RESTROOMS. | | | 4) FL.ACC. CODE 4.1.3.6 MENS RESTROOM | | | ENTRY WILL REQUIRE 24" FOR SIDE EXIT. | | | 5) DOOR #2 IS LISTED AS USE AS A EXIT | | | DOOR, THIS IS PROHIBITED BY SBC 1012.1.2 | | | EGRESS DOORS SHALL BE SIDE SWINGING DOOR | | | DOORS SHALL SWING IN THE DIRECTION OF | | | EGRESS WHEN SERVING AN OCCUPANT LOAD OF | | | 50 OR MORE. | | | 6) PROVIDE SITE PLAN TO SHOW SECOND EXIT | | | IS PROTECTED THROUGH TO THE EXTERIOR. | | | 7) SBC TABLE 705.1.2- EXIT ACCESS DOOR | | | AT THE KITCHEN/ OFFICE AREA NEEDS TO | | | BE A 20 MINUTE RATED DOOR, | | | 8).SBC 1606.4.1/1707.4.1- ALL EXTERIOR | | | GLAZING TO HAVE LARGE MISSLE IMPACT TEST | | | ING BY DADE COUNTY OR SBCCI, REPORTS AS | | | WELL AS THE TECHNICAL DRAWINGS THAT | | | SUPPORT THE REPORT WILL BE REQUIRED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 | | | 9) THE THIRD SET OF PLANS DOES NOT HAVE | | | THE LIFE SAFETY PLAN IN IT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-01-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-01-08 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | | | | 1] | | | PROVIDE ACCESSIBILITY AT ENTRY AND AN | | | ACCESSIBLE ROUTE THOUGHOUT. | | | 2] | | | BI-FOLD DOORS AT PATIO AREA CANNOT BE | | | CONSIDERED AS AN APPROVED EGRESS TYPE | | | DOOR. | | | 3] | | | PROVIDE SITE PLAN TO SHOW SECOND EXIT | | | ISPROTECTED THRU TO THE OUTSIDE. | | | 4] | | | SUBMIT LIFE SAFETY,EGRESS PLAN. | | | 5] | | | EXPLAIN CLOSET,DOOR SHALL NOT OPEN INTO | | | PATH OF EGRESS. | | | 6] | | | DOOR #4 AT SERVICE CORRIDOR SHALL BE | | | RATED. | | | 7] | | | SUBMIT PRODUCT TESTING FORALL EXTERIOR | | | DOORS AND GLAZING. | | | 8] | | | PROVIDE MANUVERING CLEARENCE AT WOMENS | | | RESTROOM ENTRANCE,SEE SECT.4.13.6 | | | F.A.C.B.C.[FIG. 25B]. | | | 9] | | | LANDING AT BOTTOM OF RAMP LEADING TO BAR | | | AREA,SHALL BE CLEAR 48"X48", SEE F.A.C. | | | B.C. 4.8.4. | | | 10] | | | PROVIDE HANDRAILS ON BOTH SIDES OF RAMP | | | AT MAIN DINING ROOM, SEE F.A.C.B.C. 4.8. | | | 5. | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 561-659-8096 | | | #8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-05-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-05-14 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-05-14 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-01-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-17 |
Time |
20:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-17 |
Time |
20:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
20:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE; MISSING AIC RATING | | | OF PANELBOARD"K". PLEASE SHOW. | | | | | | 2)NOTE: PLEASE SEE LOADING OF BRANCH | | | BREAKERS. ALL CONTINUOUS LOADS ARE TO BE | | | SHOWN AT 125%. (LIGHTING ETC) PLEASE | | | SEE LOADS SHOWN, IF 125% IS ADDED THEN | | | LOAD EXCEEDS 80% OF BREAKER PER 384-16D | | | PLEASE SHOW ALL CONTINOUS LOADS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-04-05 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-04-05 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2001-04-05 00:00:00 | 1) AWNINGS ARE TO BE FIRE RETARDANT | | | IF PERSONS WILL BE UNDERNEATH IT. | | | 2) SEATING IS NOT TO INTERFERE WITH | | | EXITING FROM INSIDE THE ASSEMBLY | | | OCCUPANCY. