Plan Review Details - Permit 00110364
Plan Review Stops For Permit 00110364
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-04-11 Cont ID  
Sent By hpiskura Date 2001-04-11 Time 14:44 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-12-08 Cont ID  
Sent By hpiskura Date 2000-12-08 Time 14:50 Rev Time 0.00
Received By hpiskura Date 2000-12-05 Time 10:15 Sent To  
Notes
2001-01-08 00:00:00LETTER W/ APPLICATION

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-01-17 Cont ID  
Sent By btrobaug Date 2002-01-17 Time 15:23 Rev Time 1.00
Received By btrobaug Date 2002-01-17 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 10:13 Sent To  
Notes
2002-01-14 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT THE BURIAL
 DEPTH FOR SERVICE ENTRANCE CONDUCTORS
 ARE SHOWN AT TWO DIFFERENT DEPTHS ON
 FRONT PAGE ETC-0.? PLEASE SEE 300-5
 FOR MIN 24" DEPTH.
  
 2)NOTE: PLEASE SEE ETC-5, PLEASE CLARIFY
 SIZING OF EQUIPMENT/ AIC RATINGS ETC
 ON LINE DIAGRAM SHOWN ON ETC-5, PLEASE
 NOTE NO DETAILS WERE GIVEN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-02 Cont ID  
Sent By dpalmer Date 2001-11-02 Time 10:48 Rev Time 0.00
Received By dpalmer Date 2001-11-02 Time 10:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-04-06 Cont ID  
Sent By dpalmer Date 2001-04-06 Time 16:46 Rev Time 0.00
Received By dpalmer Date 2001-04-06 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 22:40 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 22:40 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. (LIGHTING ETC)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 ETX 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-12-12 Cont ID  
Sent By mgonzale Date 2000-12-12 Time 06:58 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 OVERALL SITE PLAN HAS BEEN APPROVED
 THROUGH PUBLIC UTILITIES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-04-10 Cont ID  
Sent By mcarsill Date 2001-04-10 Time 09:36 Rev Time 0.00
Received By mcarsill Date 2001-04-10 Time 09:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-11-13 Cont ID  
Sent By mcarsill Date 2000-11-13 Time 09:35 Rev Time 0.00
Received By mcarsill Date 2000-11-13 Time 09:35 Sent To  
Notes
2001-01-08 00:00:001) CLEARLY IDENTIFY FIRE HYDRANT
 LOCATIONS IN RELATION TO NEW BUILDING.
 2) PLEASE INDICATE ROOF COVERING
 CLASSIFICATION.
 3) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 4) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. CUT SHEETS, WIRING
 DIAGRAM AND FLOOR PLANS ARE TO BE
 SUBMITTED UNDER SEPARATE PERMIT.
 5) PROVIDE COMPLETE PLANS AND PERMIT FOR
 THE INSTALLATION OF THE HOOD,DUCT AND
 EXTINGUISHING SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-04-05 Cont ID  
Sent By pkrauss Date 2001-04-03 Time 14:36 Rev Time 0.30
Received By pkrauss Date 2001-04-03 Time 13:26 Sent To  
Notes
2001-04-03 00:00:00******************PROVISO***************
  
  
 1.EXHAUST DUCT SHALL BE A MINIMUM OF
 10' ADJACENT OF THE FRESH AIR
 INTAKE.
  
 2.A MINIMUM OF 18" IS REQURIED
 BETWEEN ROOF SURFACE AND TO
 BOTTOM OF SUPPORT TO THE CONDENSER
 UNIT STAND AS PER THE AMMENDED 1997
 SMC 304.2.5.
  
 3.ADDITIONAL PLANS & PERMIT REQUIRED
 FOR HOOD, GREASE AND SUPPLY DUCT.
  
 4.ADDITIONAL PLANS & PERMIT REQUIRED
 FOR THE FIRE SUPPRESSION SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 10:56 Rev Time 0.50
Received By ndenmark Date 2000-12-14 Time 10:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-07-29 Cont ID  
Sent By jleech Date 2001-07-29 Time 06:03 Rev Time 1.00
Received By jleech Date 2001-07-29 Time 06:03 Sent To  
Notes
2001-07-29 00:00:00GAS PIPE PLAN HAS BEEN APPROVED.

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-07-22 Cont ID  
Sent By jleech Date 2001-07-22 Time 09:16 Rev Time 1.50
Received By jleech Date 2001-07-22 Time 09:16 Sent To  
Notes
2001-07-22 00:00:00DENIED;
  
 1.IS BLACK IRON WELDED OR SCREW PIPE OR
 BOTH? PLEASE SPECIFY ON PLANS.
  
 2.(GAS RISER DIAGRAM) EQUIPMENT UNDER
 THE HOOD, SIZE STUBOUTS FOR EACH
 APPLIANCE. 184000 BTU >1 1/4" ETC. AND
 SHOW ACCESSIBLE STOPS FOR EACH
 APPLIANCE. IS BOTTOM PIPE 2" ALSO
 PLEASE MARK ON PLANS.
  
