| Plan Review Stops For Permit 00110376 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-11-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-08 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-08 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS IN HALLWAYS ARE TO | | | BE INSTALLED AT LEAST THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT BUILDING. | | | 3) FIRE ALARM SYSTEM AND FIRE SPRINKLER | | | SYSTEM TO BE MONITORED BY A LICENSED | | | UL LISTED CENTRAL STATION. | | | 4) ENTIRE SYSTEM TO BE TESTED WITH THE | | | FIRE RESCUE DEPARTMENT. | | | 5) SYSTEM TO BE INSTALLED IN ACCORDANCE | | | WITH NFPA 72. | | | 6) THE SINGLE STATION SMOKE DETECTORS | | | INSTALLED WITHIN THE APARTMENTS ARE TO | | | BE AUDIBLE WITHIN THE SLEEPING ROOMS OF | | | THAT UNIT. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|