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-25 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-25 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-11 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-11 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2001-01-11 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 2) ALL SUNBRELLA AWNINGS TO BE FIRE | | | RETARDANT. PLEASE PROVIDE FLAME | | | CERTIFICATIONS TO THIS OFFICE UNDER | | | SEPARATE COVER WITH LETTER. | | | 3) NO COMBUSTIBLES PERMITTED IN MAKE-UP | | | AIR PLENUM AREA. | | | 4) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION FOR WALLS, CEILINGS AND | | | SEATING CONTAINED WITHIN THE SPACE. | | | 5) NO FIRE ALARM EQUIPMENT SHOWN ON | | | DRAWINGS. ON JANUARY 11,2001, WRITER | | | CALLED AND SPOKE TO TERRY MARCUM OF DK | | | ARCHITECTS. HE WAS ADVISED THAT FIRE | | | ALARM EQUIPMENT WOULD BE REQUIRED IN THE | | | SPACE BUT A SEPARATE FIRE ALARM CONTROL | | | PANEL WOULD NOT BE NECESSARY. SEPARATE | | | PLANS AND PERMITS WOULD BE REQUIRED. | | | 6) THERE IS AN AREA NEAR BAR 116 THAT | | | HAS ONLY ONE STEP AND IT APPEARS THAT | | | AN EXIT SIGN DIRECTS PERSONS TO EXIT | | | BY USING THE ONE STEP. CHANGES IN | | | ELEVATION IN THE MEANS OF EGRESS LESS | | | THAN 21 INCHES SHALL BE BY RAMPS. STAIRS | | | WHEN USED TO BE A MINIMUM OF THREE AT | | | SEVEN INCHES. IT ALSO APPEARS THAT THIS | | | AREA IS NOT WIDE ENOUGH TO SUPPORT | | | EXITING THROUGH IT. ON JANUARY 18,2001, | | | WRITER ALSO SPOKE TO TERRY MARCUM ABOUT | | | THIS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-13 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER OR HYDRAULIC | | | CALCULATIONS PROVIDED WITH PLANS.THE | | | ENTIRE SPACE IS TO BE COMPLETELY FIRE | | | SPRINKLER PROTECTED. THIS INCLUDES ALL | | | COOLERS, FREEZERS, MECHANICAL AND | | | STORAGE ROOMS. | | | 2) PROVISIONS ARE TO BE MADE FOR THE | | | SEATING OF AT LEAST TWO HANDICAPPED | | | PERSONS. | | | 3) IT APPEARS THAT THE WAITING AND HOST | | | STATION SIT DIRECTLY IN FRONT OF MAIN | | | ENTRY/EXIT DOORS. | | | 4) ANY CHANGES IN ELEVATION LESS THAN | | | 21 INCHES SHALL BE BY RAMPS. STEPS WHEN | | | USED ARE TO EQUAL AT LEAST THREE AT 7 | | | INCHES EACH. | | | 5) PLATFORMS TO COMPLY WITH FIRE AND | | | BUILDING CODE REGULATIONS. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-05-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-22 |
Time |
11:24 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-05-22 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2001-05-22 00:00:00 | AS BUILTS - MECH PERMIT 01030736 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-02-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-26 |
Time |
09:27 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-02-26 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2001-02-26 00:00:00 | RELOCATED AHU, SERVICE PLATFORM AND | | | LADDER. | | | | | | DUCT SMOKE DETECTOR TIED TO BUILDING | | | FIRE ALARM SYSTEM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-01-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-26 |