 3.PLEASE SUBMIT MANUFACTOR'S SPECIFCA-
 TION SHEETS FOR THE WATER HEATER. IS
 HEATER FAN DRIVEN OR NATURALLY VENTED?
 WATER HEATER "A" DETAIL ON PAGE PTC-01
 SHOWS A VENT AT BOTTOM OF HEATER NONE
 AT THE TOP. PAGE PTC-02 SHOWS AIR MAKE
 UP CAULKULATIONS FOR NATURAL MAKE UP
 AIR.
  
 GAS PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-05-12 Cont ID  
Sent By jleech Date 2001-05-12 Time 12:44 Rev Time 2.50
Received By jleech Date 2001-05-12 Time 12:44 Sent To  
Notes
2001-05-12 00:00:00PROVISO;
  
 REVISED GAS DRAWINGS REQUIRED BEFORE
 GAS PERMIT IS ISSUED.
  
 CORRECTIONS REQUIRED FOR GAS DRAWING;
  
 1.ISOMETRIC AND FLAT DRAWINGS, PIPE
 SIZES ARE NOT THE SAME.
 2.IS BLACK IRON TREADED OR WELDED?
 3.DRIP LEG REQUIRED FOR REST. EQUIP
 MENT.
 4.SHUTOFF VALVES REQUIRED FOR EACH
 GAS APPLIANCE AND FUTURE BBQ GAS
 PIPE.
 5. SHUTOFF VALUES MUST BE
 ACCESSIBLE.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-04-08 Cont ID  
Sent By pschmitz Date 2001-04-08 Time 14:34 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-04-08 00:00:00PLUMBING PLAN REVIEWDENIED
 CODE REFERENCE SPC 94
 (1)SHT PTC-02 CONTACT DEPT OF HOTEL BUS-
 INESS REGULATION, PLAN REVIEW,FOR THIER
 COMMENTS, BEFORE PLBGREVIEW APPROVAL.
 954-958-5520,3 SETS OF PLANS.
 (2)SHT PTC-02 GREASE WASTE: COMPLY WITH
 SEC 921 COMBINATION WASTE & VENT SYSTEM
 EVERY PIPE SHALL BE 2 PIPE SIZES LARGER
 THAN REQUIRED,MAIN LINE 4", BRANCHES3",
 MINIMUM VENT SIZE 2",UPSTREAM,DOWNSTREAM
 (3)SHT PTC-02 SEC 804.1, ALL INDIRECT
 WASTE TO FLOOR SINKS,6" OFF FLOOR.
 (4)SHT PTC-02 SEE ATTACHED GAS PERMIT
 APPLICATION REQUIRMENTS,.
 (5)SHT LP-02 PUBLIC REST RM. FACILITIES,
 TAB 407,SHOW CALCULATIONS FOR NUMBER OF
 FIXTURES REQUIRED.
 (6) SHT PTC-01 SHOW SEATING DIAGRAM FOR
 NUMBER OF PERSONS,NUMBER OF MEALS SERVED
 (7)SHT PTC-01 CONTACT WPB REGIONAL SEWER
 TREATMENT PLANT,RODNEY COMPO,837-4074
 FOR GREASE TRAP SIZE, AND STANDARDS.
 (8) SHT PTC -02 BACK FLOW PREVENTER
 REQUIRED ON DOMESTIC WATER SERVICE,
 SPC-94 SEC 601.6
 END OF COMMENTS, PAULSCHMITZ
 QUESTIONS561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-11-27 Cont ID  
Sent By jleech Date 2000-11-27 Time 10:26 Rev Time 2.00
Received By pschmitz Date 2000-11-27 Time 10:26 Sent To  
Notes
2001-01-08 00:00:001.HANDICAP STALLS IN-SWING DOOR MUST NOT
 INTRUDE ON CLEAR FLOOR SPACE OF
 LAVITORY.
  
 2.WASTE RECEPTACLE AND BABY CHANGING
 UNIT MUST NOT INTRUDE INTO CLEAR FLOOR
 SPACE OF LAVITORY.
  
 3.HANDICAP URINNAL HEIGHT IS 17" MAX.
 [ATC-4 #4]
  
 4.THE FOLLOWING ITEMS ARE REQUIRED FOR
 PLUMBING REVIEW;
 A.SANITARY RISER DIAGRAMS;
 GREASY WASTE AND SANITARY FOR
 RESTAURANT AND BATHROOMS.
 B.WATER RISERS FOR RESTAURANT AND
 BATHROOMS.
 C.RESTAURANT EQUIPMENT SCHEDULE.
 D.FLOOR PLAN OF RESTAURANT SHOWING
 EQUIPMENT LAYOUT AND LINE DRAWING
 OF SANITARY
 E.LINE DRAWING OF BATHROOMS SAN.
 PIPING.
 F.DRINKING FAUNTAIN LOCATION.
 G. GREASE TANK SIZE AND LOCATION.
 TO BE APPROVED BY RODNEY COMPO.
 CITY ORDINANCE #2938-96.
  
 JOHN LEECH
 PLUMBING PLAN REVIEW
 (561)659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-04-24 Cont ID  
Sent By sgraham Date 2001-04-24 Time 13:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***