Time |
08:03 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-01-26 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2001-01-26 00:00:00 | PRIOR COMMENTS ADDRESSED BY REVISIONS | | | CHANGES WRITTEN IN BY ENGINEER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-24 |
Time |
12:56 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-01-24 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2001-01-24 00:00:00 | ***************DENIED******************* | | | 1. PROVIDE DETAILS ON PLATFORM AREA FOR | | | AHU -1 SHOWING CONSTRUCTION AND | | | CLEARANCE DETAILS. SHOW COMPLIANCE WITH | | | 1997 SMC 304.2.1 ACCESSIBLILITY FOR | | | SERVICE AND 304.4.1 MINIMUM CLEARANCE | | | FOR ACCESS AND REMOVAL OF EQUIPMENT. | | | MINIMUM SIZES FOR PASSAGEWAYS AND | | | PLATFORM DIMENSIONS TO BE SHOWN ON PLAN. | | | | | | 2. NOTE: SEPARATE PERMITS REQUIRED FOR | | | HOOD, SUPPRESSION SYSTEM,AND | | | COOLER/ FREEZERS | | | | | | 3.SUBMIT TWO COMPLETE SETS OF SIGNED AND | | | SEALED DRAWINGS FOR REVIEW AND | | | PROCESSING. ONE SET FOR FIELD AND ONE | | | SET FOR THE JOB. THIS SUBMITTAL | | | INCLUDED TWO OLD REVISIONS AND ONLY ONE | | | NEW SET OF REVISIONS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-07 |
Time |
14:10 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
2000-12-07 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************DENIED******************* | | | | | | 1. PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89. | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | 3. 1997 SMC 610 REQUIRES LOCATION OF ALL | | | FIRE DAMPERS ETC. TO BE CLEARLY SHOWN | | | ON PLAN ALONG WITH THE INSTALLATION | | | DETAILS BY DESIGNER. NO FIRE DAMPERS | | | SHOWN ESP. AT SHAFT WALL PENETRATION. | | | 4. CLEAR UP CONFLICT BETWEEN EQUIPMENT | | | SCHEDULE AND REFRIGERANT PIPE SCHEMATIC | | | ON AC-3. | | | 5. SHOW CFM VALUE OF DROP IN FRONT OF | | | BEER COOLER. | | | 6. INDICATE LOCATIONS OF RETURN AIR | | | GRILLS INTO CEILING PLENUM. | | | 7. NOTE: NO COMBUSTIBLES ALLOWED IN | | | RETURN AIR PLENUM ABOVE CEILING AREA. | | | PER 1997 SMC 609.1.1 (INCLUDING NO PVC) | | | 8. DUCT SMOKE DETECTOR TO BE TIED TO | | | BUILDING FIRE ALARM SYSTEM. | | | 9. PROVIDE ELEVATION SHOWING HOOD | | | EXHAUST DUCT PITCH REQUIRED 1" PER FOOT | | | SLOPE BACK TO HOOD.(BOTH HOODS). | | | 10. REQUIRED ENCLOSURE FOR GREASE | | | EXHAUST DUCT TO BE FOR A SINGLE EXHAUST | | | DUCT AND FOR NO OTHER PURPOSE PER 1997 | | | SMC 505.9. PLAN SHOWS OTHER DUCTS AND | | | PIPING IN SHAFT. CLEARANCE FROM DUCT TO | | | INSIDE OF ENCLOSURE TO BE MIN. 6" PER | | | 1997 SMC 505.9.1. | | | 11. ACCESS TO AHU TO BE PROVIDED FOR | | | SERVICE AND CLEANING PER 304.3. PROVIDE | | | MANUFACTURES REQUIRED CLEARANCE AREA | | | TO BE DEDICATED FOR SERVICE AND CLEANING | | | 12. NOTE: SEPARATE PERMITS ARE REQUIRED | | | FOR WALK IN COOLERS/FREEZERS AND HOOD | | | SYSTEMS INCLUDED ASSOCIATED DUCT WORK. | | | COMPLETE PLANS ARE REQUIRED AT TIME OF | | | MECHANICAL PERMIT APPLICATION FOR THESE | | | SYSTEMS PRIOR TO ANY WORK BEING DONE ON | | | THEM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-03-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-01 |
Time |
07:33 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2001-03-01 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-25 |
Time |
15:47 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-01-25 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | PROVISO; | | | REVISED DRAWINGS REQUIRED SHOWING | | | HAND WRITTEN CHANGES MADE BY | | | ARCHITECT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-25 |
Time |
09:30 |
Rev Time |
2.50 |
| Received By |
jleech |
Date |
2001-01-25 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2001-01-25 00:00:00 | FOLLOW UP OF PAUL SCHMITZ REVIEW ON | | | 12/3/2000. | | | | | | 1.COVER SHEET, GOVERNING CODES, CHANGE | | | TO; 94 STANDARD PLUMBING CODE AND 97 | | | STANDARD GAS CODE. | | | | | | 2.OK | | | | | | 3.CHANGE SHT. A-401 FROM HUB DRAIN TO | | | FLOOR SINK. | | | | | | 4.SHT. P1 LOCATION AND SIZE OF GREASE | | | TRAP ( FOUR GREASE TRAPS ON PROPERTY | | | SHOW LOCATION AND SIZE OF G.T. TO BE | | | USED.) | | | | | | 5.OK | | | | | | 6.OK | | | 7.AIR CHAMBERS (ADD NOTE TO P-3 THAT AIR | | | CHAMBERS TO BE READLY ACCESSIBLE AND | | | RECHARGEABLE) | | | | | | 8.97 SGC TABLE 305.4A SHOULD BE USED TO | | | SIZE GAS PIPE. PIPE SIZE TO GRILL | | | SHOULD 3". ADD TOTAL BTU'S 1,913,400. | | | | | | 9.OK | | | | | | 10.P-2 (IN FLOOR GAS LINE) CHANGE NOTE | | | TO READ LIGHT WEIGHT CONCRETE. | | | | | | 11.CHANGE (P-2 "PLUMBING FIXTURE | | | SCHEDULE") WATER HEATER FROM L.P. TO | | | NATERAL. | | | | | | SECOND REVIEW BY; JOHN LEECH | | | 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-12-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-03 |
Time |
10:24 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | GOVERNING CODE:STD PLBG 94,STD GAS 97 | | | (1) COVER SHT STD. PLBG CODE 94. | | | (2) DEPT OF HOTEL BUSINESS REGULATION | | | PLAN REVIEW & COMMENTS BEFORE PLBG APPR. | | | CONTACT /954-958-5520 PLAN REVIEW. | | | (3) SHT A-401 SQUARE BUFFET, HUB DRAINS, | | | PROHIBITED, SEC 802 ALL INDIRECT TO | | | FLOOR SINKS. | | | (4) SHT P-1 LOCATION & SIZE OF EXISTING | | | GREASE TRAP. | | | (5) SHT P-1 DISHWASHER TO SANITARY | | | SEWER, LOCAL ORD. # 2938-96 | | | (6) SHT P-1 BAR #116 HAND SINK, NO DRAIN | | | SEC 701.2 ALL INDIRECT WASTE,6" OFF FLR. | | | (7) SHT P-3 AIR CHAMBERS TO BE ACCESSIBL | | | & RECHARGEABLE,SEC 607.8.3 | | | (8) SHT P-3 GAS DIAGRAM, SHOW TOT.BTU'S | | | TOT.DEVELOPED LENGTH TO FARTHEST POINT. | | | GAS PSI & TABEL USED TO SIZE PIPE. | | | AUTO SOV TO BE BELOW CEILING WITH A | | | UNION DOWN STREAM OF SOV, NFPA-54,5.5.4 | | | TYPE OF JOINTS WELDED OR SCREWED? 306.4 | | | SEDEMENT TRAPS ON DROPS,NFPA-54, 5.5.6 | | | (9) SHT AC-1 GAS WTR.HTR. RM #108 SHOW | | | CALCULATIONS FOR COMBUSTION AIR. | | | (10)SHT P-1 BURIED BUILDING PIPING,(GAS) | | | 308.3.2 NOT APPR.& NOT READLY ACCESSIBLE | | | END OF COMMENTS | | | CONTACT PAUL SCHMITZ 561-659- 8096X8233 |
|
|